11. TROUBLESHOOTING
11.2.9 Flow for actions when the CPU module is not started up
The flow when the CPU module is not started up is described.
Complete
NO
YES
NO
YES
NO
NO
NO
YES
YES
NO
YES
NO
YES
YES
NO
YES
The CPU module is not started up.
Is the power supply
module LED ON?
Are all the power of the power
supply modules ON? Is the power supply
module wired correctly?
Try to connect the peripheral device.
Is it available
to communicate with
the peripheral device?
Is the extension cable
connected to the incorrect
direction? (Connected IN and
IN, or OUT and OUT?)
Is the RUN/STOP key
switch of the CPU
module at RESET?
at RESET
Not at RESET
Switch the power supply module and
confirm the LED lights.
Is CPU module up?
See Flowchart for actions when the
"POWER" LED is turned OFF
(Refer to .)
Review the wiring and turn the all
power supply ON.
Is CPU module up?
Is CPU module up?
Is CPU module up?
Make the PLC diagnosis, and execute
the troubleshooting according to the
result.
Switch the RUN/STOP key switch
to RUN.
Hardware error of the power supply
Possible hardware errors are described below.
1) CPU module
2)Main base unit, Extension base unit
3)Extension cable
4)Network module (Only when installed)
For the malfunctioning module even after executed the serial
operation check from the minimum system, please consult
your local Mitsubishi service center or representative,
explaining a detailed description of the problem.
Connect the extension cable.
Содержание A2USCPU(S1)
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 Memo...
Страница 254: ...App 59 APPENDIX Appendix5 2 A1S61PN A1S62PN and A1S63P power supply modules Unit mm inch...
Страница 256: ...App 61 APPENDIX Appendix5 3 3 A1S35B main base unit Unit mm inch Appendix5 3 4 A1S38B main base unit Unit mm inch...
Страница 262: ...App 67 APPENDIX Appendix5 5 Memory cassette Appendix5 5 1 A2SNMCA 30KE memory cassette Unit mm inch...
Страница 271: ......
Страница 272: ......