–87–
Checking code
Meaning, detecting method
Cause
Checking method & Countermeasure
Discharge
temperature
abnormality
(Outdoor unit)
1102
1. When 140˚C (284˚F) or more
discharge temperature is de-
tected during operations (the
first time), outdoor unit stops
once, mode is changed to re-
start mode after 3 minutes, then
the outdoor unit restarts.
2. When 140˚C (284˚F) or more
temp. is detected again (the
second time) within 30 minutes
after stop of outdoor unit, emer-
gency stop is observed with
code No. “1102” displayed.
3. When 140˚C (284˚F) or more
temp. is detected 30 or more
minutes after stop of outdoor
unit, the stop is regarded as the
first time and the process
shown in 1 is observed.
4. 30 minutes after stop of outdoor
unit is intermittent fault check
period with LED displayed
(1202).
See
Refrigerant amount check.
Check operating conditions and opera-
tion status of indoor/outdoor units.
Check operation status by actually
performing cooling or heating opera-
tions.
Cooling
: Indoor LEV
(Cooling-only) LEV1, 3 (BC)
SVA (BC)
Heating
: Indoor LEV
(Heating-only) LEV3 (BC)
SVB (BC)
SV3 ~ 6
See
Trouble check of LEV and sole-
noid valve.
Check address setting of indoor unit
connection.
Confirm that ball valve is fully opened.
Check outdoor fan.
See
Trouble check of outdoor fan.
Check operation status of cooling-only
or heating-only.
See
Trouble check of solenoid
valve.
Check resistance of thermistor.
Check inlet temperature of sensor
with LED monitor.
1) Gas leak, gas shortage.
2) Overload operations.
3) Poor operations of indoor LEV.
4) Poor operations of BC controller
LEV:
Cooling-only
: LEV3
Cooling-main : LEV1, 3
Heating-only, Heating-main:
LEV3
Defronst
: LEV3
5) Poor operations of BC controller
SVM
:
Cooling-only, defrost
6) Poor operations of BC controller
SVA
:
Cooling-only, Cooling-main
7) Poor operations of BC controller
SVB
:
Heating-only, Heating-main
8) Poor operations of solenoid
valves.
SV (3 ~ 6)
Heating-only, Heating-main
9) Setting error of connection
address.
10)Poor operations of ball valve.
11) Outdoor unit fan block, motor
trouble, poor operations of fan
controller
→
Heating (Heating-only,
Heating-main).
3) ~ 11) : Rise in discharge
temp. by low pressure drawing.
12)Gas leak between low and high
pressures.
4-way valve trouble, compres-
sor trouble, solenoid valve
SV1 trouble.
13)Poor operations of solenoid valve
SV2.
Bypass valve SV2 can not
control rise in discharge temp.
14)Thermistor trouble.
15)Thermistor input circuit trouble on
control circuit board.
Содержание PURY-100TMU
Страница 8: ... 7 Controller Box ...
Страница 11: ... 10 G A board CNIPM1 CN15V1 CNDR1 CNE CNDC1 Power board ...
Страница 12: ... 11 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5 ...
Страница 13: ... 12 RELAY 10 board RELAY 4 board ...
Страница 14: ... 13 2 Refrigerant Circuit Diagram and Thermal Sensor ...
Страница 15: ... 14 3 Electrical Wiring Diagram 1 MC P N ...
Страница 17: ... 16 3 CMB 108 1010NU F ...
Страница 18: ... 17 4 CMB 1013 1016NU F ...
Страница 71: ... 70 Motor Compressor G A board Red U V W N P White Blue Blue Capacitor C1 Red IPM ...