[
X
Troubleshooting ]
- 212 -
HWE10190
GB
2) Therefore, if the power source is turned off within 30 minutes, the lev remains fully closed and the refrigerant remains sealed.
When only the power for the indoor unit is turned off, the indoor unit LEV turns from faintly open to fully closed.
3) In the cooling cycle, the section between "21S4b, c" and "LEV2" will form a closed circuit. To recover the refrigerant or evac-
uate the system, "LEV1" and "SV5b, c" will be open by setting SW5-8 to ON in the stop mode.
Set SW5-8 to OFF upon completion of all work.
3. Leak spot: In the case of extension pipe for indoor unit (Heating season)
(1) Run all the indoor units in heating test run mode.
1) To run the indoor unit in test run mode, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON.
2) Change the setting of the remote controller for all the indoor units to the heating mode.
3) Check that all the indoor units are performing a heating operation.
(2) Stop all the indoor units, and stop the compressor.
1) To stop all the indoor units and the compressors, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON.
2) Check that all the indoor units are stopped.
(3) Close the service valves (BV1 and BV2).
(4) Collect the refrigerant that remains inside the indoor unit. Do not discharge refrigerant into air into the atmosphere
when it is collected.
(5) Repair the leak.
(6) After repairing the leak, perform evacuation of the extension pipe for the indoor unit, and open the service valves
(BV1 and BV2) to adjust refrigerant.
4. Leak spot: In the case of outdoor unit (Heating season)
1) Collect the refrigerant in the entire system (outdoor unit, extended pipe and indoor unit).Do not discharge refrigerant into the
atmosphere when it is collected.
2) Repair the leak.
3) After repairing the leak, perform evacuation of the entire system, and calculate the standard amount of refrigerant to be added
(for outdoor unit, extended pipe and indoor unit), and charge the refrigerant.
Refer to "IX [4] 3. "(page 112)
If the indoor or outdoor units need to be turned off for repairing leaks during Step 1) above, turn off the power approximately
1 hour after the units came to a stop.
→
LEV2 on the outdoor unit will open when the unit remains stopped for 15 minutes. When these valves are open, refrigerant
in the outdoor unit heat exchanger can be collected, and air can be evacuated from the outdoor unit heat exchanger.
If the power is turned off in less than 15 minutes, LEV2 may close, trapping high-pressure refrigerant in the outdoor unit heat
exchanger and creating a highly dangerous situation.
0000002115.book 212 ページ 2011年6月4日 土曜日 午前10時48分
Содержание PUHY-P250YJM-A
Страница 1: ......
Страница 11: ... 2 HWE10190 GB ...
Страница 25: ... 16 HWE10190 GB ...
Страница 45: ... II Restrictions 36 HWE10190 GB ...
Страница 47: ... 38 HWE10190 GB ...
Страница 57: ... 48 HWE10190 GB ...
Страница 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Страница 71: ... 62 HWE10190 GB ...
Страница 73: ... V Remote Controller 64 HWE10190 GB ...
Страница 75: ... 66 HWE10190 GB ...
Страница 82: ... 73 HWE10190 GB VII Refrigerant Circuit 1 Refrigerant Circuit Diagram 75 2 Principal Parts and Functions 78 ...
Страница 83: ... 74 HWE10190 GB ...
Страница 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Страница 93: ... 84 HWE10190 GB ...
Страница 115: ... VIII Control 106 HWE10190 GB ...
Страница 117: ... 108 HWE10190 GB ...
Страница 137: ... 128 HWE10190 GB ...
Страница 225: ... X Troubleshooting 216 HWE10190 GB ...
Страница 226: ... 217 HWE10190 GB XI LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 219 ...
Страница 227: ... 218 HWE10190 GB ...
Страница 272: ......