Check code
5201
(F5)
High pressure sensor (63HS) trouble
Abnormal points and detection methods
Causes and checkpoints
When the detected pressure in the high pressure sensor is 1 kgf/
F
[14.2
PSIG] or less during operation, the compressor stops operation and
enters into an anti-restart mode for 3 minutes.
When the detected pressure is 1 kgf/
F
[14.2 PSIG] or less immediately
before restarting, the compressor falls into an abnormal stop with a
check code <5201>.
For 3 minutes after compressor restarting, during defrosting operation,
and for 3 minutes after returning from defrosting operation, above
mentioned symptoms are not determined as abnormal.
Defective high pressure sensor
Decrease of internal pressure caused by gas
leakage
Disconnection or contact failure of connector
Malfunction of input circuit on outdoor multi controller
circuit board
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting
any connectors, or replacing boards.
Diagnosis
Remedy
The black square (■) indicates a switch position.
63HS: High pressure sensor
SW1 Setting
ON
OFF
Display on LED1, 2
Unit
−99.9–999.9
kgf/
F
[PSIG]
4
1 2
5 6 7 8
3
No
Yes
Yes
No
No
70
OCH634C
Is there any abnormality such
as disconnection, looseness or
breakage?
Is the detected internal pressure
normal?
Is the detected pressure normal?
Connect the wiring/connector properly.
Replace it in case of breakage.
Check the refrigerant circuit, and recharge
refrigerant after repairing the leakage.
Replace the 63HS.
Replace the outdoor multi
controller circuit board.
Check the wiring and connector connection.
Check an internal pressure of the
refrigerant circuit.
Check the detected pressure in 63HS,
then compare it with the internal pressure.
The detected pressure in 63HS can be displayed by an
operation of SW1 on the outdoor controller board.