- 112 -
HWE10190
GB
3. Amount of refrigerant to be added
The amount of refrigerant that is shown in the table below is factory-charged to the outdoor units.
The amount necessary for extended pipe (field piping) is not included and must be added on site.
(1) Calculation formula
The amount of refrigerant to be added depends on the size and the length of field piping. (unit in m[ft])
Round up the calculation result to the nearest 0.1kg. (Example: 18.04kg to 18.1kg)
Round up the calculation result in increments of 4oz (0.1kg) or round it up to the nearest 1oz.
(Example: 178.21
oz
to 179oz)
Outdoor unit model
P250
P350
P400
Amount of pre-charged refrigerant in
the outdoor unit (kg)
8.0
11.5
11.5
Amount of pre-charged refrigerant in
the outdoor unit [lbs-oz]
17-10
25-6
25-6
Amount of added refrigerant (kg) = (0.29x L
1
) + (0.2 x L
2
) + (0.12 x L
3
) + (0.06 x L
4
) + (0.024 x L
5
) +
α
Amount of added refrigerant (oz) = (3.12x L
1
' ) +(2.15 x L
2
' ) + (1.29 x L
3
' ) + (0.65 x L
4
' ) + (0.26 x L
5
' ) +
α'
L
1
: Length of ø19.05 [3/4"] liquid pipe (m)
L
2
: Length of ø15.88 [5/8"] liquid pipe (m)
L
3
: Length of ø12.7 [1/2"] liquid pipe (m)
L
4
: Length of ø9.52 [3/8"] liquid pipe (m)
L
5
: Length of ø6.35 [1/4"] liquid pipe (m)
α
,
α
' : Refer to the table below.
L
1
' : Length of ø19.05 [3/4"] liquid pipe [ft]
L
2
' : Length of ø15.88 [5/8"] liquid pipe [ft]
L
3
' : Length of ø12.7 [1/2"] liquid pipe [ft]
L
4
' : Length of ø9.52 [3/8"] liquid pipe [ft]
L
5
' : Length of ø6.35 [1/4"] liquid pipe[ft]
Total capacity of
connected indoor units
α
(kg)
α
'(oz)
P250, P300-F
3.0
106
P500, P600-F
5.0
177
P750, P900-F
8.0
283
0000002115.book 112 ページ 2011年6月4日 土曜日 午前10時48分
Содержание PUHY-P250YJM-A
Страница 1: ......
Страница 11: ... 2 HWE10190 GB ...
Страница 25: ... 16 HWE10190 GB ...
Страница 45: ... II Restrictions 36 HWE10190 GB ...
Страница 47: ... 38 HWE10190 GB ...
Страница 57: ... 48 HWE10190 GB ...
Страница 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Страница 71: ... 62 HWE10190 GB ...
Страница 73: ... V Remote Controller 64 HWE10190 GB ...
Страница 75: ... 66 HWE10190 GB ...
Страница 82: ... 73 HWE10190 GB VII Refrigerant Circuit 1 Refrigerant Circuit Diagram 75 2 Principal Parts and Functions 78 ...
Страница 83: ... 74 HWE10190 GB ...
Страница 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Страница 93: ... 84 HWE10190 GB ...
Страница 115: ... VIII Control 106 HWE10190 GB ...
Страница 117: ... 108 HWE10190 GB ...
Страница 137: ... 128 HWE10190 GB ...
Страница 225: ... X Troubleshooting 216 HWE10190 GB ...
Страница 226: ... 217 HWE10190 GB XI LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 219 ...
Страница 227: ... 218 HWE10190 GB ...
Страница 272: ......