5. Dipswitch setting (Factory setting)
1. Function setting
(1) SW1
Switch
position
Function
Switch setting
ON
OFF
1
Active Thermistor
(Intake air thermistor)
Built-in thermistor on the remote
controller
Indoor unit
2
Filter clogging
detection
Available
Unavailable
3
Filter life
2500 hr
100 hr
4
Outdoor air intake
Enabled
Disabled
5
Remote display
Thermo-ON signal
Fan output
6
Humidifier operation
During heating mode
During heating operation
7
Fan speed
Low
Very low
8
Fan speed at heating
Thermo-OFF
Preset fan speed
Follows the setting of SW1-7
9
Auto restart after
power failure
Enabled
Disabled
10
Power start/stop
Enabled
Disabled
1) Adress board
Factory setting
(2) SW3
Switch
position
Function
Switch setting
ON
OFF
1
Unit type
Cooling only
Heat pump
2
Heater
available
Heater available
Heater not available
3
-
-
-
4
Heater
control
Heater ON during defrost and error
Heater OFF during defrost and error
5
-
6
-
-
-
7
-
-
-
8
Heating
4-deg up
Disabled
Enabled
9
-
-
-
10
-
-
-
Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting