44
OCH771
Check Code Abnormal points and detection method
Cause
Judgment and action
U9
(4220)
Detailed
codes
PFC error (Overvoltage/
Undervoltage/Overcurrent)
PFC detected any of the following:
a) Increase of DC bus voltage
to 430 V. (ZM60-140V)
b) Decrease in PFC control
voltage to 12 V DC or lower.
c) Increase in input current
to 50 A peak. (For models
equipped with single-phase
PFC only) (ZM60-140V)
1
Abnormal increase in power source
voltage
2
Decrease in power source voltage,
instantaneous stop
3
Disconnection of compressor wiring
4
Misconnection of reactor
5
Defective outdoor power circuit board
6
Defective reactor
7
Disconnection or loose connection
of CN2 on the outdoor power circuit
board/controller circuit board
12
Check the field facility for the power
supply.
3
Correct the wiring (U.V.W phase) to
compressor. Refer to "10-8. TEST
POINT DIAGRAM". (Outdoor power cir-
cuit board).
4
Correct the wiring of reactor.
5
Replace outdoor power circuit board.
6
Replace reactor.
7
Check CN2 wiring.
10
20
PFC/IGBT error
(Undervoltage)
When Compressor is running,
DC bus voltage stays at 310V or
lower for consecutive 10 seconds
(ZM60–140V)
1
Incorrect switch settings on the
outdoor controller circuit board for
model select
2
Defective outdoor power circuit board
3
Defective outdoor controller circuit
board
1
Correction of a model select
2
Replace outdoor power circuit board.
3
Replace outdoor controller circuit board
Ud
(UD)*
(1504)
Over heat protection
Abnormal if outdoor pipe thermistor (TH3)
detects 70°C
or more during compressor
operation.
1
Defective outdoor fan (fan motor)
or short cycle of outdoor unit during
cooling operation
2
Defective outdoor pipe thermistor
(TH3)
3
Defective outdoor controller board
1
Check outdoor unit air passage.
23
Turn the power off and on again to
check the check code. If U4 is dis-
played, follow the U4 processing direc-
tion.
*The check code in the parenthesis indi-
cates PAR-4xMAA ("x" represents 0 or
later).
UF
(4100)
Compressor overcurrent interruption
(When compressor locked)
Abnormal if overcurrent of DC bus or
compressor is detected within 30 seconds
after compressor starts operating.
1
Stop valve is closed.
2
Decrease of power supply voltage
3
Looseness, disconnection or reverse
of compressor wiring connection
4
Defective compressor
5
Defective outdoor power board
6
DIP switch setting difference of out-
door controller circuit board.
1
Open stop valve.
2
Check facility of power supply.
3
Correct the wiring (U
•
V
•
W phase) to
compressor. Refer to "10-8. TEST
POINT DIAGRAM" (Outdoor power
circuit board).
4
Check compressor.
Refer to "10-5. HOW TO CHECK THE
PARTS".
5
Replace outdoor power circuit board.
6
Check the DIP switch setting of outdoor
controller circuit board. Refer to "Model
Select" in "1) Function of switches" in
"10-9. FUNCTION OF SWITCHES,
CONNECTORS AND JUMPERS".
UH
(5300)
Current sensor error or input current error
Abnormal of 38 A of input current is
detected, or 34 A or more of input current is
detected for 10 seconds continuously
1
Disconnection of compressor wiring
2
Defective circuit of current sensor on
outdoor power circuit board
3
Decrease of power supply voltage
1
Correct the wiring (U
•
V
•
W phase) to
compressor. Refer to "10-8. TEST
POINT DIAGRAM" (Outdoor power
circuit board).
2
Replace outdoor power circuit board.
3
Check the facility of power supply.
Содержание PUZ-ZM60VHA2
Страница 21: ...21 OCH771 PUZ ZM60VHA2 ET ER UK PUZ ZM71VHA2 ET ER UK 6 OUTLINES AND DIMENSIONS 1 2 1 1 2 Unit mm ...
Страница 23: ...23 OCH771 PUZ ZM60VHA2 ET ER UK PUZ ZM71VHA2 ET ER UK 7 WIRING DIAGRAM ...
Страница 24: ...24 OCH771 PUZ ZM100VKA2 ET ER UK ...
Страница 25: ...25 OCH771 PUZ ZM125VKA2 ET ER UK PUZ ZM140VKA2 ET ER UK ...
Страница 26: ...26 OCH771 PUZ ZM100YKA2 ET ER UK PUZ ZM125YKA2 ET ER UK PUZ ZM140YKA2 ET ER UK ...
Страница 27: ...27 OCH771 PUZ ZM200YKA2 UK PUZ ZM250YKA2 UK ...