9 -
7
EMC AND LOW VOLTAGE DIRECTIVES
9.
(b) When wiring with cable that exceeds 2m (6.56ft.), but is 10m (32.81ft.) or less
• Ground the shield section of the external wiring cable with the cable clamp.
(Ground the shield at the closest location to the A1SD75 external wiring
connector.)
• Install a ferrite core.
• Wire the external wiring cable to the drive unit and external device with the
minimum distance of cable.
(c) Ferrite core and cable clamp types and required quantities
• Cable clamp
• Ferrite core
• Required quantity
(d) Cable clamp mounting position
Type :
AD75CK (Manufactured by Mitsubishi Electric)
Type :
ZCAT3035-1330 (TDK ferrite core)
Contact: TDK Corporation
Cable length
Prepared part
Required Qty
1 axis
2 axes
3 axes
Within 2m (6.56ft.)
AD75CK
1
1
1
2m (6.56ft.) to 10m (32.81ft.)
AD75CK
1
1
1
ZCAT3035-1330
1
2
3
Inside control panel
A1SD75
AD75CK
20 to 30cm
(7.87 to 11.81inch)
Содержание A2USCPU(S1)
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 Memo...
Страница 254: ...App 59 APPENDIX Appendix5 2 A1S61PN A1S62PN and A1S63P power supply modules Unit mm inch...
Страница 256: ...App 61 APPENDIX Appendix5 3 3 A1S35B main base unit Unit mm inch Appendix5 3 4 A1S38B main base unit Unit mm inch...
Страница 262: ...App 67 APPENDIX Appendix5 5 Memory cassette Appendix5 5 1 A2SNMCA 30KE memory cassette Unit mm inch...
Страница 271: ......
Страница 272: ......