background image

15

1 2 3 4 5 6

8.1. Low noise mode (on-site modification) (Fig. 8-1)

By performing the following modification, operation noise of the outdoor unit can be

reduced by about 3-4 dB.

The low noise mode will be activated when a commercially available timer or the

contact input of an ON/OFF switch is added to the CNDM connector (option) on the

control board of the outdoor unit.

•   The ability varies according to the outdoor temperature and conditions, etc.

1

  Complete the circuit as shown when using the external input adapter  

 

(PAC-SC36NA-E). (Option)

2

 SW7-1 (Outdoor unit control board): OFF

3

  SW1 ON: Low noise mode

  SW1 OFF: Normal operation

A

  Circuit diagram example (low noise mode)

B

  On-site arrangement

C

  External input adapter (PAC-SC36NA-E)

X: Relay

D

  Outdoor unit control board

E

  Max. 10 m

F

  Power supply for relay

8.3. Refrigerant collecting (pump down)

Perform the following procedures to collect the refrigerant when moving the indoor 

unit or the outdoor unit.

1

  Supply power (circuit breaker).

  *   When power is supplied, make sure that “CENTRALLY CONTROLLED” is not 

displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis-

played, the refrigerant collecting (pump down) cannot be completed normally.

  *   Start-up of the indoor-outdoor communication takes about 3 minutes after the 

power (circuit breaker) is turned on. Start the pump-down operation 3 to 4 

minutes after the power (circuit breaker) is turned ON.

2

  After the liquid stop valve is closed, set the SWP switch on the control board of 

the outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and 

outdoor units) start operating and refrigerant collecting operation begins. LED1 

and LED2 on the control board of the outdoor unit are lit.

  *  

Only set the SWP switch (push-button type) to ON if the unit is stopped. However, even 

if the unit is stopped and the SWP switch is set to ON less than 3 minutes after the 

compressor stops, the refrigerant collecting operation cannot be performed. Wait until 

compressor has been stopped for 3 minutes and then set the SWP switch to ON again.

*  Set the refrigerant address using the DIP switch of the outdoor unit.

1

  Wiring from the Remote Control

This wire is connected to TB5 (terminal board for remote controller) of the indoor 

unit (non-polar).

2

 When a Different Refrigerant System Grouping is Used.

Up to 16 refrigerant systems can be controlled as one group using the slim MA remote controller.

Note:

In single refrigerant system (twin/triple), there is no need of wiring 

2

.

A

  Outdoor unit

B

  Indoor unit

C

  Master remote controller

D

  Subordinate remote controller

E

  Standard 1:1 (Refrigerant address = 00)

F

  Simultaneous twin (Refrigerant address = 01)

G

  Simultaneous triple (Refrigerant address = 02)

E

  SW 1 - 3 ~ 6

F

  SW 1 - 3 ~ 6

G

  SW 1 - 3 ~ 6

A

Fig. 8-1

3

  Because the unit automatically stops in about 2 to 3 minutes when the refrigerant 

collecting operation is completed (LED1 off, LED2 lit), be sure to quickly close the 

gas stop valve. If LED1 is lit and LED2 is off and the outdoor unit is stopped, refrig-

erant collection is not properly performed. Open the liquid stop valve completely, 

and then repeat step 

2

 after 3 minutes have passed.

  *   If the refrigerant collecting operation has been completed normally (LED1 off, 

LED2 lit), the unit will remain stopped until the power supply is turned off.

4

 Turn off the power supply (circuit breaker).

  *   Note that when the extension piping is very long with large refrigerant amount, 

it may not be possible to perform a pump-down operation. When performing 

the pump-down operation, make sure that the low pressure is lowered to near 

0 MPa (gauge).

 Warning:

When pumping down the refrigerant, stop the compressor before disconnect

-

ing the refrigerant pipes. The compressor may burst if air etc. get into it.

9. System control (Fig. 9-1)

Fig. 9-1

SW1

Function table

  <SW1>

Function

Operation according to 

switch setting

ON

OFF

SW1

function 

settings

1 Compulsory de-

frosting

Start

Normal

2 Error history clear

Clear

Normal

3

4

5

6

Refrigerant system 

address setting

Settings for outdoor unit 

addresses 0 to 15

TB1

A

G

F

A

A

E

B

B

B

B

B

B

D

C

TB1

TB1

TB4

TB5

TB4

TB5

TB4

TB4

TB5

TB4

TB4

1

1

2

 ON

 OFF

 ON

 OFF

 ON

 OFF

3    4    5    6

3    4    5    6

3    4    5    6

 ON

 OFF

2

A

   Circuit diagram example (Demand function)

B

   On-site  arrangement

X, Y: Relay

C

  External input adapter (PAC-SC36NA-E)

D

  Outdoor unit control board

E

  Max. 10 m

F

  Power supply for relay

8.2. Demand function (on-site modification) (Fig. 8-2)

By performing the following  modification, energy consumption  can be reduced  to 

0–100% of the normal consumption.

The demand function will be activated when a commercially available timer or the

contact input of an ON/OFF switch is added to the CNDM connector (option) on the

control board of the outdoor unit.

1

  Complete the circuit as shown when using the external input adapter  

 

(PAC-SC36NA-E). (Option)

2

  By setting SW7-1 on the control board of the outdoor unit, the energy consump-

tion (compared to the normal consumption) can be limited as shown below.

SW7-1

SW2

SW3

Energy consumption 

Demand 

function

ON

OFF

OFF

100%

ON

OFF

75%

ON

ON

50%

OFF

ON

0% (Stop)

A

Fig. 8-2

8. Special functions

SW1

1

3

E

B

F

CNDM

X

X

SW2

SW3

1

3

CNDM

Y

X

X

Y

F

B

E

C

D

C

D

10. Specifications

Outdoor model

PUZ-ZM35VKA

PUZ-ZM50VKA

PUZ-ZM60VHA

PUZ-ZM71VHA

Power supply (V / Phase / Hz)

230 / Single / 50

Dimensions (H × W × D)

mm

630 × 809 × 300

943 × 950 × 330(+30)

Sound level *1

Cooling

dB(A)

44

44

47

47

Heating

46

46

49

49

*1 Measured under rated operation frequency.

Brown

Red

Orange

Brown

Red

Orange

BH79D314H06_EN.indd   15

2017/02/10   8:46:55

Содержание PUZ-ZM-HA

Страница 1: ...resente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓΧEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ Για σωστή και ασφαλή χρήση διαβάστε προσεκτικά αυτό το εγχειρίδιο καθώς και το εγχειρίδιο εγκατάστασης της εσωτερικής μονάδας προτού εγκαταστήσετε τη μονάδα του κλιματιστικού MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este ma...

Страница 2: ...ng product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an au thorized technician to install them If accessories are incorrectly installed water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric shock or fire may result The user should never a...

Страница 3: ... capacity is larger than the specified capacity breakdown or fire may result 1 4 Before starting the test run Caution Turn on the main power switch more than 12 hours before starting operation Starting operation just after turning on the power switch can severely damage the internal parts Keep the main power switch turned on during the operation season Before starting operation check that all pane...

Страница 4: ... situate the air outlet of the unit so that it is not directly exposed to strong winds Strong wind entering the air outlet may impede the normal airflow and a malfunction may result The following shows three examples of precautions against strong winds 1 Face the air outlet towards the nearest available wall about 500 mm away from the wall Fig 2 4 2 Install an optional air guide if the unit is ins...

Страница 5: ...ocally added refrigerant C Create an appropriate ventilation open area Make sure that the width of the open area is 0 9 m or more and the height of the open area is 0 15 m or more However the height from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m A...

Страница 6: ...tallation manual Install the indoor unit so that the height from the floor to the bottom of the indoor unit is h0 for wall mounted 1 8 m or more for ceiling suspended cassette and ceiling coucealed 2 2 m or more There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 4 1 5 6 2 0 8 2 5 10 3 0 12 3 5 14 4 0 16 4 5 20 5 0 24...

Страница 7: ...zene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thick nesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sul furic compounds oxidants debris or du...

Страница 8: ...y a thin layer of refrigeration oil Ap plied on site When usual pipe sealing is used refer to Table 1 for flaring of R32 refrigerant pipes The size adjustment gauge can be used to confirm A measurements Table 1 Fig 4 2 Copper pipe O D mm A mm Flare tool for R32 Flare tool for R22 R407C Clutch type ø6 35 1 4 0 0 5 1 0 1 5 ø9 52 3 8 0 0 5 1 0 1 5 ø12 7 1 2 0 0 5 1 0 1 5 ø15 88 5 8 0 0 5 1 0 1 5 ø19 ...

Страница 9: ...ipe connec tion sections of the outdoor unit Do not use the refrigerant from the unit to purge air from the refrigerant lines After the valve work is completed tighten the valve caps to the correct torque 20 to 25 N m 200 to 250 kgf cm Failure to replace and tighten the caps may result in refrigerant leakage In addition do not damage the insides of the valve caps as they act as a seal to prevent r...

Страница 10: ...l attached to the unit Refer to the 1 5 Using R32 refrigerant air conditioners for more information Be careful when installing multiple units Connecting to an incorrect indoor unit can lead to abnormally high pressure and have a serious effect on operation performance R32 maintenance refilling Before servicing refilling the equipment with R32 to ensure that there is no risk of explosion from elect...

Страница 11: ... pipes for ZM35 71 models The existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option ZM35 50 ZM60 71 Drain socket PAC SJ08DS E PAC SH71DS E Drain pan PAC SG63DP E PAC SG64DP E Limits of refrigerant piping...

Страница 12: ... E E For Power For Power L N S1 S2 S3 J J F Terminal block G Indoor Outdoor connection terminal block S1 S2 S3 H Service panel I Clamp Clamp the cables so that they do not contact the center of the service panel or the gas valve J Earth terminal J J ZM35 50 Note If the protective sheet for the electrical box is removed during servicing be sure to reinstall it Caution Be sure to install N Line With...

Страница 13: ... Max for PEA Wiring size 3 1 5 Polar 3 The 10 m wire is attached in the remote controller accessory 4 The figures are NOT always against the ground S3 terminal has 24 VDC against S2 terminal However between S3 and S1 these terminals are NOT electrically insulated by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and ...

Страница 14: ...med up at least 12 hours to prevent breakdown 4 If the insulation resistance rises above 1 M the compressor is not faulty Caution The compressor will not operate unless the power supply phase connection is correct Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the...

Страница 15: ... twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 A Fig 8 1 3 Because the unit automatically stops in about 2 to 3 minutes when the refrigerant collecting operation is completed LED1 off LED2 lit be sure to quickly close the gas stop valve If LED1 is lit and LED2 is off and the outdoor unit is stopped refrig erant collection is not properly ...

Страница 16: ...sabilidade que os aparelhos de ar condicionado e bombas de calor abaixo descritos para uso residencial comercial e de indústria ligeira erklærer hermed under eneansvar at de herunder beskrevne airconditionanlæg og varmepumper til brug i privat boligbyggeri erhvervsområder og inden for let industri intygar härmed att luftkonditioneringarna och värmepumparna som beskrivs nedan för användning i bostä...

Страница 17: ... Het Engels is het origineel De andere taalversies zijn vertalingen van het origineel VOORZICHTIG Het lekken van koelvloeistof kan verstikking veroorzaken Zorg voor ventilatie in overeenstemming met EN378 1 Isoleer de leidingen met isolatiemateriaal Direct contact met de onbedekte leidingen kan leiden tot brandwonden of bevriezing Stop nooit batterijen in uw mond om inslikking te voorkomen Het ins...

Страница 18: ...0 150 1000 300 200 1000 300 1000 1000 1000 300 500 400 1000 100 1000 400 2000 300 1000 500 150 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 Fig 2 19 UNIT mm Max 500 Max 500 Max 300 ...

Страница 19: ...sh Branch Westgate Business Park Ballymount Dublin 24 Ireland Italian Branch Centro Direzionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scand...

Отзывы: