5. SEQUENCE INSTRUCTIONS
5
−
22
MELSEC-A
(3) Program which resets the 100ms retentive timer and counter.
•
Coding
0 LD
X004
1 OUT
T225
K18000
2 LD
T225
3 OUT
C23
K16
4 RST
T225
7 LD
C23
8 OUT
Y055
9 LD
X005
10
RST
C23
13
END
(
)
(
)
(
)
T225 turns on after X4 has been
on for 30 minutes.
The number of ON times of T225
is counted.
When T225 has turned on, T225 is reset.
When C23 has counted up, Y55 turnes on.
When X5 turns on, C23 is reset.
X004
T225
C23
X005
K18000
T225
K16
C23
RST
T225
RST
C23
Y055