4 -
16
CPU MODULE
4.
Self-diagnostics list
*1
Can be changed by the parameter settings of the peripheral devices.
*2
Indicated as a three-digit trouble code only for errors with the "CHK" instruction.
Diagnosis item
Diagnosis timing
CPU module
status
Status of
"RUN" LED
Contents of error
indication
Error code
(D9008)
Me
mo
ry
e
rro
r
Instruction code check
Upon execution of each instruction
Stop
Flickering
INSTRCT CODE ERR.
10
Parameter setting check
• When switching ON or resetting
• When switching from (STOP, PAUSE) to
(RUN, STEP
RUN)
PARAMETER ERROR
11
No END instruction
• When M9056 or M9057 is ON
• When switching from (STOP, PAUSE) to
(RUN, STEP
RUN)
MISSING END INS.
12
Unable to execute instruction
•
• Upon execution of each instruction
• When switching from (STOP, PAUSE) to
(RUN, STEP
RUN)
CAN'T EXECUTE(P)
13
Format (CHK instruction) check
• When switching from (STOP, PAUSE) to
(RUN, STEP
RUN)
CHK FORMAT ERR.
14
Unable to execute instruction
• When interruption occurred
• When switching from (STOP, PAUSE) to
(RUN, STEP
RUN)
CAN'T EXECUTE(I)
15
CPU e
rr
or
RAM check
• When switching ON or resetting
• When M9084 is ON during STOP
Stop
Flickering
RAM ERROR
20
Operation circuit check
• When switching ON or resetting
OPE.CIRCUIT ERR.
21
Watchdog error supervision
• Upon execution of END instruction
WDT ERROR
22
END instruction not executed
• Upon execution of END instruction
END NOT EXECUTE
24
Main CPU check
Always
MAIN CPU DOWN
26
I/
O er
ro
r
Module verification error
*1 (Default: stop)
Upon execution of END instruction
(However, not checked when M9084 is ON.)
Stop/Operate
Flickering/
ON
UNIT VERIFY ERR.
31
Fuse blown
*1 (Default: stop)
Upon execution of END instruction
(However, not checked when M9084 is ON.)
FUSE BREAK OFF
32
S
pec
ia
l f
u
nc
tion
mo
du
le
er
ro
r
Control bus check
Upon execution of FROM, TO instruction
Stop
Flickering
CONTROL-BUS ERR.
40
Special function module error
Upon execution of FROM, TO instruction
SP.UNIT DOWN
41
Link module error
• When switching ON or resetting
• When switching from (STOP, PAUSE) to
(RUN, STEP
RUN)
LINK UNIT ERROR
42
I/O interrupt error
When interruption occurs
I/O INT.ERROR
43
Special function module
allocation error
• When switching from (STOP, PAUSE) to
(RUN, STEP-RUN)
SP.UNIT LAY.ERR.
44
Special module access error
*1 (Default: stop)
Upon execution of FROM, TO instruction
Stop/Operate
Flickering/
ON
SP.UNIT ERROR
46
Link parameter error
• When switching from (STOP, PAUSE) to
(RUN, STEP-RUN)
Operate
ON
LINK PARA.ERROR
47
B
a
tter
y
Low battery
Always
(However, not checked when M9084 is ON.)
Operate
ON
BATTERY ERROR
70
Operation error
*1 (Default: stop)
Upon execution of each instruction
Stop/Operate
Flickering/
ON
OPERATION ERROR
*2
[<CHK> ERROR
]
50
CJ SCJ JMP CALL(P) FOR to NEXT
Содержание A2USCPU(S1)
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 Memo...
Страница 254: ...App 59 APPENDIX Appendix5 2 A1S61PN A1S62PN and A1S63P power supply modules Unit mm inch...
Страница 256: ...App 61 APPENDIX Appendix5 3 3 A1S35B main base unit Unit mm inch Appendix5 3 4 A1S38B main base unit Unit mm inch...
Страница 262: ...App 67 APPENDIX Appendix5 5 Memory cassette Appendix5 5 1 A2SNMCA 30KE memory cassette Unit mm inch...
Страница 271: ......
Страница 272: ......