- 35 -
IC
TB5
TB15
1 2
01
IC
TB5
TB15
1 2
02
IC
TB5
TB15
1 2
04
104
IC
TB5
TB15
1 2
06
A1 B2
MA
A1 B2
RC
A1 B2
MA
IC
TB5
1 2
TB15
IC
TB5
TB15
1 2
05
03
L2
L1
L22
L21
L3
L4
L23
L24
105
A1 B2
RC
L31
L32
NO
a. Indoor/outdoor transmission line
The same as 1. (3)
b. Centralized control transmission line
The same as 1. (4)
c-1. MA remote controller wiring
The same as 1. (1)
c-2. M-net remote controller wiring
The same as 2. (1)
Control wiring example
Group
Prohibited items
Allowable length
1. Make sure to connect the system controller.
2. M-NET and MA remote controllers can not be connected to-
gether to the indoor unit within a same group.
3. M-NET remote controller of 3 units or more can not be con-
nected to the indoor unit within a same group.
6.
7.
8. When the total number of indoor units exceeds 20 sets, trans-
mission line booster is required.
9. When the total number of indoor units exceed 16 sets and
they include Type 200 or above, the transmission line booster
is required.
– Example to use shielded wire –
Group
Group
Note 2
System controller
Notes:
1. Leave SW2-1 as “OFF” when connecting LM adapter only.
2. LM adapter requires the power source of 1-phase AC 230V.
Note1
Note1
Group
Replacement of the power supply selecting connector (CN41)
on the outdoor unit should be done only on one outdoor unit.
Grounding work is required for S-terminal of the centralized
control transmission block (TB7) on one outdoor unit only.
CN41
→
CN40 Replace
SW2-1 OFF
→
ON
Leave CN41 as it is.
SW2-1 OFF
→
ON
4. MA remote controller of 3 units or more can not be connected
to the indoor unit within a same group.
5. Do not connect together the terminal blocks (TB5) of the in-
door unit connected to different outdoor units.
OC
TB3
TB7
51
✻
2
BC
TB02
55
OC
TB3
TB7
53
✻
2 BC
TB02
54
TB02
52
✻
2
BS
NO
Connect
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
3. System where MA remote controller and M-NET remote controller coexist