9 -
10
ERROR CODE LIST
9.
Table 9.2 Error Code List for AnSHCPU (Continue)
Error Message
Error
Code
(D9008)
Detailed
Error
Code
(D9092)
CPU
States
Error and Cause
Corrective Action
"LINK PARA.
ERROR"
47
—
Stop or
Continue
(set by
parameter)
(1) There is inconsistency for some
reason between the data, which is
written by the peripheral device in
the parameter area of the link under
link range designation using
parameter setup, and the link
parameter data read by the CPU
module.
(2) The total number of stations is set at
"
0.
"
(1) Write parameters and check again.
(2) If the error persists, there is a fault in
hardware. Consult Mitsubishi
representative.
"OPERATION
ERROR"
50
—
Stop or
Continue
(set by
parameter)
(1) The result of BCD conversion
exceeds the rated range ("9999" or
"99999999").
(2) There is a setting exceeding the
rated device range, disabling
execution of calculation.
(3) The file register is used on the
program without designation of the
capacity of the file register.
Use the peripheral device to read and
correct the error step in the program.
(Check the setting range of the device,
BCD conversion value and so on.)
503
The data stored by the designated
device or a constant exceeds the
allowable range.
Use the peripheral device to read and
correct the error step in the program.
504
The setting quantity of handled data
exceeds the allowable range.
509
The number of special instructions for
CC-Link executed in each scan
exceeds 64.
Reduce the special instructions for CC-
Link executed in each scan to within 64.
A special instruction for CC-Link is
executed to a CC-Link module to which
no parameter is defined.
Define parameters.
"MAIN CPU
DOWN"
60
—
Stop
(1) The CPU walfunctioned due to
noise.
(2) Hardware failure.
(1) Take proper countermeasures for
noise.
(2) Consult Mitsubishi representative.
"BATTERY
ERROR"
70
—
Continue
(1) The battery voltage is low.
(2) The battery lead connector is not
connected.
(1) Replace the battery.
(2) Connect the lead connector to use
the built-in RAM memory or power
failure compensation function.
Содержание MELSEC-A series