OK
NO
➀
Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
➁
Wiring for control (hereinafter referred to as transmission line) shall be (5cm or more) apart from power source wiring so
that it is not influenced by electric noise from power source wiring. (Do not insert transmission line and power source wire
in the same conduit.)
➂
Be sure to provide designated grounding work to outdoor unit.
➃
Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removed
at the time of service work.
➄
Never connect 380~415V(220~240V )power source to terminal block of transmission line.If connected,electrical parts
will be burnt out
➅
Use 2-core shield cable for transmission line. If transmission lines of different systems are wired with the same multiple-
core cable, the resultant poor transmitting and receiving will cause erroneous operations.
Outdoor
unit
Indoor unit
Remote
BC controller
controller
2-core cable
2-core cable
Outdoor
unit
Remote
controller
Indoor unit
Multiple-
core cable
BC controller
Type of cable
Cable diameter
Remarks
Sheathed 2-core cable (unshielded)
CVV
0.3
~ 1.25mm
2
(0.75
~ 1.25mm
2
)
✻
1
More than 1.25mm
2
Shielding wire (2-core)
CVVS or CPEVS
When 10m is exceeded, use cables with
the same specification as transmission cables.
0.3
~ 1.25mm
2
(0.75
~ 1.25mm
2
)
✻
1
Max length : 200m
Transmission cables
M-NET Remote controller cables
MA Remote controller cables
CVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
CVV : PV insulated PVC sheathed control cable
—
✻
1 Connected with simple remote controller.
- 18 -
™
™
Restrictions
[1] Electrical Work & M-NET control
1. Attention
2. Types of control cable
Содержание PURY-P200
Страница 49: ... 46 Heat exchanger Fan guard Heat exchanger Fan guard P400 type Front view of the unit Rear view of the unit ...
Страница 57: ... 54 CNVDC DC bus voltage input 1 3 LED1 LED2 SW2 CNTR IPM back CNN Fan motor output Fuse CNRS2 3 FAN board ...
Страница 64: ... 61 Relay board RELAY 4 board Relay board RELAY 10 board ...