FX2N-32DP-IF Profibus-DP Interface Unit
Advanced Devices 5
5-4
5.2.1
32DP-IF Status (M8000 ~ M8009 and D8000 ~ D8009)
Figure 5.2: Momentary Power failures
Figure 5.3: 32DP-IF Version
Table 5.3: Special Auxiliary Relays (M8000 ~ M8009)
Diagnostic
Device
Name
Description
M8000
(
8
)
RUN LED monitor
ON when 32DP-IF is exchanging data with extension I/O
blocks/units and special. This device operate same as RUN
LED.
M8001 ~ M8003
Reserved
M8004
(
8
)
(ref. D8004)
Error occurrence
ON when one or more error flags (M8060 to M8068) is ON. If
this bit is ON, error number is written in D8004.
M8005, M8006
Reserved
M8007
(
8
) (
4
)
(ref. D8007)
Momentary
power failure
See Figure 5.2.
M8008, M8009
Reserved
Table 5.4: Special Data Registers (D8000 ~ D8009)
Diagnostic
Device
Name
Description
D8000
Reserved
D8001
(
8
)
32DP-IF version
This value is 32DP-IF version code. See Figure 5.3.
D8002, D8003
Reserved
D8004
(
8
) (
4
)
Error number
M
The contents of this register
identifies which error flag
is active, i.e. if
= 8061, identifies M8061
D8005, D8006
Reserved
D8007
(
8
) (
4
)
Number of
momentary
power failures
This value is counted when M8007 is ON. This value is reset
on full power OFF.
D8008
(
8
)
Power failure
detection period
Power failure detection period is 10 ms.
D8009
Reserved
AC Power
Exchanged
with DP-master
M8007
Momentary power failure
10 ms
5 ms
This time is power failure detection period.
Version No.: Ex. 100 = V1.00
Module Type No.: Ex. 20 = 32DP-IF
dec
Содержание FX2N-32DP-IF
Страница 4: ...FX2N 32DP IF Profibus DP Interface Unit ii...
Страница 6: ...FX2N 32DP IF Profibus DP Interface Unit iv...
Страница 12: ...FX2N 32DP IF Profibus DP Interface Unit x...
Страница 64: ...FX2N 32DP IF Profibus DP Interface Unit Address Setting 6 6 2 MEMO...
Страница 78: ...FX2N 32DP IF Profibus DP Interface Unit User Parameter 7 7 14 MEMO...
Страница 80: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostic Message 8 8 2 MEMO...
Страница 86: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 9 9 6 MEMO...
Страница 92: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 6 Figure A 6 Setting Global Parameter...
Страница 96: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 10 MEMO...
Страница 102: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 6 Figure B 6 Setting Global Parameter...
Страница 106: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 10 MEMO...
Страница 192: ...FX2N 32DP IF Profibus DP Interface Unit Appendix C C 86 MEMO...
Страница 194: ...FX2N 32DP IF Profibus DP Interface Unit Appendix D D 2 MEMO...
Страница 197: ......