Contents

1. Safety precautions

After installation work has been completed, explain the “Safety Precautions,” use, and 

maintenance of the unit to the customer according to the information in the Operation 

Manual and perform the test run to ensure normal operation. Both the Installation Manual 

and Operation Manual must be given to the user for keeping. These manuals must be 

passed on to subsequent users.

 : Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

/

 : Indicates warnings and cautions when using R32 refrigerant.

 Warning:

•   The unit must not be installed by the user. Ask a dealer or an authorized techni

-

cian to install and repair the unit. If the unit is installed incorrectly, water leakage, 

electric shock, or fire may result.

•   For  installation  and  relocation  work,  follow  the  instructions  in  the  Installation 

Manual and use tools and pipe components specifically made for use with R32 

refrigerant. If pipe components not designed for R32 refrigerant are used and the 

unit is not installed correctly, the pipes may burst and cause damage or injuries. 

In addition, water leakage, electric shock, or fire may result.

•   The unit must be installed according to the instructions in order to minimize the 

risk of damage from earthquakes, typhoons, or strong winds. An incorrectly in

-

stalled unit may fall down and cause damage or injuries.

•   The unit must be securely installed on a structure that can sustain its weight. If 

the unit is mounted on an unstable structure, it may fall down and cause damage 

or injuries.

•   If  the  air  conditioner  is  installed  in  a  small  room,  measures  must  be  taken  to 

prevent the refrigerant concentration in the room from exceeding the safety limit 

in the event of refrigerant leakage. Consult a dealer regarding the appropriate 

measures to prevent the allowable concentration from being exceeded. Should 

the refrigerant leak and cause the concentration limit to be exceeded, hazards 

due to lack of oxygen in the room may result.

•   Ventilate the room if refrigerant leaks during operation. If refrigerant comes into 

contact with a flame, poisonous gases will be released.

•   All electric work must be performed by a qualified technician according to local 

regulations and the instructions given in this manual. The units must be powered 

by dedicated power lines and the correct voltage and circuit breakers must be 

used. Power lines with insufficient capacity or incorrect electrical work may result 

in electric shock or fire.

•   Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to 

connect the refrigerant pipes. If the pipes are not connected correctly, the unit will 

not be properly grounded and electric shock may result.

•   Use only specified cables for wiring. The wiring connections must be made se

-

curely with no tension applied on the terminal connections. Also, never splice the 

cables for wiring (unless otherwise indicated in this document).

  Failure to observe these instructions may result in overheating or a fire.

•  If the supply cord is damaged, it must be replaced by the manufacturer, its service 

agent or similarly qualified persons in order to avoid hazard.

•  The appliance shall be installed in accordance with national wiring regulations.

•   The terminal block cover panel of the outdoor unit must be firmly attached. If the 

cover panel is mounted incorrectly and dust and moisture enter the unit, electric 

shock or fire may result.

•   When installing or relocating, or servicing the air conditioner, use only the speci

-

fied refrigerant (R32) to charge the refrigerant lines. Do not mix it with any other 

refrigerant and do not allow air to remain in the lines.

   If air is mixed with the refrigerant, then it can be the cause of abnormal high pres

-

sure in the refrigerant line, and may result in an explosion and other hazards.

   The use of any refrigerant other than that specified for the system will cause me

-

chanical failure or system malfunction or unit breakdown. In the worst case, this 

could lead to a serious impediment to securing product safety.

•   Use only accessories authorized by Mitsubishi Electric and ask a dealer or an au

-

thorized technician to install them. If accessories are incorrectly installed, water 

leakage, electric shock, or fire may result.

•   Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are not 

performed correctly, water leakage, electric shock, or fire may result.

•   The user should never attempt to repair the unit or transfer it to another location. 

If the unit is installed incorrectly, water leakage, electric shock, or fire may result. 

If the air conditioner must be repaired or moved, ask a dealer or an authorized 

technician.

•   After installation has been completed, check for refrigerant leaks. If refrigerant 

leaks into the room and comes into contact with the flame of a heater or portable 

cooking range, poisonous gases will be released.

•  Do not use means to accelerate the defrosting process or to clean, other than 

those recommended by the manufacturer.

•  The appliance shall be stored in a room without continuously operating ignition 

sources (for example: open flames, an operating gas appliance or an operating 

electric heater).

•  Do not pierce or burn.

•  Be aware that refrigerants may not contain an odour.

/

  Pipe-work shall be protected from physical damage.

•  The installation of pipe-work shall be kept to a minimum.

•  Compliance with national gas regulations shall be observed.

•  Keep any required ventilation openings clear of obstruction.

/

  Do not use low temperature solder alloy in case of brazing the refrigerant pipes.

/

  When performing brazing work, be sure to ventilate the room sufficiently.

  Make sure that there are no hazardous or flammable materials nearby.

  When performing the work in a closed room, small room, or similar location, make 

sure that there are no refrigerant leaks before performing the work.

  If refrigerant leaks and accumulates, it may ignite or poisonous gases may be 

released.

/

  The appliance shall be stored in a well-ventilated area where the room size cor

-

responds to the room area as specified for operation.

/

  Keep  gas-burning appliances, electric  heaters,  and other fire  sources  (ignition 

sources) away from the location where installation, repair, and other air condi

-

tioner work will be performed.

  If refrigerant comes into contact with a flame, poisonous gases will be released.

/

  Do not smoke during work and transportation.

 Warning:

Describes precautions that must be observed to prevent danger of injury or death 

to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

Note: This symbol mark is for EU countries only.

This symbol mark is according to the directive 2012/19/EU Article 14 Information for users and Annex IX.

Your MITSUBISHI ELECTRIC product is designed and manufactured with high quality materials and components which can be recycled and reused.

This symbol means that electrical and electronic equipment, at their end-of-life, should be disposed of separately from your household waste.

Please, dispose of this equipment at your local community waste collection/recycling centre.

In the European Union there are separate collection systems for used electrical and electronic product.

Please, help us to conserve the environment we live in!

 Caution:

•  Do not vent R32 into the atmosphere.

 

 Before installing the unit, make sure you read all the “Safety precautions”. 

1. Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2. Installation location  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

3. Installing the outdoor unit   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

4. Installing the refrigerant piping   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5. Drainage piping work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

6. Electrical work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

7. Test run  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

8. Special functions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

9. System control (Fig. 9-1)  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

10. Specifications

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT

WARNING

(Risk of fire)

This mark is for R32 refrigerant only. Refrigerant type is written on nameplate of outdoor unit.

In case that refrigerant type is R32, this unit uses a flammable refrigerant.

If refrigerant leaks and comes in contact with fire or heating part, it will create harmful gas and there is risk of fire.

Read the OPERATION MANUAL carefully before operation.

Service personnel are required to carefully read the OPERATION MANUAL and INSTALLATION MANUAL before operation.

Further information is available in the OPERATION MANUAL, INSTALLATION MANUAL, and the like.

BH79D314H06_EN.indd   2

2017/02/10   8:46:43

Содержание PUZ-ZM-HA

Страница 1: ...resente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓΧEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ Για σωστή και ασφαλή χρήση διαβάστε προσεκτικά αυτό το εγχειρίδιο καθώς και το εγχειρίδιο εγκατάστασης της εσωτερικής μονάδας προτού εγκαταστήσετε τη μονάδα του κλιματιστικού MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este ma...

Страница 2: ...ng product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an au thorized technician to install them If accessories are incorrectly installed water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric shock or fire may result The user should never a...

Страница 3: ... capacity is larger than the specified capacity breakdown or fire may result 1 4 Before starting the test run Caution Turn on the main power switch more than 12 hours before starting operation Starting operation just after turning on the power switch can severely damage the internal parts Keep the main power switch turned on during the operation season Before starting operation check that all pane...

Страница 4: ... situate the air outlet of the unit so that it is not directly exposed to strong winds Strong wind entering the air outlet may impede the normal airflow and a malfunction may result The following shows three examples of precautions against strong winds 1 Face the air outlet towards the nearest available wall about 500 mm away from the wall Fig 2 4 2 Install an optional air guide if the unit is ins...

Страница 5: ...ocally added refrigerant C Create an appropriate ventilation open area Make sure that the width of the open area is 0 9 m or more and the height of the open area is 0 15 m or more However the height from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m A...

Страница 6: ...tallation manual Install the indoor unit so that the height from the floor to the bottom of the indoor unit is h0 for wall mounted 1 8 m or more for ceiling suspended cassette and ceiling coucealed 2 2 m or more There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 4 1 5 6 2 0 8 2 5 10 3 0 12 3 5 14 4 0 16 4 5 20 5 0 24...

Страница 7: ...zene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thick nesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sul furic compounds oxidants debris or du...

Страница 8: ...y a thin layer of refrigeration oil Ap plied on site When usual pipe sealing is used refer to Table 1 for flaring of R32 refrigerant pipes The size adjustment gauge can be used to confirm A measurements Table 1 Fig 4 2 Copper pipe O D mm A mm Flare tool for R32 Flare tool for R22 R407C Clutch type ø6 35 1 4 0 0 5 1 0 1 5 ø9 52 3 8 0 0 5 1 0 1 5 ø12 7 1 2 0 0 5 1 0 1 5 ø15 88 5 8 0 0 5 1 0 1 5 ø19 ...

Страница 9: ...ipe connec tion sections of the outdoor unit Do not use the refrigerant from the unit to purge air from the refrigerant lines After the valve work is completed tighten the valve caps to the correct torque 20 to 25 N m 200 to 250 kgf cm Failure to replace and tighten the caps may result in refrigerant leakage In addition do not damage the insides of the valve caps as they act as a seal to prevent r...

Страница 10: ...l attached to the unit Refer to the 1 5 Using R32 refrigerant air conditioners for more information Be careful when installing multiple units Connecting to an incorrect indoor unit can lead to abnormally high pressure and have a serious effect on operation performance R32 maintenance refilling Before servicing refilling the equipment with R32 to ensure that there is no risk of explosion from elect...

Страница 11: ... pipes for ZM35 71 models The existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option ZM35 50 ZM60 71 Drain socket PAC SJ08DS E PAC SH71DS E Drain pan PAC SG63DP E PAC SG64DP E Limits of refrigerant piping...

Страница 12: ... E E For Power For Power L N S1 S2 S3 J J F Terminal block G Indoor Outdoor connection terminal block S1 S2 S3 H Service panel I Clamp Clamp the cables so that they do not contact the center of the service panel or the gas valve J Earth terminal J J ZM35 50 Note If the protective sheet for the electrical box is removed during servicing be sure to reinstall it Caution Be sure to install N Line With...

Страница 13: ... Max for PEA Wiring size 3 1 5 Polar 3 The 10 m wire is attached in the remote controller accessory 4 The figures are NOT always against the ground S3 terminal has 24 VDC against S2 terminal However between S3 and S1 these terminals are NOT electrically insulated by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and ...

Страница 14: ...med up at least 12 hours to prevent breakdown 4 If the insulation resistance rises above 1 M the compressor is not faulty Caution The compressor will not operate unless the power supply phase connection is correct Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the...

Страница 15: ... twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 A Fig 8 1 3 Because the unit automatically stops in about 2 to 3 minutes when the refrigerant collecting operation is completed LED1 off LED2 lit be sure to quickly close the gas stop valve If LED1 is lit and LED2 is off and the outdoor unit is stopped refrig erant collection is not properly ...

Страница 16: ...sabilidade que os aparelhos de ar condicionado e bombas de calor abaixo descritos para uso residencial comercial e de indústria ligeira erklærer hermed under eneansvar at de herunder beskrevne airconditionanlæg og varmepumper til brug i privat boligbyggeri erhvervsområder og inden for let industri intygar härmed att luftkonditioneringarna och värmepumparna som beskrivs nedan för användning i bostä...

Страница 17: ... Het Engels is het origineel De andere taalversies zijn vertalingen van het origineel VOORZICHTIG Het lekken van koelvloeistof kan verstikking veroorzaken Zorg voor ventilatie in overeenstemming met EN378 1 Isoleer de leidingen met isolatiemateriaal Direct contact met de onbedekte leidingen kan leiden tot brandwonden of bevriezing Stop nooit batterijen in uw mond om inslikking te voorkomen Het ins...

Страница 18: ...0 150 1000 300 200 1000 300 1000 1000 1000 300 500 400 1000 100 1000 400 2000 300 1000 500 150 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 Fig 2 19 UNIT mm Max 500 Max 500 Max 300 ...

Страница 19: ...sh Branch Westgate Business Park Ballymount Dublin 24 Ireland Italian Branch Centro Direzionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scand...

Отзывы: