6-3. SELF-DIAGNOSIS ACTION TABLE

Note: Refer to the manual of outdoor unit for the details of display 
         such as F, U, and other E.

Error Code

Abnormal point and detection method 

Cause

Countermeasure

P1

Room temperature thermistor (TH1)

1

 The unit is in 3-minute resume 

  prevention mode if short/open of 
  thermistor is detected. Abnormal if the 

unit does not reset normally after 3 min-
utes. (The unit returns to normal opera-
tion, if it has been reset normally.)

2

 Constantly detected during cooling, 

  drying and heating operation
  Short:  90°C or more
  Open: -40°C or less

1

 Defective thermistor 

 characteristics

2

 Contact failure of  connector 

(CN20) on the indoor controller 
board (Insert failure)

3

 Breaking of wire or contact 

  failure of thermistor wiring

4

 Defective indoor controller 

board

1

3

 Check resistance value of thermistor.

0°C.....15.0k

"

10°C.......9.6k

"

20°C.......6.3k

"

30°C.......4.3k

"

40°C.......3.0k

"

If you put force on (draw or bend) the lead wire 
with measuring resistance value of thermis-
tor, breaking of wire or contact failure can be 
detected.

2

 Check contact failure of  connector (CN20) 

on the indoor controller board. Refer to 6-5.  
Turn the power back on and check restart 
after inserting connector again.

4

 Check room temperature display on remote 

controller.

  Replace indoor controller board if there is 

abnormal difference with actual room 

 temperature.

Turn the power off, and on again to operate 
after checking.

P2

Pipe temperature thermistor/Liquid 
(TH2)

1

 The unit is in 3-minute resume 

  prevention mode if short/open of 
  thermistor is detected. Abnormal if the 

unit does not reset normally after 3 min-
utes. (The unit returns to normal opera-
tion, if it has been reset normally.)

2

 Constantly detected during cooling, 

  drying, and heating (except defrosting) 

operation.

  Short:  90°C or more
  Open: -40°C or less

 1

 Defective thermistor 

 characteristics

2

 Contact failure of  connector 

(CN21) on the indoor controller 
board (Insert failure)

3

 Breaking of wire or contact 

  failure of thermistor wiring

4

 Defective refrigerant circuit is 

causing thermistor temperature 
of 90°C or more or -40°C or 
less.

5

 Defective indoor controller board

1

3

 Check resistance value of thermistor.

For characteristics, refer to (P1) above.

2

 Check contact failure of  connector (CN21) 

on the indoor controller board. Refer to 6-5. 
Turn the power on and check restart after 
inserting connector again.

4

 Check pipe <liquid> temperature with remote 

controller in test run mode. If pipe <liquid> 
temperature is extremely low (in cooling 
mode) or high (in heating mode), refrigerant 
circuit may have defect.

5

 Check pipe <liquid> temperature with remote 

controller in test run mode. If there is extreme 
difference with actual pipe <liquid> tempera-
ture, replace indoor controller board. 

Turn the power off, and on again to operate 
after checking.

P4

Drain sensor (DS)

1

 Suspensive abnormality, if short/open 

of thermistor is detected for 30 seconds 
continuously.

  Turn off compressor and indoor fan.

2

 Short/open is detected for 30 seconds 

continuously during suspensive 

 abnormality.
  (The unit returns to normal operation, 
   if it has been reset normally.)

3

 Detect the following condition.

• During cooling and drying operation
• In case that pipe <liquid> temperature - 

room temperature < -10 deg

  (Except defrosting)
• When pipe <liquid> temperature or 

room temperature is short/open 

 temperature.
• During drain pump operation

1

 Defective thermistor 

 characteristics

2

 Contact failure of  connector 

(CN31) on the indoor controller 
board (Insert failure)

3

 Breaking of wire or contact 

  failure of drain sensor wiring

4

 Defective indoor controller board

1

3

 Check resistance value of thermistor.

  0°C.......6.0k

"

10°C.......3.9k

"

20°C.......2.6k

"

30°C.......1.8k

"

40°C.......1.3k

"

2

 Check contact failure of  connector (CN31) 

on the indoor controller board. Refer to 6-5. 
Turn the power back on and check restart 
after inserting connector again.

4

 Replace indoor controller board if drain 

  pump operates with the line of drain sensor 

connector CN31-

1

 and 

2

 is short-circuited, 

and abnormality reappears.

Turn the power off, and on again to operate 
after checking.

P5

Malfunction of drain pump (DP)

1

 Suspensive abnormality, if thermistor 

  of drain sensor heats itself and 
  temperature rises slightly. Turn off 
  compressor and indoor fan.

2

 Drain pomp is abnormal if the condition 

above is detected during suspensive 
abnormality.

3

 Constantly detected during drain pump 

operation

1

 Malfunction of drain pump

2

 Defective drain

  Clogged drain pump
  Clogged drain pipe

3

 Attached drop of water at the 

drain sensor

• Drops of drain trickles from 

lead wire

• Clogged filter is causing 

wave of drain.

4

 Defective indoor controller board

1

 Check if drain pump works.

2

 Check drain function.

3

 Check the setting of lead wire of drain sen-

sor and check clogs of the filter.

4

 Replace indoor controller board if drain 

  pump operates with the line of drain sensor 

connector CN31-

1

 and 

2

 is short-circuited 

and abnormality reappears.

  Refer to 6-5.

Turn  the power off, and on again to operate 
after checking.

Содержание Mr.SLIM SLZ-KA25VAQ

Страница 1: ...ASSEMBLY PROCEDURE 25 December 2010 No OCH493 WIRED REMOTE CONTROLLER Option Indoor unit Model names Service Ref SLZ KA25VAQ SLZ KA25VAQ TH SLZ KA35VAQ SLZ KA35VAQ TH SLZ KA50VAQ SLZ KA50VAQ TH INDOOR...

Страница 2: ...orizontal airflow automatically during cooling or dehumidifying Air Intake Inhales air from room Indoor Unit SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH 1 PART NAMES AND FUNCTIONS Note The phrase Wir...

Страница 3: ...the cover ON OFF button Fan Speed button Filter button Enter button Test Run button Check button Clear button Airflow Up Down button Louver button Operation button To return operation number Ventilat...

Страница 4: ...is off Temperature Setting Shows the target temperature Day of Week Shows the current day of the week Time Timer Display Shows the current time unless the simple or Auto Off timer is set If the simpl...

Страница 5: ...tance at 26 Width Height Depth Weight Air direction Sound level High Medium Low Fan speed High Medium Low Fan speed regulator Thermistor TH1 at 25 Thermistor TH2 at 25 Thermistor TH5 at 25 h A A W kW...

Страница 6: ...D PRESSURE LEVEL dB 0 dB 0 0002 bar BAND CENTER FREQUENCIES Hz SLZ KA50VAQ TH High Medium 39 SPL dB 34 LINE 50Hz NOTCH Low 30 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE...

Страница 7: ...M Air intake grille 55 35 35 55 Auto vane Grille Air intake hole Air intake hole Air outlet hole Air outlet hole 301 301 377 377 650 650 V M V M V M Detail drawing of fresh air intake Ceiling surface...

Страница 8: ...8 WIRED REMOTE CONTROLLER Unit mm 130 19 120 43 5 Option...

Страница 9: ...9 9 WIRING DIAGRAM 4 SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH...

Страница 10: ...Condenser evaporator temperature thermistor TH5 Room temperature thermistor TH1 Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe con...

Страница 11: ...ors hold the housing of the connector DO NOT pull the lead wires Lead wire PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE ERROR CODE ERROR CO...

Страница 12: ...mptom Remark Number of times Wireless remote controller Wired remote controller Beeper sounds OPERATION INDICATOR lamp blinks Check code Number of times Wireless remote controller Wired remote control...

Страница 13: ...terminal block Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote controller wire short Note Operation is not possible for about 30 seconds after cancellation of...

Страница 14: ...re with remote controller in test run mode If pipe liquid temperature is extremely low in cooling mode or high in heating mode refrigerant circuit may have defect 5 Check pipe liquid temperature with...

Страница 15: ...oling or drying mode 1 Check clogging of the filter 2 Remove blockage 4 Measure the resistance of fan motor s winding Measure the output voltage of fan s connector FAN on the indoor controller board W...

Страница 16: ...Do not use cable 3 or more The number of connecting indoor units max 16 units The number of connecting remote control ler max 2 units When the above mentioned problem of 1 3 are not seen 4 Diagnose re...

Страница 17: ...y of the remote controller control board Error code E1 2 Abnormal if the clock function of remote controller cannot be normally operated Error code E2 1 Defective remote controller 1 Replace remote co...

Страница 18: ...it 1 Mis setting of refrigerant address for outdoor unit There is no unit corresponding to refrigerant address 0 1 Check the setting of refrigerant address for outdoor unit Set the refrigerant address...

Страница 19: ...5 1 Indoor power board SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH CNSK Connect to the indoor controller board CNDK between 1 to 3 220 240V AC CN2S Connect to the indoor controller board CN2D betwee...

Страница 20: ...ontrol signal 13V pulse input 1 3 4 Operation indicator 13VDC 3 3 5 Malfunction indicator 13VDC 3 CN6V Vane motor output MV CN90 Connect to the wire less remote controller board CNB CN31 Drain sensor...

Страница 21: ...ature 10 C 30 C Pipe temperature thermistor liquid TH2 Indoor fan motor MF Check method and criterion Part name Normal KA25VAQ Normal WHT BLK BLK BLU BLU YLW BRN RED 386 428 81 91 28 32 157 174 KA35VA...

Страница 22: ...20 6 3k 25 5 2k 30 4 3k 40 3 0k Thermistor R0 6 0k 5 Fixed number of B 3390 2 Rt 6exp 3390 0 6 0k 10 3 9k 20 2 6k 25 2 2k 30 1 8k 40 1 3k 60 0 6k Thermistor for lower temperature 1 273 t 1 273 1 273...

Страница 23: ...controller board and relay must be within 10m Be sure to secure insulation material by tape etc 5 Green Yellow Orange Connector 5P Indoor unit side Multiple remote controller adapter PAC SA88HA E Be...

Страница 24: ...d connector with the plastic tape Vane motor Horizontal vane Connector Unlocking button Vane motor 3 Set the vertical vane of the air outlet by hand slowly within the range in the table below Measured...

Страница 25: ...air intake grille 2 Remove the 3 screws of fan guard Air intake grille knob 3 Removing the panel 1 Remove the air intake grille Refer to step 1 Corner panel See Figure 2 1 Remove the screw of the corn...

Страница 26: ...nd the fan 2 from the indoor controller board 6 Remove the 3 screws fixed to the piping cover and remove the piping cover See Photo 9 7 Remove the 6 screws fixed to the flat plate and remove the flat...

Страница 27: ...hoto 9 from the heat exchanger and remove the heat exchanger 9 Removing the drain pump DP and drain sensor DS 1 Remove the panel Refer to step 3 2 Remove the drain pan Refer to step 6 3 Remove the 2 s...

Страница 28: ...MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN CCopyright 2010 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Dec 2010 No OCH493 Made in Japan New publication effective Dec 2010 Specifications subj...

Отзывы: