CPU MODULE
4.2.3
Setting ranges of timer and counter
(1) Timer setting range
(a) Default values of the timer setting ranges are as follows:
(b) When timer-use points are set to 257 or more, the default values will be as
follows:
(c) The timer type can be arbitrarily set in serial numbers, with T0 to T255 in 8 point
units, and T256 to T2047 in 16 point units.
By setting the timer points actually to be used, the timer processing time
subsequent to the END instruction can be shortened.
(d) Timer setting values are as follows:
(2) Counter setting range
(a) Default values of counter setting ranges are as follows:
(b) When the counter-use points are set to 257 points or more, the default values
will become as follows:
(c) A counter which can be setup as an interrupt counter must be in the range C244
to C255 only, and any counters outside the range cannot be set up.
The setup is made with parameters in C224 to C255 by one point for the
interrupt counter.
Any counter in the range C224 to C255 which is not set up as an interrupt
counter can be used as a normal counter.
Timer points
:256 points
100ms timer
:T0 to T199
10ms timer
:T200 to T255
Retentive timer
:None
100ms timer
:T0 to T199
10ms timer
:T200 to T255
100ms timer
:T256 to T2047
T0 to T255
: constant or word device (D)
T256 to T2047
: word device (D, W, R)
(Allocate a storage device for the set value by setting
parameters.)
Counter points
:256 points
Normal counter
:C0 to C255
Interrupt counter :None
Normal counter :C0 to C255
Normal counter :C256 to C1024
Содержание A2USCPU(S1)
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 Memo...
Страница 254: ...App 59 APPENDIX Appendix5 2 A1S61PN A1S62PN and A1S63P power supply modules Unit mm inch...
Страница 256: ...App 61 APPENDIX Appendix5 3 3 A1S35B main base unit Unit mm inch Appendix5 3 4 A1S38B main base unit Unit mm inch...
Страница 262: ...App 67 APPENDIX Appendix5 5 Memory cassette Appendix5 5 1 A2SNMCA 30KE memory cassette Unit mm inch...
Страница 271: ......
Страница 272: ......