7. APPLICATION INSTRUCTIONS
7
−
75
MELSEC-A
DFRO , PRC
A program which reads data of 2 words from address 14 of buffer memory of the
AD61C (head station number 1) to D10 and D11 when X0 is turned ON.
K
K
K
DFRO 1 14
D10
1
PRC M0 Y000
0
X000
……... M0 turns ON when communication
processing is completed.
•
Coding
0 LD
X000
1 DFRO K1
K14
D10
K1
10
PRC
M0
Y000
17
END
Содержание MELSEC-A series
Страница 1: ......
Страница 2: ......
Страница 13: ...A 11 MEMO...
Страница 505: ...APPENDICES APP 100 MELSEC A MEMO...
Страница 507: ......
Страница 508: ......