–31–
2)
Method of retrieval/confirmation
• Retrieval/confirmation of group registration information on indoor unit ...............
2
The address of the indoor unit being registered on the remote controller is displayed.
[Operation procedure]
1
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
LOUVER
button
(
A
+
B
) at the same time for 2 seconds to change to the registration mode.
2
In order to confirm the indoor unit address already registered, press
TIMER
button (
E
). (See figure below.) When the
group of plural sets is registered, the addresses will be displayed in order at each pressing of
TIMER
button (
E
).
3
After completing the registration, continuously press the
FILTER
+
LOUVER
button (
A
+
B
) at the same time for 2
seconds to change to the original ordinary mode (with the remote controller under stopping).
• Retrieval/confirmation of registration information ................................................
3
The registered information on a certain unit (indoor unit, outdoor unit, remote controller or the like) is displayed.
[Operation procedure]
1
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
LOUVER
button
(
A
+
B
) at the same time for 2 seconds to change to the registration mode.
2
Operate
MODE
button (
G
) for the interlocked setting mode. (See figure below.)
3
Assign the unit address of which registration information is desired to confirm with the
(TIMER SET) switch
(
H
). Then press the
TIMER
button (
E
) to display it on the remote controller. (See figure below.)
Each pressing of
TIMER
button (
E
) changes the display of registered content. (See figure below.)
4
After completing the retrieval/confirmation, continuously press the
FILTER
+
LOUVER
button (
A
+
B
) at the same
time for 2 seconds to change to the original ordinary mode (with the remote controller under stopping).
• Registered
• No registration.
ERROR CODE
OA UNIT ADDRESS NO
˚C
ERROR CODE
OA UNIT ADDRESS NO
˚C
▲
▼
1
Press the switch for confirmation (
E
)
Note: Only one address will be displayed
when the registration is one even the
switch is how often pressed
Indicates the type of unit
(Indoor unit in this case)
1
1
SET TEMP.
ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE
TIMER
FAN SPEED
LOUVER
VENTILATION
AIR DIRECTION
TIMER SET
Содержание PURY-100TMU
Страница 8: ... 7 Controller Box ...
Страница 11: ... 10 G A board CNIPM1 CN15V1 CNDR1 CNE CNDC1 Power board ...
Страница 12: ... 11 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5 ...
Страница 13: ... 12 RELAY 10 board RELAY 4 board ...
Страница 14: ... 13 2 Refrigerant Circuit Diagram and Thermal Sensor ...
Страница 15: ... 14 3 Electrical Wiring Diagram 1 MC P N ...
Страница 17: ... 16 3 CMB 108 1010NU F ...
Страница 18: ... 17 4 CMB 1013 1016NU F ...
Страница 71: ... 70 Motor Compressor G A board Red U V W N P White Blue Blue Capacitor C1 Red IPM ...