- 124 -
Over-current protection ( [ P450-P650 model ] No.2 Comp)
Harmonic control device abnormality
1202 (1102)
Preliminary discharge temperature abnormality or preliminary discharge thermal sensor abnormality (TH11)
1205 (5105)
Preliminary pipe temperature sensor abnormality (TH5)
Preliminary THHS sensor/circuit abnormality
1216 (5107)
Preliminary pipe thermal sensor abnormality (TH7)
1221 (5106)
Preliminary ambient temperature thermal sensor abnormality (TH6)
1402 (1302)
Preliminary high pressure abnormality or preliminary pressure sensor abnormality
1600 (1500)
4171 (4121)
Preliminary overcharged refrigerant abnormality
1605
4158 (4108)
Preliminary suction pressure abnormalit
Preliminary serial transmission abnormality
4300 (5301)
4305 (5305)
[115]
Preliminary ACCT sensor abnormality
[116]
Preliminary DCCT sensor abnormality
[117]
(Note1)
(Note1)
Preliminary ACCT sensor/circuit abnormality
[118]
Preliminary DCCT sensor/circuit abnormality
[119]
Preliminary IPM-open/ACCT connection abnormality
[120]
[05]
[00]
(Note1)
1214 (5110)
[05]
[01]
(Note1)
4300 (0403)
Preliminary ACCT miss-wiring abnormality
4320 (4220)
4325 (4225)
[108]
Preliminary bus voltage drop abnormality (S/W detect)
[109]
Preliminary bus voltage rise abnormality (S/W detect)
[110]
Preliminary bus voltage abnormality (H/W detect)
[111]
Preliminary logic circuit for H/W error detect abnormality
4330 (4230)
4335 (4235)
(Note1)
Preliminary heat sink overheating abnormality
4340 (4240)
4345 (4245)
(Note1)
Preliminary overload abnormality
4350 (4250)
4355 (4255)
[101]
Preliminary IPM abnormality
[102]
Preliminary ACCT overcurrent abnormality (H/W peak detect)
[103]
Preliminary DCCT overcurrent abnormality (H/W peak detect)
[104]
Preliminary IPM short/grounding abnormality
[105]
Preliminary load short abnormality
[106]
Preliminary ACCT overcurrent abnormality (S/W detect peak current)
[107]
Preliminary ACCT overcurrent abnormality (S/W detect effective current)
Preliminary error code
Preliminary error content
❉
Please refer to ( ) check code. [ ] : Error code No.
(Note1) Compressor inverter and fan inverter are installed in these R410A series. When checking the check code or the 2-digit detail
code, refer to the last digit to confirm whether the error code is for the compressor or for the fan.
Example) Code 4225
→
Bus voltage drop
Error for fan inverter system
Code 4250
→
IPM / bus voltage fault
Error for compressor inverter system
The last digit
Inverter address (system)
Potential model
0 or 1
1
Compressor inverter system
5
5
Fan inverter system
2. Intermittent fault check code (only for outdoor unit)