Error Code

Abnormal point and detection method 

Cause

Countermeasure

P6

Freezing/overheating protection is oper-
ating

1

 Freezing protection (Cooling mode)

The unit is in 6-minute resume prevention 

mode if pipe <liquid or condenser/evapo-
rator> temperature stays under -15°C for 
3 minutes after the compressor started. 
Abnormal if it stays under 15°C for 3 
minutes again within 16 minutes after 
6-minute resume prevention mode.

    

2

 Overheating protection (Heating mode)

The units is in 6-minute resume 
prevention mode if pipe <condenser / 

evaporator> temperature is detected as 
over 70°C after the compressor started. 
Abnormal if the temperature of over 

70°C is detected again within 10 min-

utes after 6-minute resume prevention 
mode.

P8

1

 Slight temperature difference 

between indoor room  

  temperature and pipe <liquid 
  or condenser / evaporator> 
 temperature 

thermistor

• Shortage of refrigerant
• Disconnected holder of pipe 

<liquid or condenser / 

    evaporator> thermistor
• Defective refrigerant circuit

2

 Converse connection of 

  extension pipe (on plural units 

connection)

3

 Converse wiring of indoor/

  outdoor unit connecting wire 

(on plural units connection)

4

 Defective detection of indoor 

room temperature and pipe 
<condenser / evaporator> 

 temperature 

thermistor

5

 Stop valve is not opened 

 completely.

(Cooling or drying mode)

1

 Clogged filter (reduced airflow)

2

 Short cycle of air path

3

 Low-load (low temperature) 

operation out of the tolerance 
range

4

 Defective indoor fan motor

 • Fan motor is defective.
 • Indoor controller board is defec-

tive.

5

 Defective outdoor fan control

6

 Overcharge of refrigerant

7

 Defective refrigerant circuit 

(clogging)

(Heating mode)

1

 Clogged filter (reduced airflow)

2

 Short cycle of air path

3

 Overload (high temperature) 

operation out of the tolerance 
range

4

 Defective indoor fan motor

 • Fan motor is defective.
 • Indoor controller board is defec-

tive.

5

 Defective outdoor fan control

6

 Overcharge of refrigerant

7

 Defective refrigerant circuit 

(clogging)

8

 Bypass circuit of outdoor unit 

is defective. 

(Cooling or drying mode)

1

 Check clogging of the filter.

2

 Remove blockage.

4

 Measure the resistance of fan motor's winding.

  Measure the output voltage of fan's connector 

(FAN) on the indoor controller board.  

  W

The indoor controller board should be 

    normal when voltage of AC 220 - 240V is 
    detected while fan motor is connected. 
    Refer to 6-5.

5

 Check outdoor fan motor. 

67

  Check operating condition of refrigerant 

  

circuit.

(Heating mode)

1

 Check clogs of the filter.

2

 Remove blockage.

4

 Measure the resistance of fan motor's 

 winding.
  Measure the output voltage of fan's connector 

(FAN) on the indoor controller board.  

  W

The indoor controller board should be 

    normal when voltage of AC 220 - 240V is 
    detected while fan motor is connected. 
    Refer to 6-5.

5

 Check outdoor fan motor. 

6

~

8

Check operating condition of refrigerant  

        circuit.

Pipe temperature

<Cooling mode>
Detected as abnormal when the pipe tem-
perature is not in the cooling range 3 min-
utes after compressor start and 6 minutes 
after the liquid or condenser/evaporator pipe 
is out of cooling range.
Note 1) It takes at least 9 min. to detect.
Note 2) Abnormality P8 is not detected in 

drying mode.

Cooling range : -3 deg 

(TH-TH1) 

TH: Lower temperature between liquid pipe 

temperature (TH2) and condenser/
evaporator temperature (TH5)

TH1: Intake temperature 

<Heating mode>
When 10 seconds have passed after the 
compressor starts operation and the hot 
adjustment mode has finished, the unit is 
detected as abnormal when condenser/
evaporator pipe temperature is not in heat-
ing range within 20 minutes. 

Note 3) It takes at least 27 minutes to 

detect abnormality.

Note 4) It excludes the period of defrosting 

(Detection restarts when defrosting 
mode is over)

Heating range : 3 deg 

(TH5-TH1)  

23

Check converse connection of extension 

 

pipe or converse wiring of indoor/outdoor 

 

unit connecting wire.

1

~

4

Check pipe <liquid or condenser /   

evaporator> temperature with room  
temperature display on remote controller 
and outdoor controller circuit board.

 

Pipe <liquid or condenser / evaporator>  
temperature display is indicated by 

 

setting SW2 of outdoor controller circuit  
board as follows.

Conduct temperature check with outdoor 
controller circuit board after connecting 
‘A-Control Service Tool(PAC-SK52ST)’.

(

)

Содержание Mr.SLIM SLZ-KA25VAQ

Страница 1: ...ASSEMBLY PROCEDURE 25 December 2010 No OCH493 WIRED REMOTE CONTROLLER Option Indoor unit Model names Service Ref SLZ KA25VAQ SLZ KA25VAQ TH SLZ KA35VAQ SLZ KA35VAQ TH SLZ KA50VAQ SLZ KA50VAQ TH INDOOR...

Страница 2: ...orizontal airflow automatically during cooling or dehumidifying Air Intake Inhales air from room Indoor Unit SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH 1 PART NAMES AND FUNCTIONS Note The phrase Wir...

Страница 3: ...the cover ON OFF button Fan Speed button Filter button Enter button Test Run button Check button Clear button Airflow Up Down button Louver button Operation button To return operation number Ventilat...

Страница 4: ...is off Temperature Setting Shows the target temperature Day of Week Shows the current day of the week Time Timer Display Shows the current time unless the simple or Auto Off timer is set If the simpl...

Страница 5: ...tance at 26 Width Height Depth Weight Air direction Sound level High Medium Low Fan speed High Medium Low Fan speed regulator Thermistor TH1 at 25 Thermistor TH2 at 25 Thermistor TH5 at 25 h A A W kW...

Страница 6: ...D PRESSURE LEVEL dB 0 dB 0 0002 bar BAND CENTER FREQUENCIES Hz SLZ KA50VAQ TH High Medium 39 SPL dB 34 LINE 50Hz NOTCH Low 30 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE...

Страница 7: ...M Air intake grille 55 35 35 55 Auto vane Grille Air intake hole Air intake hole Air outlet hole Air outlet hole 301 301 377 377 650 650 V M V M V M Detail drawing of fresh air intake Ceiling surface...

Страница 8: ...8 WIRED REMOTE CONTROLLER Unit mm 130 19 120 43 5 Option...

Страница 9: ...9 9 WIRING DIAGRAM 4 SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH...

Страница 10: ...Condenser evaporator temperature thermistor TH5 Room temperature thermistor TH1 Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe con...

Страница 11: ...ors hold the housing of the connector DO NOT pull the lead wires Lead wire PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE ERROR CODE ERROR CO...

Страница 12: ...mptom Remark Number of times Wireless remote controller Wired remote controller Beeper sounds OPERATION INDICATOR lamp blinks Check code Number of times Wireless remote controller Wired remote control...

Страница 13: ...terminal block Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote controller wire short Note Operation is not possible for about 30 seconds after cancellation of...

Страница 14: ...re with remote controller in test run mode If pipe liquid temperature is extremely low in cooling mode or high in heating mode refrigerant circuit may have defect 5 Check pipe liquid temperature with...

Страница 15: ...oling or drying mode 1 Check clogging of the filter 2 Remove blockage 4 Measure the resistance of fan motor s winding Measure the output voltage of fan s connector FAN on the indoor controller board W...

Страница 16: ...Do not use cable 3 or more The number of connecting indoor units max 16 units The number of connecting remote control ler max 2 units When the above mentioned problem of 1 3 are not seen 4 Diagnose re...

Страница 17: ...y of the remote controller control board Error code E1 2 Abnormal if the clock function of remote controller cannot be normally operated Error code E2 1 Defective remote controller 1 Replace remote co...

Страница 18: ...it 1 Mis setting of refrigerant address for outdoor unit There is no unit corresponding to refrigerant address 0 1 Check the setting of refrigerant address for outdoor unit Set the refrigerant address...

Страница 19: ...5 1 Indoor power board SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH CNSK Connect to the indoor controller board CNDK between 1 to 3 220 240V AC CN2S Connect to the indoor controller board CN2D betwee...

Страница 20: ...ontrol signal 13V pulse input 1 3 4 Operation indicator 13VDC 3 3 5 Malfunction indicator 13VDC 3 CN6V Vane motor output MV CN90 Connect to the wire less remote controller board CNB CN31 Drain sensor...

Страница 21: ...ature 10 C 30 C Pipe temperature thermistor liquid TH2 Indoor fan motor MF Check method and criterion Part name Normal KA25VAQ Normal WHT BLK BLK BLU BLU YLW BRN RED 386 428 81 91 28 32 157 174 KA35VA...

Страница 22: ...20 6 3k 25 5 2k 30 4 3k 40 3 0k Thermistor R0 6 0k 5 Fixed number of B 3390 2 Rt 6exp 3390 0 6 0k 10 3 9k 20 2 6k 25 2 2k 30 1 8k 40 1 3k 60 0 6k Thermistor for lower temperature 1 273 t 1 273 1 273...

Страница 23: ...controller board and relay must be within 10m Be sure to secure insulation material by tape etc 5 Green Yellow Orange Connector 5P Indoor unit side Multiple remote controller adapter PAC SA88HA E Be...

Страница 24: ...d connector with the plastic tape Vane motor Horizontal vane Connector Unlocking button Vane motor 3 Set the vertical vane of the air outlet by hand slowly within the range in the table below Measured...

Страница 25: ...air intake grille 2 Remove the 3 screws of fan guard Air intake grille knob 3 Removing the panel 1 Remove the air intake grille Refer to step 1 Corner panel See Figure 2 1 Remove the screw of the corn...

Страница 26: ...nd the fan 2 from the indoor controller board 6 Remove the 3 screws fixed to the piping cover and remove the piping cover See Photo 9 7 Remove the 6 screws fixed to the flat plate and remove the flat...

Страница 27: ...hoto 9 from the heat exchanger and remove the heat exchanger 9 Removing the drain pump DP and drain sensor DS 1 Remove the panel Refer to step 3 2 Remove the drain pan Refer to step 6 3 Remove the 2 s...

Страница 28: ...MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN CCopyright 2010 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Dec 2010 No OCH493 Made in Japan New publication effective Dec 2010 Specifications subj...

Отзывы: