–97–
Checking code
Meaning, detecting method
Cause
Checking method & Countermeasure
5201
5201
5203
5301
Pressure
sensor
abnormality
(outdoor unit)
IDC sensor/
circuit trouble
Pressure sensor abnor
mality (BC controller)
High
pressure
side
Intermedi-
ate
1
When pressue sensor detects
0.098MPa (14.22psi) or less dur-
ing operation, outdoor unit once
stops with 3 minutes restarting
mode, and restarts if the detected
pressure of pressure sensor ex-
ceeds 0.098MPa (14.22psi)
imediately before restarting.
2
If the detected pressure of sen-
sor is less than 0.098MPa
(14.22psi) immediately before
restarting, error stop is com-
menced displaying 5201.
3
Under 3 minutes restarting
mode, LED displays intermittent
fault check.
4
During 3 minutes after com-
pressor start, defrosting and 3
minutes after defrosting opera-
tions, trouble detection is ig-
nored.
When high or intermidiate pressure
sensor detects 0.098MPa (14.2psi)
or less immediately before starting,
error stop is commenced display-
ing “5201”, or “5203”.
•
If IDC 20 A is detected just
before the inverter starts, or
•
If IDC 10 A is detected dur-
ing inverter operation after 5
seconds has passed since the
inverter started when the INV
board’s SW1-1 is OFF.
1) Pressutre sensor trouble.
2) Inner pressure drop due to a leak-
age.
3) Broken cover.
4) Coming off of pin at connector por-
tion, poor contact.
5) Broken wire.
6) Faulty thermistor input circuit of
MAIN board.
1) Pressure sensor trouble.
2) Inner pressure drop due to gas leak.
3) Broken cover.
4) Coming off of pin at connector por-
tion, poor contact.
5) Broken wire.
6) Faulty pressure sensor input circuit
of control board.
1) Contact is faulty.
2) The current sensor (DCCT) is con-
nected with reverse polarity.
3) An error was made in the SW1-1
setting.
4) The INV board is defective. The
current sensor (DCCT) is defective.
See
Troubleshooting of pressure
sensor
.
See
troubleshooting of pressure
sensor
.
Check the contacts of CNCT on the
INV board.
Check the DCCT polarity.
•
With SW1-1 OFF, is the inverter’s
output wiring open?
•
With SW1-1 OFF, is a compressor
which is not specified for this model
connected to the inverter’s output?
If none of the items in 1) to 3) is appli-
cable, and if the trouble reappears
even after the power is switched on
again, replace the INV board and the
DCCT (when replacing the circuit
board, be sure to connect all the con-
nectors, ground wires, etc. securely) by
the following procedure.
1
Replace the INV board only. If it
recovers, the INV board is defec-
tive.
2
If it does not recover, reinstall the
INV board and replace the DCCT.
If it recovers, the DCCT is defec-
tive.
If it does not recover after
1
and
2
above, both the INV board and the
DCCT are defective.
Содержание PURY-100TMU
Страница 8: ... 7 Controller Box ...
Страница 11: ... 10 G A board CNIPM1 CN15V1 CNDR1 CNE CNDC1 Power board ...
Страница 12: ... 11 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5 ...
Страница 13: ... 12 RELAY 10 board RELAY 4 board ...
Страница 14: ... 13 2 Refrigerant Circuit Diagram and Thermal Sensor ...
Страница 15: ... 14 3 Electrical Wiring Diagram 1 MC P N ...
Страница 17: ... 16 3 CMB 108 1010NU F ...
Страница 18: ... 17 4 CMB 1013 1016NU F ...
Страница 71: ... 70 Motor Compressor G A board Red U V W N P White Blue Blue Capacitor C1 Red IPM ...