background image

5

4. Installing the refrigerant piping

A

Flare cutting dimensions

B

Flare nut tightening torque

90

°

 

±

0.5

°

ø

A

R1/64 to R1/32

A

45

°±

2

°

B

C

D

Fig. 4-1

4.1. Precautions for devices that use R410A refrigerant

• Refer to page 3 for precautions not included below on using air conditioners

with R410A refrigerant.

• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil

applied to the flared sections.

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the table to the below. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.

 Warning:

When installing or moving the air conditioner, use only the specified refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refriger-
ant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.

A12, A18

A24-A42

Liquid pipe

ø6.35 mm, 1/4inch

ø9.52 mm, 3/8 inch

thickness 0.8 mm, 1/32 inch

thickness 0.8 mm, 1/32 inch

Gas pipe

ø12.7 mm, 1/2 inch

ø15.88 mm, 5/8 inch

thickness 0.8 mm, 1/32 inch

thickness 1.0 mm, 3/64 inch

• Do not use pipes thinner than those specified above.

4.2. Connecting pipes (Fig. 4-1)

• When commercially available copper pipes are used, wrap liquid and gas pipes

with commercially available insulation materials (heat-resistant to 100 °C, 212 °F or
more, thickness of 12 mm, 1/2 inch or more).

• The indoor parts of the drain pipe should be wrapped with polyethylene foam insu-

lation materials (specific gravity of 0.03, thickness of 9 mm, 23/64 inch or more).

• Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening

flare nut. 

A

• Use two wrenches to tighten piping connections. 

B

• Use leak detector or soapy water to check for gas leaks after connections are com-

pleted.

• Apply refrigerating machine oil over the entire flare seat surface. 

C

• Use the flare nuts for the following pipe size. 

D

A12, A18

A24, A42

Gas side

Pipe size (mm, inch)

ø12.7, 1/2”

ø15.88, 5/8”

Liquid side

Pipe size (mm, inch)

ø6.35, 1/4”

ø9.52, 3/8”

*1: The flare nut is attached to its pipe.
*2: The flare nut is in the outdoor unit accessory.

Do not use the flare nut attached. If it is used, a gas leakage or even a pipe
extraction may occur.

• When bending the pipes, be careful not to break them. Bend radii of 100 mm,

3-15/16 inch to 150 mm, 5-27/32 inch are sufficient.

• Make sure the pipes do not contact the compressor. Abnormal noise or vibration

may result.

1

 Pipes must be connected starting from the indoor unit.

Flare nuts must be tightened with a torque wrench.

2

 Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil

(Applied on site).

A

(Fig. 4-1)

Copper pipe O.D.

Flare dimensions

 øA dimensions

(mm)

(inch)

(mm)

(inch)

ø6.35

1/4”

8.7 - 9.1

11/32 - 23/64

ø9.52

3/8”

12.8 - 13.2

1/2 - 33/64

ø12.7

1/2”

16.2 - 16.6 41/64 - 21/32

ø15.88

5/8”

19.3 - 19.7 49/64 - 25/32

Copper pipe O.D.

Flare nut O.D.

Tightening torque

(mm)

(inch)

(mm)

(inch)

(N·m)

(ft·lbs)

ø6.35

1/4”

17

43/64

14 - 18

10 - 13

ø9.52

3/8”

22

7/8

34 - 42

25 - 30

ø12.7

1/2”

26

 1 - 3/64

49 - 61

35 - 44

ø15.88

5/8”

29

1 - 9/64

68 - 82

49 - 59

B

(Fig. 4-1)

4.3. Refrigerant piping (Fig. 4-3)

For A12, A18

Remove the service panel 

D

 (one screw).

For A24-A42

Remove the service panel 

D

 (three screws) and the front piping cover 

A

 (two screws)

and rear piping cover 

B

 (two screws).

1

Perform refrigerant piping connections for the indoor/outdoor unit when the out-
door unit’s stop valve is completely closed.

2

Vacuum-purge air from the indoor unit and the connection piping.

3

After connecting the refrigerant pipes, check the connected pipes and the indoor
unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)

4

Vacuumize the refrigerant lines through the service port of the liquid stop valve
and then open the stop valves completely (for both the liquid and gas stop valves).
This will completely connect the refrigerant lines of the indoor and outdoor units.

• If the stop valves are left closed and the unit is operated, the compressor and

control valves will be damaged.

• Use a leak detector or soapy water to check for gas leaks at the pipe connec-

tion sections of the outdoor unit.

• Do not use the refrigerant from the unit to purge air from the refrigerant lines.
• After the valve work is completed, tighten the valve caps to the correct torque:

20 to 25 N·m, 14 to 18 ft·lbs (200 to 250 kgf·cm).
Failure to replace and tighten the caps may result in refrigerant leakage. In
addition, do not damage the insides of the valve caps as they act as a seal to
prevent refrigerant leakage.

5

 Use sealant to seal the ends of the thermal insulation around the pipe connection

sections to prevent water from entering the thermal insulation.

(inch)

Fig. 4-3

C

B

A

E

D

A

Front piping cover

B

Piping cover

C

Stop valve

D

Service panel

E

Band radius : 100 mm, 3-15/16 inch-150 mm, 5-27/32 inch

D

A24-A42

A12, A18

 BG79U896H02_en

06.5.31, 14:31

5

Содержание PUY-A NHA

Страница 1: ...indoor unit installation manual thoroughly before installing the air conditioner unit MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado Air Conditioners PUZ A NHA PUZ A NHA BS PUY A NHA PUY A NHA BS FOR INSTALLER PARA EL INSTALADOR ...

Страница 2: ...ure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric shock or fire m...

Страница 3: ...kylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessa...

Страница 4: ...an optional air outlet guide the clearance for A42 models is 1000 mm 39 3 8 inch or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for A42 models is 1000 mm 39 3 8 inch or more 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for upward airflow the clearance is 500 1000 mm 19 11 16 39 3 8 inch or m...

Страница 5: ...occur When bending the pipes be careful not to break them Bend radii of 100 mm 3 15 16 inch to 150 mm 5 27 32 inch are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit Flare nuts must be tightened with a torque wrench 2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigerat...

Страница 6: ...ps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result I Double spanner section Do not apply a spanner other than to this sec tion Doing so would cause coolant leaks J Seal section Seal the end of the heat insulation material at the pipe connection section with whatever seal material you have on hand so that water does not infiltrate the heat insulati...

Страница 7: ...n drain piping is necessary use the drain socket or the drain pan option A12 A18 A24 A42 Drain socket PAC SG61DS E Drain pan PAC SG63DP E PAC SG64DP E A B C D E Fig 6 1 Fig 6 2 A24 A42 A12 A18 A Earth terminal B Terminal block C Clamp D Service panel E Wire the cables so that they do not contact the center of the service panel or the gas valve 6 1 Outdoor unit Fig 6 1 Fig 6 2 1 Remove the service ...

Страница 8: ...8 A12 A18 CORD COVER CONDUIT COVER CABLE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A24 42 ...

Страница 9: ... for refrigerant leakage looseness in the power supply or control wiring wrong polarity and no disconnection of one phase in the supply s Use a 500 volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1 0MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit terminals Warning Do not use the air conditioner if the insulat...

Страница 10: ...he contact input of an ON OFF switch is added to the CNDM connector option on the control board of the outdoor unit The capacity may be insufficient according to the outdoor temperature and condi tions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA Option 2 SW1 ON Low noise mode SW1 OFF Normal operation 8 2 Refrigerant collecting pump down Perform the followin...

Страница 11: ... 13 16 39 3 8 59 1 16 39 3 8 59 1 16 11 13 16 19 11 16 19 11 16 39 3 8 15 3 4 23 5 8 39 3 8 78 23 32 3 15 16 5 29 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 15 3 4 23 5 8 78 23 32 118 3 32 11 13 16 19 11 16 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 M...

Страница 12: ...idad se pueden producir una descarga eléctrica o un incendio Cuando instale o mueva el equipo de aire acondicionado utilice sólo el refri gerante indicado R410A para cargar los tubos de refrigerante No lo mezcle con otro tipo de refrigerante y vacíe completamente de aire los tubos El aire que quede en los tubos puede provocar picos de presión que causarían su rotura y otros daños Utilice sólo acce...

Страница 13: ...ón se puede producir el deterioro del aceite o una avería en el aparato Utilice aceite de éster de éter o alquilobenceno en pequeñas cantidades para recubrir las secciones abocardadas Si se mezcla aceite mineral con aceite de refrigeración se puede deteriorar el aceite No utilice otro refrigerante que no sea R410A Si utiliza otro refrigerante el cloro provocará el deterioro del aceite Utilice las ...

Страница 14: ...ionales para corriente de aire hacia arriba 3 Obstáculos sólo en la parte delantera Fig 2 14 Si utiliza una guía para salida de aire opcional el espacio libre para los modelos A42 debe ser de 1000 mm 39 3 8 inch o más 4 Obstáculos sólo en la parte delantera y trasera Fig 2 15 Si utiliza una guía para salida de aire opcional el espacio libre para los modelos A42 debe ser de 1000 mm 39 3 8 inch o má...

Страница 15: ...erías no tocan el compresor Podría producir ruidos o vibraciones extrañas 1 Las tuberías se deben conectar empezando por la unidad interior Las tuercas abocardadas se deben apretar con una llave dinamométrica 2 Caliente el tubo de líquido y el tubo de gas y aplique una fina capa de aceite de refrigeración aplicado directamente Tubo de cobre O D Dimensiones de abocinado dimensiones øA mm inch mm in...

Страница 16: ...ir ruido o puede entrar agua o polvo y la unidad se podría averiar 4 6 Añadido de refrigerante No es necesario realizar una carga adicional si la longitud de la tubería no supera los 20 m 70 ft para A12 A36 o los 30 m 100 ft para A42 Si la longitud de la tubería es superior a la especificada cargue la unidad con refrigerante R410A adicional de acuerdo con las longitudes de tubería permitidas mostr...

Страница 17: ...onal A12 A18 A24 A42 Toma de drenaje PAC SG61DS E Batería de drenaje PAC SG63DP E PAC SG64DP E 6 Trabajo eléctrico A B C D E Fig 6 1 Fig 6 2 A24 A42 A12 A18 E B A F C A Tierra del terminal B Bloque de terminales C Grapa D Panel de servicio E Enrute los cables de modo que no entren en contacto con el centro del panel de servicio o la válvula de gas 6 1 Unidad exterior Fig 6 1 Fig 6 2 1 Extraiga el ...

Страница 18: ...LE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A24 A42 6 Trabajo eléctrico PLACA DEL CONDUCTO accesorio PANEL DE SERVICIO CUBIERTA DE CABLES CUBIERTA DEL CONDUCTO BANCO DE TERMINALES BRIDA DE SUJECIÓN DE CABLES ...

Страница 19: ...que no se haya afloja do ni la fuente de alimentación ni el cableado de control que la polaridad no sea errónea y que no se haya desconectado ninguna fase de la alimenta ción s Utilice un megaohmímetro de 500V para comprobar que la resistencia entre los bornes de alimentación y la tierra es como mínimo de 1 0 MΩ Ω Ω Ω Ω s No efectúe esta prueba en los bornes de los cables de control circuito de ba...

Страница 20: ... la unidad exterior esté parada abra completamente la válvula de parada de líquido y repita el paso tres al cabo de 3 minutos Si la operación de recuperación del refrigerante se ha completado con éxito los indicadores LED1 y LED2 están encendidos la unidad continuará para da hasta que se corte la corriente 5 Corte la corriente disyuntor Ajuste la dirección de refrigerante utilizando el interruptor...

Страница 21: ...2 3 15 16 5 29 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 15 3 4 23 5 8 78 23 32 118 3 32 11 13 16 19 11 16 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 inch 7 7 8 11 13 16 39 3 8 Max 19 11 16 á 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 Max 19 11 16 á 39 3 8 59 1 16 11 13 16 19 11 16 39 3 8 59 ...

Страница 22: ......

Страница 23: ......

Страница 24: ... on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U896H02 ...

Отзывы: