APP -
27
APPENDICES
Appendix 2.2 Special Registers
Special registers are data registers of which applications have been determined inside the
PC. Therefore, do not write data to the special registers in the program (except the ones
with numbers marked 2 in the table).
Table App2.2 Special Register List
Number
Name
Description
Details
Applicable CPU
D9000
Fuse blow
Fuse blow module
number
• When fuse blown modules are detected, the lowest
number of detected units is stored in hexadecimal.
(Example: When fuses of Y50 to 6F output modules
have blown, "50" is stored in hexadecimal) To monitor
the number by peripheral devices, perform monitor
operation given in hexadecimal.
(Cleared when all contents of D9100 to D9107 are
reset to 0.)
• Fuse blow check is executed also to the output
modules of remote I/O stations.
Unusable with
A0J2H.
Only remote
I/O station
information
is valid for
A2C.
D9001
Fuse blow
Fuse blow module
number
• Stores the module numbers corresponding to setting
switch numbers or base slot numbers when fuse blow
occurred.
—
Dedicated to
A0J2H.
I/O Module for A0J2
Extension Base Unit
Setting
Switch
Stored Data
Base Unit
Slot No.
Stored Data
0
1
0
5
1
2
1
6
2
3
2
7
3
4
3
8
4
5
5
6
6
7
7
8
• In case of remote I/O station, (module I/O number/10H)
+ 1 is stored.
D9002
I/O module
verify error
I/O module verify
error unit number
• If an I/O module whose data is different from the
entered data when the power is turned on is detected,
the head I/O number of the detected module is stored
in hexadecimal. When the situation is detected in
multiple modules, the lowest number among the
module will be stored. (Storing method is the same as
that of D9000.) To monitor the number by peripheral
devices, perform monitor operation given in
hexadecimal.
(Cleared when all contents of D9116 to D9123 are
reset to 0.)
• I/O module verify check is executed also to the
modules of remote I/O terminals.
Unusable with
A0J2H.
Only remote
I/O station
information
is valid for
A2C.
• If an I/O module, of which data is different from data
entered, is detected when the power in turned on, the
I/O number corresponding to the setting switch No. or
base unit No. is stored.(Storing method is the same as
that of D9001).
• In case of remote I/O station, (module I/O number/10H)
+ 1 is stored.
—
Dedicated to
A0J2H.
Содержание A2USCPU(S1)
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 Memo...
Страница 254: ...App 59 APPENDIX Appendix5 2 A1S61PN A1S62PN and A1S63P power supply modules Unit mm inch...
Страница 256: ...App 61 APPENDIX Appendix5 3 3 A1S35B main base unit Unit mm inch Appendix5 3 4 A1S38B main base unit Unit mm inch...
Страница 262: ...App 67 APPENDIX Appendix5 5 Memory cassette Appendix5 5 1 A2SNMCA 30KE memory cassette Unit mm inch...
Страница 271: ......
Страница 272: ......