4
B
2. Installation location
Fig. 2-5
Fig. 2-4
Fig. 2-6
Fig. 2-3
Fig. 2-2
2.2. Choosing the outdoor unit installation location
/
R32 is heavier than air—as well as other refrigerants—so tends to accumulate at
the base (in the vicinity of the floor). If R32 accumulates around base, it may reach
a flammable concentration in case room is small. To avoid ignition, maintaining a
safe work environment is required by ensuring appropriate ventilation. If a refrig-
erant leak is confirmed in a room or an area where there is insufficient ventilation,
refrain from using of flames until the work environment can be improved by ensur
-
ing appropriate ventilation.
• Avoid locations exposed to direct sunlight or other sources of heat.
• Select a location from which noise emitted by the unit will not inconvenience
neighbors.
• Select a location permitting easy wiring and pipe access to the power source and
indoor unit.
• Avoid locations where combustible gases may leak, be produced, flow, or accu
-
mulate.
• Note that water may drain from the unit during operation.
• Select a level location that can bear the weight and vibration of the unit.
• Avoid locations where the unit can be covered by snow. In areas where heavy
snow fall is anticipated, special precautions such as raising the installation loca-
tion or installing a hood on the air intake must be taken to prevent the snow from
blocking the air intake or blowing directly against it. This can reduce the airflow
and a malfunction may result.
• Avoid locations exposed to oil, steam, or sulfuric gas.
• Use the transportation handles of the outdoor unit to transport the unit. If the unit
is carried from the bottom, hands or fingers may be pinched.
• Refrigerant pipes connection shall be accessible for maintenance purposes.
/
Install outdoor units in a place where at least one of the four sides is open, and in
a sufficiently large space without depressions. (Fig. 2-2)
2.3. Outline dimensions (Outdoor unit) (Fig. 2-3)
2.4. Ventilation and service space
2.4.1. Windy location installation
When installing the outdoor unit on a rooftop or other location unprotected from the
wind, situate the air outlet of the unit so that it is not directly exposed to strong winds.
Strong wind entering the air outlet may impede the normal airflow and a malfunction
may result.
The following shows three examples of precautions against strong winds.
1
Face the air outlet towards the nearest available wall about 500 mm away from
the wall. (Fig. 2-4)
2
Install an optional air guide if the unit is installed in a location where strong winds
from a typhoon, etc. may directly enter the air outlet. (Fig. 2-5)
A
Air protection guide
3
Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-6)
B
Wind direction
2.4.2. When installing a single outdoor unit (Refer to the last page)
Minimum dimensions are as follows, except for Max., meaning Maximum dimen-
sions, indicated.
Refer to the figures for each case.
1
Obstacles at rear only (Fig. 2-7)
2
Obstacles at rear and above only (Fig. 2-8)
• Do not install the optional air outlet guides for upward airflow.
3
Obstacles at rear and sides only (Fig. 2-9)
* 350 for ZM35, 50.
4
Obstacles at front only (Fig. 2-10)
5
Obstacles at front and rear only (Fig. 2-11)
6
Obstacles at rear, sides, and above only (Fig. 2-12)
* 350 for ZM35, 50.
• Do not install the optional air outlet guides for upward airflow.
2.4.3. When installing multiple outdoor units (Refer to the last page)
Leave 350 mm for ZM35, 50 and 10 mm for ZM60, 71 space or more between the
units.
1
Obstacles at rear only (Fig. 2-13)
2
Obstacles at rear and above only (Fig. 2-14)
• No more than 3 units must be installed side by side. In addition, leave space as shown.
• Do not install the optional air outlet guides for upward airflow.
3
Obstacles at front only (Fig. 2-15)
4
Obstacles at front and rear only (Fig. 2-16)
5
Single parallel unit arrangement (Fig. 2-17)
*
When using an optional air outlet guide installed for upward airflow, the clearance is
500 mm or more.
6
Multiple parallel unit arrangement (Fig. 2-18)
*
When using an optional air outlet guide installed for upward airflow, the clearance is
1000 mm or more.
7
Stacked unit arrangement (Fig. 2-19)
• The units can be stacked up to two units high.
• No more than 2 stacked units must be installed side by side. In addition, leave space as
shown.
■
ZM35, 50
■
ZM60, 71
A
950
330
+25
943
175
600
370
809
500
62
154.5
300+23
630
360
OK
OK
OK
NG
BH79D314H06_EN.indd 4
2017/02/10 8:46:50