9
OCH634C
3
SPECIFICATIONS
Service Ref.
PUMY-P200YKM1, PUMY-P200YKM1-BS
Power source
380/400/415 V, 50 Hz
Cooling capacity
(Nominal)
kW
*1
22.4
kcal/h
*1
19,300
BTU/h
*1
76,400
Power input
kW
6.05
Current input
A
9.88, 9.39, 9.05
COP
kW/kW
3.70
Temp. range of
cooling
Indoor temp.
W.B.
15 to 24°C
Outdoor temp.
D.B.
−5 to 52°C
*3, *4
Heating capacity
(Nominal)
kW
*2
25.0
kcal/h
*2
21,500
BTU/h
*2
85,300
Power input
kW
5.84
Current input
A
9.54, 9.06, 8.74
COP
kW/kW
4.28
Temp. range of
heating
Indoor temp.
D.B.
15 to 27°C
Outdoor temp.
W.B.
−20 to 15°C
*3, *4
Indoor unit
connectable
Total capacity
50 to 130% of outdoor unit capacity
Model/Quantity
CITY MULTI
15–200/12
Branch box
kW type: 15–100/8
Mixed system
Branch
box 1 unit
CITY MULTI
15–200/5
Branch box
kW type: 15–100/5
Branch
box 2 units
CITY MULTI
15–200/3
Branch box
kW type: 15–100/8
Sound pressure level (measured in anechoic room) dB <A>
56/61
Power pressure level (measured in anechoic room) dB <A>
75/80
Refrigerant
piping diameter
Liquid pipe
mm (inch)
9.52 (3/8)
*5
Gas pipe
mm (inch)
19.05 (3/4)
FAN
Type × Quantity
Propeller Fan × 2
Airflow rate
m³/min
137 (303)
L/s
2,316
cfm
4,908
Control, Driving mechanism
DC control
Motor output
kW
0.20 + 0.20
External static pressure
0
Compressor
Type × Quantity
Scroll hermetic compressor × 1
Manufacturer
Siam Compressor Industry Co., Ltd.
Starting method
Inverter
Capacity control
%
Cooling 25 to100
Heating 17 to 100
Motor output
kW
5.3
Case heater
kW
0
Lubricant
FV50S(2.3litter)
External finish
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
External dimension HxWxD
mm
1338 × 1050 x 330(+25)
inch
52-11/16 × 41-11/32 × 13 (+1)
Protection devices High pressure protection
High pressure Switch
Inverter circuit (COMP./FAN)
Overcurrent detection, Overheat detection(Heat sink thermistor)
Compressor
Compressor thermistor, Over current detection
Fan motor
Overheating, Voltage protection
Refrigerant
Type × original charge
R410A 7.3 kg
Control
Electronic Expansion Valve
Net weight
kg (lb)
137 (303)
Heat exchanger
Cross Fin and Copper tube
HIC circuit (HIC: Heat Inter-Changer)
HIC circuit
Defrosting method
Reversed refrigerant circuit
Drawing
External
BK01V793
Wiring
BH79J683
Standard
attachment
Document
Installation Manual
Accessory
Grounded lead wire × 2
Optional parts
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
*1 Nominal cooling conditions
*2 Nominal heating conditions
Indoor :
27
°C
D.B./19
°C
W.B. [81
°
F D.B/66
°
F W.B.]
20
°C
D.B. [68
°
F D.B.]
Outdoor :
35
°C
D.B. [95
°
F D.B.]
7
°C
DB/6
°C
W.B. [45
°
F D.B./43
°
F W.B.]
Pipe length :
7.5 m [24-9/16 ft]
7.5 m [24-9/16 ft]
Level difference :
0 m [0 ft]
0 m [0 ft]
Note: 1. Nominal conditions *
1
, *
2
are subject to ISO 15042.
2. Due to continuing improvement, above specifications may be subject to change without notice.
*3 10 to 52
:
, when connecting following models: PKFY-P15/20/25VBM, PFFY-P20/25/32VLE(R)M, PFFY-P20/25/32VKM,
PEFY-P40/63VMA3-E; and M series, S series, and P series type indoor unit.
*4 −15 to 52
:
, when using an optional air protect guide [PAC-SH95AG-E]. However, this condition does not apply to the indoor unit
listed in *3.
*5 Liquid pipe diameter: 12.7 mm, in case of further piping length is longer than 60 m.
Unit converter
kcal/h = kW × 860
BTU/h = kW × 3,412
cfm = m3/min × 35.31
lb = kg/0.4536
Above specification data is
subject to rounding variation.