FX2N-32DP-IF Profibus-DP Interface Unit
Advanced Devices 5
5-8
Note 3: Communication status
This device is the 32DP-IF’s communication status. According to the status of 32DP-IF the
bits are set and reset as follows.
*1 Clear data global control:
When this command is received, the 32DP-IF set to “0” the output
data (D100 ~ D199) of extension units/blocks connected it.
*2 Unfreeze global control:
The UNFREEZE control command stops freeze control mode. The
input data (D0 ~ D99) of extension units/blocks connected to the
32DP-IF is immediately sent to the DP-master.
*3 Freeze global control:
The DP-master sends a FREEZE control command to a group of
DP-slaves to hold their current input status. The input data (D0 ~ D99)
of extension units/blocks connected to the 32DP-IF are withheld until
the next FREEZE/UNFREEZE control command is received.
*4 Unsync global control:
The UNSYNC command stops SYNC control mode. The output data
(D100 ~ D199) send from the DP-master is immediately transmitted
to extension units/blocks connected to the 32DP-IF.
*5 Sync global control:
The DP-master sends a SYNC control command to a group of
DP-slaves to synchronize their current output states. The output data
(D100 ~ D199) of extension units/blocks connected to the 32DP-IF
remains constant until the next SYNC/UNSYNC command is
received.
Table 5.10: Communication Status in D8025
Bit No.
Description
1 (ON)
0 (OFF)
Bit 0
Module on-line/off-line
Module on-line
Module off-line
Bit 1
Reserved
Bit 2
Diagnosis flag
New diagnosis not yet fetched by
DP-master
New diagnosis fetched by
DP-master
Bit 3
Reserved
Bit 4, 5
DP-status
(bit 5, 4) = (0, 0)
Wait parameter state
(bit 5, 4) = (0, 1)
Wait configuration state
(bit 5, 4) = (1, 0)
Data exchange state
(bit 5, 4) = (1, 1)
Not possible
Bit 6, 7
DP-watchdog state
(bit 7, 6) = (0, 0)
Baud search state
(bit 7, 6) = (0, 1)
Baud control state
(bit 7, 6) = (1, 0)
DP search state
(bit 7, 6) = (1, 1)
Not possible
Bit 8
Reserved
BIt 9
Clear data global control
*1
Clear data command received
No clear data command received
Bit 10
Unfreeze global control
*2
Unfreeze command received
No unfreeze command received
Bit 11
Freeze global control
*3
Freeze command received
No freeze command received
Bit 12
Unsync global control
*4
Unsync command received
No unsync command received
Bit 13
Sync global control
*5
Sync command received
No sync command received
Bit 14, 15 Reserved
Содержание FX2N-32DP-IF
Страница 4: ...FX2N 32DP IF Profibus DP Interface Unit ii...
Страница 6: ...FX2N 32DP IF Profibus DP Interface Unit iv...
Страница 12: ...FX2N 32DP IF Profibus DP Interface Unit x...
Страница 64: ...FX2N 32DP IF Profibus DP Interface Unit Address Setting 6 6 2 MEMO...
Страница 78: ...FX2N 32DP IF Profibus DP Interface Unit User Parameter 7 7 14 MEMO...
Страница 80: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostic Message 8 8 2 MEMO...
Страница 86: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 9 9 6 MEMO...
Страница 92: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 6 Figure A 6 Setting Global Parameter...
Страница 96: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 10 MEMO...
Страница 102: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 6 Figure B 6 Setting Global Parameter...
Страница 106: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 10 MEMO...
Страница 192: ...FX2N 32DP IF Profibus DP Interface Unit Appendix C C 86 MEMO...
Страница 194: ...FX2N 32DP IF Profibus DP Interface Unit Appendix D D 2 MEMO...
Страница 197: ......