–72–
Note 1 :
•
Symptoms of incorrect i.e, reverse connection of PS
1
and PS
3
to BC controller board
Note 2 :
•
Check using LED monitor display switch (outdoor MAIN board SW1)
Note 3 :
•
Check CNP1 (liquid measurement) and CMP3 (intermediate) connectors on BC controller board for disconnection or
looseness.
Note 4 :
•
With the sensor of the applicable connector removed from the board, use the LED monitor display switch (Note 1) to
check the pressure value.
Pressure Sensor Replacement Precaution
Symptom
Cooling-only
Cooling-principal
Heating-only
Heating-principal
Normal
Insufficient
cooling.
SC11 large
SC16 small
PHM < 0
SC11 large
SC16 small
PHM < 0
Warm indoor SC
small. When SV
opens some
noise produced.
SC11 small
SC16 small
PHM < 0
Insufficient heating
Warm indoor SC small
When SV opens some
noise produced
Measured Data
High pressure of
outdoor
Low pressure of
outdoor
BC controller pressure
(liquid measurement)
(intermediate)
Signal
HPS
LPS
PS1
PS3
SW1 Setting
Remarks
See converter.
See converter.
Convert saturation
temperature to
desired pressure
using converter.
1
ON
2 3 4 5 6 7 8 9 10
1
ON
2 3 4 5 6 7 8 9 10
1
ON
2 3 4 5 6 7 8 9 10
1
ON
2 3 4 5 6 7 8 9 10
(Pressure sensor output voltage)
Содержание PURY-100TMU
Страница 8: ... 7 Controller Box ...
Страница 11: ... 10 G A board CNIPM1 CN15V1 CNDR1 CNE CNDC1 Power board ...
Страница 12: ... 11 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5 ...
Страница 13: ... 12 RELAY 10 board RELAY 4 board ...
Страница 14: ... 13 2 Refrigerant Circuit Diagram and Thermal Sensor ...
Страница 15: ... 14 3 Electrical Wiring Diagram 1 MC P N ...
Страница 17: ... 16 3 CMB 108 1010NU F ...
Страница 18: ... 17 4 CMB 1013 1016NU F ...
Страница 71: ... 70 Motor Compressor G A board Red U V W N P White Blue Blue Capacitor C1 Red IPM ...