2. Capacity code setting
(1) SW2
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
The switches are set to correspond to the unit capacity.
PVFY-P12NAMU-E1
PVFY-P18NAMU-E1
PVFY-P24NAMU-E1
PVFY-P30NAMU-E1
PVFY-P36NAMU-E1
PVFY-P48NAMU-E1
PVFY-P54NAMU-E1
3. Model setting
(1) SW4
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
Note:
Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop
(remote controller off). There is no need to power cycle the unit.
4. Power voltage setting
(1) SW5
1) Indoor control board
Dipswitch settings must be operated with the main power turned OFF.
Factory setting
220V
(208V)
240V
(230V)
Set SW5 to 240V side when the power supply is 230 volts.
When the power supply is 208 volts, set SW5 to 220V side.