Check code
1501
(U2)
Refrigerant shortage trouble
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Chart 2 of 2
*For the voltage, refer to
"8-8. HOW TO CHECK THE
COMPONENTS".
No
No
No
Yes
Yes
Yes
Yes
Yes
No
51
OCH634C
Continued from the previous page.
Is the voltage(*) detected?
Is the voltage normal value?
Is it free from any trace of over-
heating or burning?
Is the resistance detected?
Replace the outdoor controller board.
Replace the 63HS.
Replace the indoor LEV.
Replace the indoor controller board.
Check the 63HS voltage.
Check the voltage and appearance of the
outdoor controller board.
Disconnect the indoor LEV wiring and
check the resistance.
Is the resistance detected?
Replace the thermistor.