Items
PURY-P500
CMB-P108GA
Ambient temp.
Indoor
DB/WB
Outdoor
Quantity
Set
Indoor unit
Quantity in operation
Condition
Model
–
Main pipe
Piping
Branch pipe
m
Total piping length
Indoor unit fan notch
–
Refrigerant volume
kg
Outdoor
Total current
A
unit
Volts
V
LEV
Indoor unit
Pulse
opening
BC controller (1/2/3)
Pressure
High pressure/Low pressure
BC controller liquid side/mid point
MPa
Discharge (TH11/TH12)
Heat exchanger outlet (TH5)
Accumulator
Inlet
Outdoor
Outlet
Sectional
unit
Suction (Compressor)
˚C
temp.
Shell bottom (Compressor)
Indoor
LEV inlet
unit
Heat exchanger inlet
27.0/19.0
35.0/24.0
4
4
250
125
100
32
5
10
45
Hi
Compressor frequency (No.1 / No.2)
Hz
380/415
388
387
325
2000
2000
200
2000
2000
210
261
84/87
42
15
15
21/17
37/42
24
13
PURY-P550
CMB-P108GA
27.0/19.0
35.0/24.0
4
4
250
125
125
63
5
10
45
Hi
28.2
29.2
26.3/24.0
28.8/26.4
380/415
50Hz:85/50
60Hz:73/60
50Hz:96/50
60Hz:88/60
388
373
387
362
82/85
2.65/2.65
2.69/2.69
2.80/0.86
2.85/0.85
40
15
15
19/17
42/42
23
13
Outdoor unit
BC contoroller