- 32 -
[
II
Restrictions ]
GB
HWE10190
4. An example of a system in which a system controller is connected to the transmission cable for the centralized con-
trol system and the power is supplied from the outdoor unit
(1) Sample control cable wiring configuration
(2) Cautions
1) No more than two MA remote controllers can be connect-
ed to a group of indoor units.
2) Do not connect the terminal blocks (TB5) of the indoor
units that are connected to different outdoor units with
each other.
3) The replacement of the power jumper connector from
CN41 to CN40 must be performed on only one outdoor
unit in the system.
4) Connect the S (shield) terminal of the terminal block for
centralized control system connection (TB7) on the out-
door unit whose power jumper was moved from CN41 to
CN40 to the ground terminal of the unit.
5) When a power booster is connected to the transmission
cable for the centralized control system, leave the power
jumper on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor-outdoor transmission cable
Same as section [5] 1.
2) Transmission cable for the centralized control system
L31 +L32
≤
200m [656ft]
(only L31, L32
≤
200m [656ft])
3) MA remote controller wiring
Same as section [5] 1.
4) Maximum cable distance via outdoor unit (1.25 mm
2
[AWG16] min.)
L32+L31+L1
≤
500m [1640ft]
L32+L2
≤
500m [1640ft]
L1+L2+L31
≤
500m [1640ft]
IC
TB5
TB 15
1 2
01
A B
IC
TB5
1 2
TB 15
02
A B
Group
Group
Note 1 When only the LM adapter is connected, leave DIP SW2-1 to OFF as it is.
Note 2 LM adapter operates on a single-phase 200 VAC power supply.
L1
L2
OC
TB3
TB7
S
S
S
S
51
OC
TB3
TB7
52
A B S
L31
L32
Note 2 and 3
Note 1
Leave the power jumper as
it is on CN41.
SW2-1 OFF→ON
To be connected
Move the power jumper from
CN41 to CN40.
SW2-1 OFF→ON
MA (main body)
MA (main body)
System controller
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
0000002115.book 32 ページ 2011年6月4日 土曜日 午前10時48分
Содержание PUHY-P250YJM-A
Страница 1: ......
Страница 11: ... 2 HWE10190 GB ...
Страница 25: ... 16 HWE10190 GB ...
Страница 45: ... II Restrictions 36 HWE10190 GB ...
Страница 47: ... 38 HWE10190 GB ...
Страница 57: ... 48 HWE10190 GB ...
Страница 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Страница 71: ... 62 HWE10190 GB ...
Страница 73: ... V Remote Controller 64 HWE10190 GB ...
Страница 75: ... 66 HWE10190 GB ...
Страница 82: ... 73 HWE10190 GB VII Refrigerant Circuit 1 Refrigerant Circuit Diagram 75 2 Principal Parts and Functions 78 ...
Страница 83: ... 74 HWE10190 GB ...
Страница 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Страница 93: ... 84 HWE10190 GB ...
Страница 115: ... VIII Control 106 HWE10190 GB ...
Страница 117: ... 108 HWE10190 GB ...
Страница 137: ... 128 HWE10190 GB ...
Страница 225: ... X Troubleshooting 216 HWE10190 GB ...
Страница 226: ... 217 HWE10190 GB XI LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 219 ...
Страница 227: ... 218 HWE10190 GB ...
Страница 272: ......