Error Code

Abnormal point and detection method 

Cause

Countermeasure

P9

Pipe temperature thermistor / Condenser 
/ Evaporator (TH5)

1

 The unit is in 3-minute resume protec-

tion mode if short/open of thermistor is 
detected. Abnormal if the unit does not 
get back to normal within 3 minutes. (The 
unit returns to normal operation, if it has 
been reset normally.)

2

 Constantly detected during cooling, 

drying, and heating operation (except 
defrosting)

  Short: 90°C or more
  Open: -40°C or less

1

 Defective thermistor 

 characteristics

2

 Contact failure of  connector 

(CN29) on the indoor controller 
board (Insert failure)

3

 Breaking of wire or contact 

  failure of thermistor wiring

4

 Temperature of thermistor is 

90°C or more or -40°C or less 
caused by defective refrigerant 
circuit.

5

 Defective indoor controller 

board

1

Check resistance value of thermistor.

 

For characteristics, refer to (P1) above.

2

 Check contact failure of  connector (CN29) 

on the indoor controller board. 

  Refer to 6-5.
  Turn the power on and check restart after 

inserting connector again.

4

 Operate in test run mode and check pipe 

<condenser/evaporator> temperature with 
outdoor controller circuit board. If pipe 

  <condenser/evaporator> temperature is 

extremely low (in cooling mode) or high (in 
heating mode), refrigerant circuit may have 
defect.

5

 Operate in test run mode and check pipe 

<condenser/evaporator> temperature with 
outdoor control circuit board. If there is 

  extreme difference with actual pipe 
  <condenser/evaporator> temperature replace 

indoor controller board.

  There is no abnormality if none of above 

comes within the unit.

  Turn  the power off and on again to operate.

E0

or

E4

Remote controller transmission 
error(E0)/signal receiving error(E4)

1

 Abnormal if main or sub remote con-

troller cannot receive any transmission 
normally from indoor unit of refrigerant 
address “0” for 3 minutes.

  (Error code : E0)

2

 Abnormal if sub-remote controller could 

not receive for any signal for 2 minutes. 
(Error code: E0) 

1

 Abnormal if indoor controller board 

cannot receive normally any data from 
remote controller board or from other 
indoor controller board for 3 minutes. 
(Error code: E4)

2

 Indoor controller board cannot receive 

any signal from remote controller for 2 
minutes. (Error code: E4)

1

 Check disconnection or looseness of indoor 

unit or transmission wire of remote controller.

2

 Set one of the remote controllers “main”,

  if there is no problem with the action above.

3

 Check wiring of remote controller.

• Total wiring length: max. 500 m
  (Do not use cable × 3 or more)
• The number of connecting indoor units: 

max. 16 units

• The number of connecting remote control-

ler: max. 2 units

When the above-mentioned problem of 

1

~

are not seen.

4

 Diagnose remote controllers.

a) When “RC OK” is displayed,

remote controllers have no problem. 
Turn the power off, and on again to check. 
If abnormality generates again, replace 
indoor controller board.

b) When “RC NG” is displayed,

replace remote controller.

c) When “RC E3”or “ERC 00-66” is dis-

played, noise may be causing abnormality.

E3

or

E5

Remote controller transmission 
error(E3)/signal receiving error(E5)

1

 Abnormal if remote controller could not 

find blank of transmission path for 6 sec-
onds and could not transmit.

    (Error code: E3)  

2

 Remote controller receives transmitted 

data at the same time, compares the 
data, and when detecting it, judges 

  different data to be abnormal 30 
  continuous times. (Error code: E3) 

1

 Abnormal if indoor controller board could 

not find blank of transmission path.

   (Error code: E5)   

2

 Indoor controller board receives trans-

mitted data at the same time, compares 
the data,and when detecting it, judges 
different data to be abnormal 30 

  continuous times. (Error code: E5)

1

 Set a remote controller to main, and the 

other to sub.

2

 Remote controller is connected with only one 

indoor unit.

3

 The address changes to a separate setting.

4

~

Diagnose remote controller.

a) When “RC OK” is displayed, remote con-

trollers have no problem.

   Turn the power off, and on again to check.
   When becoming abnormal again, replace 

indoor controller board.

b) When “RC NG” is displayed, replace 

remote controller.

c) When “RC E3”or “ERC 00-66” is dis-

played, noise may be causing abnormality.

1

 Contact failure at transmission 

wire of remote controller

2

 All remote controllers are set 

as “sub” remote controller. In 
this case, E0 is displayed on 
remote controller, and E4 is 
displayed at LED (LED1, LED2) 
on the outdoor controller circuit 
board.

3

 Miswiring of remote controller

4

 Defective transmitting/receiving 

circuit of remote controller

5

 Defective transmitting/receiving 

circuit of indoor controller board 
of refrigerant address “0”

6

 Noise has entered into the 

transmission wire of remote 
controller.

1

 2 remote controllers are set as 

“main.”   

    (In case of 2 remote con-
     trollers)

2

 Remote controller is connected 

with 2 indoor units or more.

3

 Repetition of refrigerant 

address

4

 Defective transmitting/receiving 

circuit of remote controller

5

 Defective transmitting/receiving 

circuit of indoor controller board

6

 Noise has entered into trans-

mission wire of remote control-
ler.

In case of checking pipe temperature 
with outdoor controller circuit board, 
be sure to connect A-control service 
tool (PAC-SK52ST).

(

)

Содержание Mr.SLIM SLZ-KA25VAQ

Страница 1: ...ASSEMBLY PROCEDURE 25 December 2010 No OCH493 WIRED REMOTE CONTROLLER Option Indoor unit Model names Service Ref SLZ KA25VAQ SLZ KA25VAQ TH SLZ KA35VAQ SLZ KA35VAQ TH SLZ KA50VAQ SLZ KA50VAQ TH INDOOR...

Страница 2: ...orizontal airflow automatically during cooling or dehumidifying Air Intake Inhales air from room Indoor Unit SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH 1 PART NAMES AND FUNCTIONS Note The phrase Wir...

Страница 3: ...the cover ON OFF button Fan Speed button Filter button Enter button Test Run button Check button Clear button Airflow Up Down button Louver button Operation button To return operation number Ventilat...

Страница 4: ...is off Temperature Setting Shows the target temperature Day of Week Shows the current day of the week Time Timer Display Shows the current time unless the simple or Auto Off timer is set If the simpl...

Страница 5: ...tance at 26 Width Height Depth Weight Air direction Sound level High Medium Low Fan speed High Medium Low Fan speed regulator Thermistor TH1 at 25 Thermistor TH2 at 25 Thermistor TH5 at 25 h A A W kW...

Страница 6: ...D PRESSURE LEVEL dB 0 dB 0 0002 bar BAND CENTER FREQUENCIES Hz SLZ KA50VAQ TH High Medium 39 SPL dB 34 LINE 50Hz NOTCH Low 30 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE...

Страница 7: ...M Air intake grille 55 35 35 55 Auto vane Grille Air intake hole Air intake hole Air outlet hole Air outlet hole 301 301 377 377 650 650 V M V M V M Detail drawing of fresh air intake Ceiling surface...

Страница 8: ...8 WIRED REMOTE CONTROLLER Unit mm 130 19 120 43 5 Option...

Страница 9: ...9 9 WIRING DIAGRAM 4 SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH...

Страница 10: ...Condenser evaporator temperature thermistor TH5 Room temperature thermistor TH1 Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe con...

Страница 11: ...ors hold the housing of the connector DO NOT pull the lead wires Lead wire PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE ERROR CODE ERROR CO...

Страница 12: ...mptom Remark Number of times Wireless remote controller Wired remote controller Beeper sounds OPERATION INDICATOR lamp blinks Check code Number of times Wireless remote controller Wired remote control...

Страница 13: ...terminal block Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote controller wire short Note Operation is not possible for about 30 seconds after cancellation of...

Страница 14: ...re with remote controller in test run mode If pipe liquid temperature is extremely low in cooling mode or high in heating mode refrigerant circuit may have defect 5 Check pipe liquid temperature with...

Страница 15: ...oling or drying mode 1 Check clogging of the filter 2 Remove blockage 4 Measure the resistance of fan motor s winding Measure the output voltage of fan s connector FAN on the indoor controller board W...

Страница 16: ...Do not use cable 3 or more The number of connecting indoor units max 16 units The number of connecting remote control ler max 2 units When the above mentioned problem of 1 3 are not seen 4 Diagnose re...

Страница 17: ...y of the remote controller control board Error code E1 2 Abnormal if the clock function of remote controller cannot be normally operated Error code E2 1 Defective remote controller 1 Replace remote co...

Страница 18: ...it 1 Mis setting of refrigerant address for outdoor unit There is no unit corresponding to refrigerant address 0 1 Check the setting of refrigerant address for outdoor unit Set the refrigerant address...

Страница 19: ...5 1 Indoor power board SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH CNSK Connect to the indoor controller board CNDK between 1 to 3 220 240V AC CN2S Connect to the indoor controller board CN2D betwee...

Страница 20: ...ontrol signal 13V pulse input 1 3 4 Operation indicator 13VDC 3 3 5 Malfunction indicator 13VDC 3 CN6V Vane motor output MV CN90 Connect to the wire less remote controller board CNB CN31 Drain sensor...

Страница 21: ...ature 10 C 30 C Pipe temperature thermistor liquid TH2 Indoor fan motor MF Check method and criterion Part name Normal KA25VAQ Normal WHT BLK BLK BLU BLU YLW BRN RED 386 428 81 91 28 32 157 174 KA35VA...

Страница 22: ...20 6 3k 25 5 2k 30 4 3k 40 3 0k Thermistor R0 6 0k 5 Fixed number of B 3390 2 Rt 6exp 3390 0 6 0k 10 3 9k 20 2 6k 25 2 2k 30 1 8k 40 1 3k 60 0 6k Thermistor for lower temperature 1 273 t 1 273 1 273...

Страница 23: ...controller board and relay must be within 10m Be sure to secure insulation material by tape etc 5 Green Yellow Orange Connector 5P Indoor unit side Multiple remote controller adapter PAC SA88HA E Be...

Страница 24: ...d connector with the plastic tape Vane motor Horizontal vane Connector Unlocking button Vane motor 3 Set the vertical vane of the air outlet by hand slowly within the range in the table below Measured...

Страница 25: ...air intake grille 2 Remove the 3 screws of fan guard Air intake grille knob 3 Removing the panel 1 Remove the air intake grille Refer to step 1 Corner panel See Figure 2 1 Remove the screw of the corn...

Страница 26: ...nd the fan 2 from the indoor controller board 6 Remove the 3 screws fixed to the piping cover and remove the piping cover See Photo 9 7 Remove the 6 screws fixed to the flat plate and remove the flat...

Страница 27: ...hoto 9 from the heat exchanger and remove the heat exchanger 9 Removing the drain pump DP and drain sensor DS 1 Remove the panel Refer to step 3 2 Remove the drain pan Refer to step 6 3 Remove the 2 s...

Страница 28: ...MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN CCopyright 2010 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Dec 2010 No OCH493 Made in Japan New publication effective Dec 2010 Specifications subj...

Отзывы: