B
A
a
b
c
d
e
400
350
300
250
200
30
40
50
60
70
80
90
100 110
70
60
40
30
50
10
20
0
0
5
10
15
Note: A system with more than 16 branching requires 2 to 3 BC controllers (main/sub) and 3 pipes between BC controllers.
Note 1: Refer to the graph below for restrictions on refrigerant piping when the total piping length exceeds 300 m.
Note 2: Refer to the graph below for restrictions on refrigerant piping length when the piping length between the BC
controller and the farthest indoor unit exceeds 40 m. (except P250-type indoor units)
Note 3: Use the figures in the parentheses if the capacity of the connected indoor units is P200 type or above.
Note 4: When indoor units of type P200 or above are connected, neither branch joints nor branch headers can be used.
Note 5: When 2 sub BC controllers are connected, include them in the figures in the table above.
Note 6: When 2 sub BC controllers are connected, connect them in parallel.
C
Note 6
f
g
h3
h4
[Systems that requires more than 16 pipe-end connections or with multiple BC controllers
(with a use of both main and sub controllers)]
BC controller (main)
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
BC controller
(sub)
110 m or less
40 m or less
<With more than 16 branching>
(P141~P250 types: 2-line merge)
• Restrictions on piping length
Total piping length (m)
Piping length between main BC controller
and farthest indoor unit (m)
• Height difference and branch piping length between
BC controller and indoor unit. (A)
Distance between outdoor unit and
BC controller (m)
Height difference between main BC controller and
farthest indoor unit (m)
Maximum of 3 units per branch joint
Total capacity of P140 or less
(All units connected to the same
branch joint must be in the same mode.)
Junction
pipe
(option)
Branch pipe (for Y-series)
CMY-Y102S-G
H = 50 m or less (outdoor unit above)
H
’ = 40 m or less (outdoor unit below)
h1 = 15 m or less
h2 = 15 m or less
Total piping length
A + B + C + a + b + c + d + e + f + g
Piping length
Farthest piping length
Between outdoor unit - BC controller
Height difference
Between BC controller and indoor unit
Between indoor unit and BC controller
Between indoor units
Between indoor unit
and outdoor unit
Outdoor unit above
Outdoor unit below
300 m less
A + C + g or A + e
150 m or less
(175 m equivalent length or less)
A
110 m or less
e or C + g
40 m or less (Note 2)
Between main BC controller and sub BC controller
h3
15 m or less
H
50 m or less
H’
40 m or less
h1
15 m or less (10 m or less) (Note 3)
h2
15 m or less (10 m or less) (Note 3)
Between indoor (main BC controller) and
indoor (sub BC controller) units
h4
15 m or less (10 m or less)
(Notes 3 and 5)
Indoor unit
Indoor unit
Item
Piping sections
Allowable value
Outdoor unit
- 39 -