background image

18

6-4. TROUBLESHOOTING BY INFERIOR PHENOMENA 

Note: Refer to the manual of outdoor unit for the detail of remote 
         controller.

Phenomena

Cause

Countermeasure

(1)  LED2 on indoor controller board  

is off. 

  • When LED1 on indoor controller board is also off.

1

 Power supply of rated voltage is not supplied to out-

door unit.

2

 Defective outdoor controller circuit board

3

 Power supply of 220~240V is not supplied to indoor 

unit.

4

 Defective indoor power board

5

 Defective indoor controller board

1

 Check the voltage of outdoor power 

  supply terminal block (L, N) or (L

3

, N).

• When AC 220-240V is not detected,

      check the power wiring to outdoor unit  
      and the breaker.

• When AC 220-240V is detected, 
 check 

2

 (below).

2

 Check the voltage between outdoor 

  terminal block S1 and S2.

• When AC 220-240V is not detected,
  —check the fuse on outdoor controller 

circuit board.

      —check the wiring connection.

• When AC 220-240V is detected, 
 check 

3

 (below).

3

 Check the voltage between indoor terminal 

block S1 and S2.

• When AC 220-240V is not detected,

      check indoor/outdoor unit connecting  
      wire for miswiring.

• When AC 220-240V is detected, 
 check 

4

 (below).

4

 Check voltage output from CN2S on indoor 

power board (DC13.1V). Refer to 6-5.

• When no voltage is output,

      check the wiring connection.

• When output voltage is between 

DC12.5V and DC13.7V, 

 check 

5

 (below).

5

 Check the wiring connection between 

indoor controller board and indoor power 
board. Check the fuse on indoor controller 
board. If no problems are found, indoor 
controller board is defective.

  • When LED1 on indoor controller board is lit.

1

 Mis-setting of refrigerant address for outdoor unit

    (There is no unit corresponding to refrigerant 
    address “0”.)

1

 Check the setting of refrigerant address 

for outdoor unit.

    Set the refrigerant address to “0”.
    (For grouping control system under    
    which 2 or more outdoor units are 
    connected, set one of the units to “0”.)
    Set refrigerant address using SW1 (3-6) 
    on outdoor controller circuit board.

(2)  LED2 on indoor controller board 

is blinking.

  • When LED1 on indoor controller board is also blinking.
    Connection failure of indoor/outdoor unit connecting 
    wire 
  • When LED1 is lit

1

 Miswiring of remote controller wires

    Under twin indoor unit system, 2 or more indoor units 

2

 Refrigerant address for outdoor unit is wrong or not 

set.

    Under grouping control system, there are some units   
    whose refrigerant address is 0.

3

 Short-cut of remote controller wires

4

 Defective remote controller

Check indoor/outdoor unit connecting wire 
for connection failure. 

1

 Check the connection of remote cotrol-

ler wires in case of twin triple indoor unit 
system. When 2 or more indoor units are 
wired in one refrigerant system, connect 
remote controller wires to one of those 
units.

2

 Check the setting of refrigerant address 

in case of grouping control system. If 
there are some units whose refrigerant 
addresses are 0 in one group, set one 
of the units to 0 using SW1 (3-6) on out-
door controller circuit board.

34

 Remove remote controller wires and 

check LED2 on indoor controller board.

• When LED2 is blinking, check the 

short-cut of remote controller wires.

• When LED2 is lit, connect remote 
  controller wires again and:

      if LED2 is blinking, remote controller 
      is defective; if LED2 is lit, connection 
      failure of remote controller terminal 
      block etc. has returned to normal. 

Содержание Mr.SLIM SLZ-KA25VAQ

Страница 1: ...ASSEMBLY PROCEDURE 25 December 2010 No OCH493 WIRED REMOTE CONTROLLER Option Indoor unit Model names Service Ref SLZ KA25VAQ SLZ KA25VAQ TH SLZ KA35VAQ SLZ KA35VAQ TH SLZ KA50VAQ SLZ KA50VAQ TH INDOOR...

Страница 2: ...orizontal airflow automatically during cooling or dehumidifying Air Intake Inhales air from room Indoor Unit SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH 1 PART NAMES AND FUNCTIONS Note The phrase Wir...

Страница 3: ...the cover ON OFF button Fan Speed button Filter button Enter button Test Run button Check button Clear button Airflow Up Down button Louver button Operation button To return operation number Ventilat...

Страница 4: ...is off Temperature Setting Shows the target temperature Day of Week Shows the current day of the week Time Timer Display Shows the current time unless the simple or Auto Off timer is set If the simpl...

Страница 5: ...tance at 26 Width Height Depth Weight Air direction Sound level High Medium Low Fan speed High Medium Low Fan speed regulator Thermistor TH1 at 25 Thermistor TH2 at 25 Thermistor TH5 at 25 h A A W kW...

Страница 6: ...D PRESSURE LEVEL dB 0 dB 0 0002 bar BAND CENTER FREQUENCIES Hz SLZ KA50VAQ TH High Medium 39 SPL dB 34 LINE 50Hz NOTCH Low 30 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE...

Страница 7: ...M Air intake grille 55 35 35 55 Auto vane Grille Air intake hole Air intake hole Air outlet hole Air outlet hole 301 301 377 377 650 650 V M V M V M Detail drawing of fresh air intake Ceiling surface...

Страница 8: ...8 WIRED REMOTE CONTROLLER Unit mm 130 19 120 43 5 Option...

Страница 9: ...9 9 WIRING DIAGRAM 4 SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH...

Страница 10: ...Condenser evaporator temperature thermistor TH5 Room temperature thermistor TH1 Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe con...

Страница 11: ...ors hold the housing of the connector DO NOT pull the lead wires Lead wire PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE ERROR CODE ERROR CO...

Страница 12: ...mptom Remark Number of times Wireless remote controller Wired remote controller Beeper sounds OPERATION INDICATOR lamp blinks Check code Number of times Wireless remote controller Wired remote control...

Страница 13: ...terminal block Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote controller wire short Note Operation is not possible for about 30 seconds after cancellation of...

Страница 14: ...re with remote controller in test run mode If pipe liquid temperature is extremely low in cooling mode or high in heating mode refrigerant circuit may have defect 5 Check pipe liquid temperature with...

Страница 15: ...oling or drying mode 1 Check clogging of the filter 2 Remove blockage 4 Measure the resistance of fan motor s winding Measure the output voltage of fan s connector FAN on the indoor controller board W...

Страница 16: ...Do not use cable 3 or more The number of connecting indoor units max 16 units The number of connecting remote control ler max 2 units When the above mentioned problem of 1 3 are not seen 4 Diagnose re...

Страница 17: ...y of the remote controller control board Error code E1 2 Abnormal if the clock function of remote controller cannot be normally operated Error code E2 1 Defective remote controller 1 Replace remote co...

Страница 18: ...it 1 Mis setting of refrigerant address for outdoor unit There is no unit corresponding to refrigerant address 0 1 Check the setting of refrigerant address for outdoor unit Set the refrigerant address...

Страница 19: ...5 1 Indoor power board SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH CNSK Connect to the indoor controller board CNDK between 1 to 3 220 240V AC CN2S Connect to the indoor controller board CN2D betwee...

Страница 20: ...ontrol signal 13V pulse input 1 3 4 Operation indicator 13VDC 3 3 5 Malfunction indicator 13VDC 3 CN6V Vane motor output MV CN90 Connect to the wire less remote controller board CNB CN31 Drain sensor...

Страница 21: ...ature 10 C 30 C Pipe temperature thermistor liquid TH2 Indoor fan motor MF Check method and criterion Part name Normal KA25VAQ Normal WHT BLK BLK BLU BLU YLW BRN RED 386 428 81 91 28 32 157 174 KA35VA...

Страница 22: ...20 6 3k 25 5 2k 30 4 3k 40 3 0k Thermistor R0 6 0k 5 Fixed number of B 3390 2 Rt 6exp 3390 0 6 0k 10 3 9k 20 2 6k 25 2 2k 30 1 8k 40 1 3k 60 0 6k Thermistor for lower temperature 1 273 t 1 273 1 273...

Страница 23: ...controller board and relay must be within 10m Be sure to secure insulation material by tape etc 5 Green Yellow Orange Connector 5P Indoor unit side Multiple remote controller adapter PAC SA88HA E Be...

Страница 24: ...d connector with the plastic tape Vane motor Horizontal vane Connector Unlocking button Vane motor 3 Set the vertical vane of the air outlet by hand slowly within the range in the table below Measured...

Страница 25: ...air intake grille 2 Remove the 3 screws of fan guard Air intake grille knob 3 Removing the panel 1 Remove the air intake grille Refer to step 1 Corner panel See Figure 2 1 Remove the screw of the corn...

Страница 26: ...nd the fan 2 from the indoor controller board 6 Remove the 3 screws fixed to the piping cover and remove the piping cover See Photo 9 7 Remove the 6 screws fixed to the flat plate and remove the flat...

Страница 27: ...hoto 9 from the heat exchanger and remove the heat exchanger 9 Removing the drain pump DP and drain sensor DS 1 Remove the panel Refer to step 3 2 Remove the drain pan Refer to step 6 3 Remove the 2 s...

Страница 28: ...MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN CCopyright 2010 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Dec 2010 No OCH493 Made in Japan New publication effective Dec 2010 Specifications subj...

Отзывы: