8-1-2. Countermeasures for Error During Test Run
• If a problem occurs during test run, a code number will appear on the remote controller (or LED on the outdoor unit), and the
air conditioning system will automatically cease operating.
Determine the nature of the abnormality and apply corrective measures.
Check
code
(2 digits)
Check
code
(4 digits)
Trouble
Detected Unit
Remarks
Indoor
Outdoor
Remote
Controller
Ed
0403
Serial communication error
Outdoor unit Multi controller board–Power board
communication trouble
U2
1102
Compressor temperature trouble
Check delay code 1202
UE
1302
High pressure trouble
Check delay code 1402
U7
1500
Superheat due to low discharge temperature trouble
Check delay code 1600
U2
1501
Refrigerant shortage trouble
Check delay code 1601
Closed valve in cooling mode
Check delay code 1501
P6
1503
Indoor HEX freezing protection
EF
1508
4-way valve trouble in heating mode
Check delay code 1608
UF
4100
Compressor current interruption (locked compressor)
Check delay code 4350
Pb
4114
Fan trouble (Indoor)
UP
4210
Compressor overcurrent interruption
U9
4220
Voltage shortage/overvoltage/PAM error/L1open phase/primary
current sensor error/power synchronization signal error
Check delay code 4320
U5
4230
Heat sink temperature trouble
Check delay code 4330
U6
4250
Power module trouble
Check delay code 4350
U8
4400
Fan trouble (Outdoor unit)
Check delay code 4500
U3
5101
Compressor temperature thermistor (TH4) open / short
U4
5102
Suction pipe temperature thermistor (TH6) open / short
U4
5105
Outdoor liquid pipe temperature thermistor (TH3) open/short
Check delay code 1205
U4
5106
Ambient temperature thermistor (TH7) open/short
Check delay code 1221
U4
5109
HIC pipe temperature thermistor (TH2) open/short
Check delay code 1222
U4
5110
Heat sink temperature thermistor (TH8) open/short
Check delay code 1214
F5
5201
High pressure sensor (63HS) trouble
Check delay code 1402
F3
5202
Low pressure sensor (63LS) trouble
Check delay code 1400
UH
5300
Primary current error
Check delay code 4310
A0
6600
Duplex address error
Only M-NET Remote controller is detected.
A2
6602
Transmission processor hardware error
Only M-NET Remote controller is detected.
A3
6603
Transmission bus BUSY error
Only M-NET Remote controller is detected.
A6
6606
Signal communication error with transmission processor
Only M-NET Remote controller is detected.
A7
6607
No ACK error
Only M-NET Remote controller is detected.
A8
6608
No response frame error
Only M-NET Remote controller is detected.
E0/E4
6831
MA communication receive error
Only MA Remote controller is detected.
E3/E5
6832
MA communication send error
Only MA Remote controller is detected.
E3/E5
6833
MA communication send error
Only MA Remote controller is detected.
E0/E4
6834
MA communication receive error
Only MA Remote controller is detected.
EF
7100
Total capacity error
EF
7101
Capacity code error
EF
7102
Connecting excessive number of units and branch boxes
EF
7105
Address setting error
EF
7130
Incompatible unit combination
NOTES:
1. When the outdoor unit detects No ACK error/No response error, an object indoor unit is treated as a stop, and not assumed to be abnormal.
2. The check codes displayed on the units may be different between the error source and others. In that case, please refer to the check code of
error source by displayed attribute and address.
3. Refer to the service manual of indoor unit or remote controller for the detail of error detected in indoor unit or remote controller.