background image

10

7. Test run

7.2. Test run

7.2.1. Using SW4 in outdoor unit

1) PUH Type,  PUZ Type

SW4-1

ON

Cooling operation

SW4-2

OFF

SW4-1

ON

Heating operation

SW4-2

ON

2) PUY Type

SW4-1

ON

Cooling operation

SW4-2

ON or OFF

* After performing the test run, set SW4-1 to OFF.

• After power is supplied, a small clicking noise may be heard from the inside of the outdoor

unit. The electronic expansion valve is opening and closing. The unit is not faulty.

• A few seconds after the compressor starts, a clanging noise may be heard from the

inside of the outdoor unit. The noise is coming from the check valve due to the small
difference in pressure in the pipes. The unit is not faulty.

The test run operation mode cannot be changed by DIP switch SW4-2 during
the test run. (To change the test run operation mode during the test run, stop
the test run by DIP switch SW4-1. After changing the test run operation mode,
resume the test run by switch SW4-1.)

7.2.2. Using remote controller

Refer to the indoor unit installation manual.

9. System control (Fig. 9-1)

* Set the refrigerant address using the DIP switch of the outdoor unit.

1

Wiring from the Remote Control

This wire is connected to TB5 (terminal board for remote controller) of the indoor unit
(non-polar).

2

When a Different Refrigerant System Grouping is Used.

Up to 16 refrigerant systems can be controlled as one group using the slim MA re-
mote controller.

Note:
In single refrigerant system (twin/triple), there is no need of wiring 

2

2

2

2

2

.

Operation according to switch setting

ON

OFF

Start

Normal

Clear

Normal

Settings for outdoor unit ad-
dresses 0 to 15

SW1
Function table

<SW1>

Function

1 Compulsory de-

frosting

2 Error history clear
3
4
5
6

ON

1 2 3 4 5 6

OFF

A

Outdoor unit

B

Indoor unit

C

Master remote controller

D

Subordinate remote controller

E

Standard 1:1 (Refrigerant address = 00)

F

Simultaneous twin (Refrigerant address = 01)

G

Simultaneous twin (Refrigerant address = 02)

TB4

TB5

TB1

TB4

TB5

TB4

TB1

TB4

TB1

TB4

TB5

1

1

2

2

A

A

B

B

B

B

B

C

D

A

F

G

E

ON

OFF

3

4

5

6

E

 SW 1 - 3 ~ 6

ON

OFF

3

4

5

6

F

 SW 1 - 3 ~ 6

ON

OFF

3

4

5

6

G

 SW 1 - 3 ~ 6

SW1
function
settings

Fig. 9-1

Refrigerant sys-
tem address set-
ting

8.1. Low noise mode (on-site modification) (Fig. 8-1)

By performing the following modification, operation noise of the outdoor unit can be
reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.
• The capacity may be insufficient according to the outdoor temperature and condi-

tions, etc.

1

Complete the circuit as shown when using the external input adapter (PAC-
SC36NA). (Option)

2

SW1 ON: Low noise mode
SW1 OFF: Normal operation

8.2. Refrigerant collecting (pump down)

Perform the following procedures to collect the refrigerant when moving the indoor
unit or the outdoor unit.

1

Before collecting the refrigerant, first make sure that the all of the SW5 DIP switches
for function changes on the control board of the outdoor unit are set to OFF. If all of the
SW5 switches are not set to OFF, record the settings and then set all of the switches
to OFF. Start collecting the refrigerant. After moving the unit to a new location and
completing the test run, set the SW5 switches to the previously recorded settings.

2

Supply power (circuit breaker).

* When power is supplied, make sure that “CENTRALLY CONTROLLED” is not

displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis-
played, the refrigerant collecting (pump down) cannot be completed normally.

3

After the gas stop valve is closed, set the SWP switch on the control board of the
outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and
outdoor units) start operating and refrigerant collecting operation begins. LED1
and LED2 on the control board of the outdoor unit are lit.

* Only set the SWP switch (push-button type) to ON if the unit is stopped. How-

ever, even if the unit is stopped and the SWP switch is set to ON less than
three minutes after the compressor stops, the refrigerant collecting operation
cannot be performed. Wait until compressor has been stopped for three min-
utes and then set the SWP switch to ON again.

4

Because the unit automatically stops in about two to three minutes after the refrig-
erant collecting operation (LED1 and LED2 are lit), be sure to quickly close the
gas stop valve. When LED1 and LED2 are lit and the outdoor unit is stopped, open
the liquid stop valve completely, and then repeat step 

3

 after three minutes have

passed.

* If the refrigerant collecting operation has been completed normally (LED1 and

LED2 are lit), the unit will remain stopped until the power supply is turned off.

5

Turn off the power supply (circuit breaker).

A

Circuit diagram example (low noise mode)

B

On-site arrangement

C

External input adapter (PAC-SC36NA)

SW1

CNDM

Red

Brown

Orange

B

C

D

E

3

1

D

Outdoor unit control board

E

Max. 10 m, 33 ft

Fig. 8-1

A

8. Special Functions

 BG79U896H02_en

06.5.31, 14:31

10

Содержание PUY-A NHA

Страница 1: ...indoor unit installation manual thoroughly before installing the air conditioner unit MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado Air Conditioners PUZ A NHA PUZ A NHA BS PUY A NHA PUY A NHA BS FOR INSTALLER PARA EL INSTALADOR ...

Страница 2: ...ure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric shock or fire m...

Страница 3: ...kylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessa...

Страница 4: ...an optional air outlet guide the clearance for A42 models is 1000 mm 39 3 8 inch or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for A42 models is 1000 mm 39 3 8 inch or more 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for upward airflow the clearance is 500 1000 mm 19 11 16 39 3 8 inch or m...

Страница 5: ...occur When bending the pipes be careful not to break them Bend radii of 100 mm 3 15 16 inch to 150 mm 5 27 32 inch are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit Flare nuts must be tightened with a torque wrench 2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigerat...

Страница 6: ...ps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result I Double spanner section Do not apply a spanner other than to this sec tion Doing so would cause coolant leaks J Seal section Seal the end of the heat insulation material at the pipe connection section with whatever seal material you have on hand so that water does not infiltrate the heat insulati...

Страница 7: ...n drain piping is necessary use the drain socket or the drain pan option A12 A18 A24 A42 Drain socket PAC SG61DS E Drain pan PAC SG63DP E PAC SG64DP E A B C D E Fig 6 1 Fig 6 2 A24 A42 A12 A18 A Earth terminal B Terminal block C Clamp D Service panel E Wire the cables so that they do not contact the center of the service panel or the gas valve 6 1 Outdoor unit Fig 6 1 Fig 6 2 1 Remove the service ...

Страница 8: ...8 A12 A18 CORD COVER CONDUIT COVER CABLE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A24 42 ...

Страница 9: ... for refrigerant leakage looseness in the power supply or control wiring wrong polarity and no disconnection of one phase in the supply s Use a 500 volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1 0MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit terminals Warning Do not use the air conditioner if the insulat...

Страница 10: ...he contact input of an ON OFF switch is added to the CNDM connector option on the control board of the outdoor unit The capacity may be insufficient according to the outdoor temperature and condi tions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA Option 2 SW1 ON Low noise mode SW1 OFF Normal operation 8 2 Refrigerant collecting pump down Perform the followin...

Страница 11: ... 13 16 39 3 8 59 1 16 39 3 8 59 1 16 11 13 16 19 11 16 19 11 16 39 3 8 15 3 4 23 5 8 39 3 8 78 23 32 3 15 16 5 29 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 15 3 4 23 5 8 78 23 32 118 3 32 11 13 16 19 11 16 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 M...

Страница 12: ...idad se pueden producir una descarga eléctrica o un incendio Cuando instale o mueva el equipo de aire acondicionado utilice sólo el refri gerante indicado R410A para cargar los tubos de refrigerante No lo mezcle con otro tipo de refrigerante y vacíe completamente de aire los tubos El aire que quede en los tubos puede provocar picos de presión que causarían su rotura y otros daños Utilice sólo acce...

Страница 13: ...ón se puede producir el deterioro del aceite o una avería en el aparato Utilice aceite de éster de éter o alquilobenceno en pequeñas cantidades para recubrir las secciones abocardadas Si se mezcla aceite mineral con aceite de refrigeración se puede deteriorar el aceite No utilice otro refrigerante que no sea R410A Si utiliza otro refrigerante el cloro provocará el deterioro del aceite Utilice las ...

Страница 14: ...ionales para corriente de aire hacia arriba 3 Obstáculos sólo en la parte delantera Fig 2 14 Si utiliza una guía para salida de aire opcional el espacio libre para los modelos A42 debe ser de 1000 mm 39 3 8 inch o más 4 Obstáculos sólo en la parte delantera y trasera Fig 2 15 Si utiliza una guía para salida de aire opcional el espacio libre para los modelos A42 debe ser de 1000 mm 39 3 8 inch o má...

Страница 15: ...erías no tocan el compresor Podría producir ruidos o vibraciones extrañas 1 Las tuberías se deben conectar empezando por la unidad interior Las tuercas abocardadas se deben apretar con una llave dinamométrica 2 Caliente el tubo de líquido y el tubo de gas y aplique una fina capa de aceite de refrigeración aplicado directamente Tubo de cobre O D Dimensiones de abocinado dimensiones øA mm inch mm in...

Страница 16: ...ir ruido o puede entrar agua o polvo y la unidad se podría averiar 4 6 Añadido de refrigerante No es necesario realizar una carga adicional si la longitud de la tubería no supera los 20 m 70 ft para A12 A36 o los 30 m 100 ft para A42 Si la longitud de la tubería es superior a la especificada cargue la unidad con refrigerante R410A adicional de acuerdo con las longitudes de tubería permitidas mostr...

Страница 17: ...onal A12 A18 A24 A42 Toma de drenaje PAC SG61DS E Batería de drenaje PAC SG63DP E PAC SG64DP E 6 Trabajo eléctrico A B C D E Fig 6 1 Fig 6 2 A24 A42 A12 A18 E B A F C A Tierra del terminal B Bloque de terminales C Grapa D Panel de servicio E Enrute los cables de modo que no entren en contacto con el centro del panel de servicio o la válvula de gas 6 1 Unidad exterior Fig 6 1 Fig 6 2 1 Extraiga el ...

Страница 18: ...LE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A24 A42 6 Trabajo eléctrico PLACA DEL CONDUCTO accesorio PANEL DE SERVICIO CUBIERTA DE CABLES CUBIERTA DEL CONDUCTO BANCO DE TERMINALES BRIDA DE SUJECIÓN DE CABLES ...

Страница 19: ...que no se haya afloja do ni la fuente de alimentación ni el cableado de control que la polaridad no sea errónea y que no se haya desconectado ninguna fase de la alimenta ción s Utilice un megaohmímetro de 500V para comprobar que la resistencia entre los bornes de alimentación y la tierra es como mínimo de 1 0 MΩ Ω Ω Ω Ω s No efectúe esta prueba en los bornes de los cables de control circuito de ba...

Страница 20: ... la unidad exterior esté parada abra completamente la válvula de parada de líquido y repita el paso tres al cabo de 3 minutos Si la operación de recuperación del refrigerante se ha completado con éxito los indicadores LED1 y LED2 están encendidos la unidad continuará para da hasta que se corte la corriente 5 Corte la corriente disyuntor Ajuste la dirección de refrigerante utilizando el interruptor...

Страница 21: ...2 3 15 16 5 29 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 15 3 4 23 5 8 78 23 32 118 3 32 11 13 16 19 11 16 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 inch 7 7 8 11 13 16 39 3 8 Max 19 11 16 á 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 Max 19 11 16 á 39 3 8 59 1 16 11 13 16 19 11 16 39 3 8 59 ...

Страница 22: ......

Страница 23: ......

Страница 24: ... on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U896H02 ...

Отзывы: