FX2N-32DP-IF Profibus-DP Interface Unit
Appendix C:
C-3
C-2:
User Parameter for Special function block
“Short configuration”, “extension configuration” and “simple communication” is prepared in the
user parameter for a special function block with a special function block.
Further information for user parameter can be found in the chapter 6. Further information for
the special function block’s BFMs can be found in each module’s manual.
C-2-1:
FX
2N
-4AD Extension Configuration (Intel Format)
Requirements:
•
Cyclic data is 4 word inputs in every cycle.
•
Parameter is 41 bytes.
Table C-2:
Cyclic Data of FX
2N
-4AD Extension Configuration
(Intel Format)
Send Data
Receive Data
1st
None
Choose between direct and averaged value ch1
2nd
Choose between direct and averaged value ch2
3rd
Choose between direct and averaged value ch3
4th
Choose between direct and averaged value ch4
Table C-3:
FX
2N
-4AD Extension Configuration (Intel Format)
Nr.
Parameter Name
Value Setting List
Description
00
(1st)
Channel 1 input
direct input value ch1
Select input value type for channel 1
from the available options (BFM #9 or
BFM #5).
averaged input value ch1
01
(2nd)
Channel 2 input
direct input value ch2
Select input value type for channel 2
from the available options (BFM #10
or BFM #6).
averaged input value ch2
02
(3rd)
Channel 3 input
direct input value ch3
Select input value type for channel 3
from the available options (BFM #11
or BFM #7).
averaged input value ch3
03
(4th)
Channel 4 input
direct input value ch4
Select input value type for channel 4
from the available options (BFM #12
or BFM #8).
averaged input value ch4
04
(5th)
Next parameter
uses EEPROM.
DON'T write parameter to
EEPROM
The 6th parameter uses EEPROM.
Select “writing to EEPROM” setting
from the available options.
write parameter to EEPROM
05
(6th)
..O/G setting
prohibit/permit
permit offset/gain setting
Select prohibit/permit setting of offset/
gain from the available options (BFM
#21).
prohibit offset/gain setting
06
(7th)
RESET/INIT.
MODULE TO
DEFAULT
no reset/initialisation
Select initialize module setting from
the available options (BFM #20).
RESET/INITIALISE MODULE
07
*1
(8th)
VERIFY RESET/
INITIALISE
COMMAND
no reset/initialisation
Select initialize module setting from
the available options (BFM #20).
RESET/INITIALISE MODULE
Содержание FX2N-32DP-IF
Страница 4: ...FX2N 32DP IF Profibus DP Interface Unit ii...
Страница 6: ...FX2N 32DP IF Profibus DP Interface Unit iv...
Страница 12: ...FX2N 32DP IF Profibus DP Interface Unit x...
Страница 64: ...FX2N 32DP IF Profibus DP Interface Unit Address Setting 6 6 2 MEMO...
Страница 78: ...FX2N 32DP IF Profibus DP Interface Unit User Parameter 7 7 14 MEMO...
Страница 80: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostic Message 8 8 2 MEMO...
Страница 86: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 9 9 6 MEMO...
Страница 92: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 6 Figure A 6 Setting Global Parameter...
Страница 96: ...FX2N 32DP IF Profibus DP Interface Unit Appendix A A 10 MEMO...
Страница 102: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 6 Figure B 6 Setting Global Parameter...
Страница 106: ...FX2N 32DP IF Profibus DP Interface Unit Appendix B B 10 MEMO...
Страница 192: ...FX2N 32DP IF Profibus DP Interface Unit Appendix C C 86 MEMO...
Страница 194: ...FX2N 32DP IF Profibus DP Interface Unit Appendix D D 2 MEMO...
Страница 197: ......