17

E6

1

 Contact failure, short circuit or, 

miswiring (converse wiring) of 
indoor/outdoor unit connecting 
wire

2

 Defective transmitting/receiv-

ing circuit of indoor controller 
board

3

 Defective transmitting/receiv-

ing circuit of indoor controller 
board

4

 Noise has entered into indoor/ 

outdoor unit connecting wire.

Check disconnection or looseness of indoor/ 
outdoor unit connecting wire of indoor unit or 
outdoor unit.

    Check all the units in case of twin indoor unit 

system.

2

-

4

 Turn the power off, and on again to check. 

If abnormality generates again, replace 
indoor controller board or outdoor 

 

controller circuit board.

* Other indoor controller board may have 

defect in case of twin indoor unit system.

E7

Indoor/outdoor unit communication 
error (Transmitting error)

Abnormal if “1” receiving is detected 30 
times continuously though indoor controller 
board has transmitted “0”.

1

 Defective transmitting receiving 

circuit of indoor controller board 

2

 Noise has entered into power 

supply.

3

 Noise has entered into outdoor 

control wire.

1

-

3

 Turn the power off, and on again to check. 

If abnormality generates again, replace 
indoor controller board.

Indoor/outdoor unit communication 
error (Signal receiving error)

1

 Abnormal if indoor controller board 

  cannot receive any signal normally for 6 

minutes after turning the power on.

2

 Abnormal if indoor controller board 

  cannot receive any signal normally for 3 

minutes. 

3

 Consider the unit abnormal under the fol-

lowing condition: When 2 or more indoor 
units are connected to one 

  outdoor unit, indoor controller board 
  cannot receive a signal for 3 minutes 

from outdoor controller circuit board, a 
signal which allows outdoor controller 
circuit board to transmit signals. 

Error Code

Abnormal point and detection method 

Cause

Countermeasure

Fb

Indoor controller board

Abnormal if data cannot be normally read 
from the nonvolatile memory of the indoor 
controller board.

1

 Defective indoor controller 

board

1

 Replace indoor controller board.

E1

or

E2

Remote controller control board

1

 Abnormal if data cannot be normally 

read from the nonvolatile memory of the 
remote controller control board.

    (Error code: E1)

2

 Abnormal if the clock function of remote 

controller cannot be normally operated.

    (Error code: E2)

1

 Defective remote controller

1

 Replace remote controller.

PA

(2502)
(2500)

 Forced compressor stop 
 (due to water leakage abnormality)

1

 When the intake temperature subtracted 

with liquid pipe temperature is less than 
-10°C, drain sensor detects whether it is 
soaked in the water or not at the interval 
of 90 seconds. (Drain pump will start 
operating when the drain sensor detects 
to be soaked in the water.)

2

 The unit has a water leakage abnormal-

ity when the following conditions, a) 
and b), are satisfied while the above-
mentioned detection is performed.

    a) The drain sensor detects to be 
        soaked in the water 10 times in a row.
    b) The intake temperature subtracted 

with liquid pipe temperature is detect-
ed to be less than -10°C for a total of 
30 minutes. 

(When the drain sensor detects to 
be NOT soaked in the water, the 
detection record of a) and b) will be 
cleared.)

3

 The drain sensor detection is performed 

    in operations other than cooling. (When 
    the unit stops operating, during heating 
    or fan operation, when the unit stops 
    because of some abnormality) 
*Once the water leakage abnormality is 
 detected, abnormality state will not be 
 released until the main power is reset.

1

  Drain pump trouble

2

  Drain defective

  · Drain pump clogging
  · Drain pipe clogging

3

  Open circuit of drain sensor 

   side heater

4

  Contact failure of drain sensor 

     connector

5

  Dew condensation on drain  

     sensor
  · Drain water trickles along 
    lead wire.
  · Drain water waving due to filter 
    clogging

6

  Extension piping connection 

   difference at twin, triple,
   quadruple system

7

  Miswiring of indoor/outdoor

   connecting at twin, triple,
   quadruple system

8

  Room temperature thermistor/

   liquid pipe temperature themis-
   tor detection is defective.

1

 Check the drain pump. 

Performance

2

 Please check whether water can be drained.

3

 Check the resistance of the drain sensor 

    side heater.

4

 Check the connector contact failure.

5

 Check the drain sensor lead wire mounted.

  

Check the filter clogging.

6

 Check the piping connection.

7

 Check the indoor/outdoor connecting wires.

8

 Check the room temperature display of 

remote controller.

Check the indoor liquid pipe temperature dis-
play of outdoor controller board.

Содержание Mr.SLIM SLZ-KA25VAQ

Страница 1: ...ASSEMBLY PROCEDURE 25 December 2010 No OCH493 WIRED REMOTE CONTROLLER Option Indoor unit Model names Service Ref SLZ KA25VAQ SLZ KA25VAQ TH SLZ KA35VAQ SLZ KA35VAQ TH SLZ KA50VAQ SLZ KA50VAQ TH INDOOR...

Страница 2: ...orizontal airflow automatically during cooling or dehumidifying Air Intake Inhales air from room Indoor Unit SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH 1 PART NAMES AND FUNCTIONS Note The phrase Wir...

Страница 3: ...the cover ON OFF button Fan Speed button Filter button Enter button Test Run button Check button Clear button Airflow Up Down button Louver button Operation button To return operation number Ventilat...

Страница 4: ...is off Temperature Setting Shows the target temperature Day of Week Shows the current day of the week Time Timer Display Shows the current time unless the simple or Auto Off timer is set If the simpl...

Страница 5: ...tance at 26 Width Height Depth Weight Air direction Sound level High Medium Low Fan speed High Medium Low Fan speed regulator Thermistor TH1 at 25 Thermistor TH2 at 25 Thermistor TH5 at 25 h A A W kW...

Страница 6: ...D PRESSURE LEVEL dB 0 dB 0 0002 bar BAND CENTER FREQUENCIES Hz SLZ KA50VAQ TH High Medium 39 SPL dB 34 LINE 50Hz NOTCH Low 30 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE...

Страница 7: ...M Air intake grille 55 35 35 55 Auto vane Grille Air intake hole Air intake hole Air outlet hole Air outlet hole 301 301 377 377 650 650 V M V M V M Detail drawing of fresh air intake Ceiling surface...

Страница 8: ...8 WIRED REMOTE CONTROLLER Unit mm 130 19 120 43 5 Option...

Страница 9: ...9 9 WIRING DIAGRAM 4 SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH...

Страница 10: ...Condenser evaporator temperature thermistor TH5 Room temperature thermistor TH1 Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe con...

Страница 11: ...ors hold the housing of the connector DO NOT pull the lead wires Lead wire PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE ERROR CODE ERROR CO...

Страница 12: ...mptom Remark Number of times Wireless remote controller Wired remote controller Beeper sounds OPERATION INDICATOR lamp blinks Check code Number of times Wireless remote controller Wired remote control...

Страница 13: ...terminal block Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote controller wire short Note Operation is not possible for about 30 seconds after cancellation of...

Страница 14: ...re with remote controller in test run mode If pipe liquid temperature is extremely low in cooling mode or high in heating mode refrigerant circuit may have defect 5 Check pipe liquid temperature with...

Страница 15: ...oling or drying mode 1 Check clogging of the filter 2 Remove blockage 4 Measure the resistance of fan motor s winding Measure the output voltage of fan s connector FAN on the indoor controller board W...

Страница 16: ...Do not use cable 3 or more The number of connecting indoor units max 16 units The number of connecting remote control ler max 2 units When the above mentioned problem of 1 3 are not seen 4 Diagnose re...

Страница 17: ...y of the remote controller control board Error code E1 2 Abnormal if the clock function of remote controller cannot be normally operated Error code E2 1 Defective remote controller 1 Replace remote co...

Страница 18: ...it 1 Mis setting of refrigerant address for outdoor unit There is no unit corresponding to refrigerant address 0 1 Check the setting of refrigerant address for outdoor unit Set the refrigerant address...

Страница 19: ...5 1 Indoor power board SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH CNSK Connect to the indoor controller board CNDK between 1 to 3 220 240V AC CN2S Connect to the indoor controller board CN2D betwee...

Страница 20: ...ontrol signal 13V pulse input 1 3 4 Operation indicator 13VDC 3 3 5 Malfunction indicator 13VDC 3 CN6V Vane motor output MV CN90 Connect to the wire less remote controller board CNB CN31 Drain sensor...

Страница 21: ...ature 10 C 30 C Pipe temperature thermistor liquid TH2 Indoor fan motor MF Check method and criterion Part name Normal KA25VAQ Normal WHT BLK BLK BLU BLU YLW BRN RED 386 428 81 91 28 32 157 174 KA35VA...

Страница 22: ...20 6 3k 25 5 2k 30 4 3k 40 3 0k Thermistor R0 6 0k 5 Fixed number of B 3390 2 Rt 6exp 3390 0 6 0k 10 3 9k 20 2 6k 25 2 2k 30 1 8k 40 1 3k 60 0 6k Thermistor for lower temperature 1 273 t 1 273 1 273...

Страница 23: ...controller board and relay must be within 10m Be sure to secure insulation material by tape etc 5 Green Yellow Orange Connector 5P Indoor unit side Multiple remote controller adapter PAC SA88HA E Be...

Страница 24: ...d connector with the plastic tape Vane motor Horizontal vane Connector Unlocking button Vane motor 3 Set the vertical vane of the air outlet by hand slowly within the range in the table below Measured...

Страница 25: ...air intake grille 2 Remove the 3 screws of fan guard Air intake grille knob 3 Removing the panel 1 Remove the air intake grille Refer to step 1 Corner panel See Figure 2 1 Remove the screw of the corn...

Страница 26: ...nd the fan 2 from the indoor controller board 6 Remove the 3 screws fixed to the piping cover and remove the piping cover See Photo 9 7 Remove the 6 screws fixed to the flat plate and remove the flat...

Страница 27: ...hoto 9 from the heat exchanger and remove the heat exchanger 9 Removing the drain pump DP and drain sensor DS 1 Remove the panel Refer to step 3 2 Remove the drain pan Refer to step 6 3 Remove the 2 s...

Страница 28: ...MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN CCopyright 2010 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Dec 2010 No OCH493 Made in Japan New publication effective Dec 2010 Specifications subj...

Отзывы: