VIII
Control ]
- 91 -
HWE10190
GB
Fan operation on the Fresh Air Intake type units
When the return air dry temperature is 5°C [41°F] or below, units may be forced to operate in the heating mode to prevent
humidifier from freezing up and to prevent cold drafts.
The fan will stop when all refrigerant systems are in trouble and during the defrost cycle. Refer to the table below for how to
set the related switches and for the operation patterns.
1) The settings in the shaded areas indicate factory settings.
2) Turning on the fan during the defrost cycle will send cold air into the room, delay normal operation from being resumed, and
cause the room temperature to drastically drop. To avoid this, set SW3-4 to OFF.
3) The operating temperature (return air dry temperature) of the fan is 0°C [32°F] or above. If the fan is operated at the outside
temperature below 0°C [32°F], depending on the ambient air conditions, dew condensation may form on the panel surface.
Use caution so that dew drips will not damage the surrounding equipments.
2) SW2,SW3-2,SW3-9,SW3-10,SW4
(3) Address switches
How to set the indoor unit addresses depends on the system. Refer to the Outdoor Unit Installation Manual and other related
documents for how to set the addresses.
Each address consists of two digits.
(Example)
To set the address to "3," set the 1's digit to "3" and leave the 10's digit to "0."
To set the address to "25," set the 1's digit to "5" and the 10's digit to "2."
3. Switch functions <Remote controller>
(1) MA remote controller (PAR-21MAA)
MA remote controller does not have switches. Refer to the Operation Manual for how to make the function settings.
Specification
SW
Operation
Notes
OFF
ON
Forced heating
operation/Fan
operation when
units are in trou-
ble
SW
1-7
Forced heating op-
eration is disabled.
The fan will operate
when the units are
in trouble. (The fan
will stop when the
fan is in trouble or
when there is a
communication er-
ror.)
Forced heating op-
eration is enabled.
The fan will not op-
erate when the
units are in trouble.
When the return air dry temperature is 5°C [41°F] or
below, units are forced to operate in the heating
mode regardless of the mode setting to prevent
cold drafts.
The units will resume operation in the selected
mode when the return air dry temperature reaches
6°C[43°F].
Regardless of the outside air temperature, the fan
will not operate if there are any problems.
Fan operation
during defrost
cycle
SW
3-4
The fan will not op-
erate when the
units in all refriger-
ant systems are in
the defrost cycle.
The fan will operate
when the units are
in the defrost cycle.
This switch is set to off to prevent the humidifier
from freezing up and to prevent cold drafts.
SW2
SW4
−
50
OFF
OFF
ON
−
100
ON
OFF
ON
No.1
100
ON
OFF
OFF
No.2 50 OFF OFF OFF
ON
OFF
1 2 3 4 5 6
1 2 3 4 5
1 2 3 4 5
ON
OFF
1 2 3 4 5 6
1 2 3 4 5
1 2 3 4 5
ON
OFF
1
2 3 4 5 6
ON
OFF
1
2 3 4 5 6
<Notes on capacity code and model settings>
If the capacity code or model setting has been incorrectly
set (e.g., when replacing the circuit board), both the indoor
and outdoor units need to be power reset.
P300-F
P600-F
P900-F
Model
System Capacity SW3-2 SW3-9 SW3-10
0000002115.book 91 ページ 2011年6月4日 土曜日 午前10時48分
Содержание PUHY-P250YJM-A
Страница 1: ......
Страница 11: ... 2 HWE10190 GB ...
Страница 25: ... 16 HWE10190 GB ...
Страница 45: ... II Restrictions 36 HWE10190 GB ...
Страница 47: ... 38 HWE10190 GB ...
Страница 57: ... 48 HWE10190 GB ...
Страница 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Страница 71: ... 62 HWE10190 GB ...
Страница 73: ... V Remote Controller 64 HWE10190 GB ...
Страница 75: ... 66 HWE10190 GB ...
Страница 82: ... 73 HWE10190 GB VII Refrigerant Circuit 1 Refrigerant Circuit Diagram 75 2 Principal Parts and Functions 78 ...
Страница 83: ... 74 HWE10190 GB ...
Страница 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Страница 93: ... 84 HWE10190 GB ...
Страница 115: ... VIII Control 106 HWE10190 GB ...
Страница 117: ... 108 HWE10190 GB ...
Страница 137: ... 128 HWE10190 GB ...
Страница 225: ... X Troubleshooting 216 HWE10190 GB ...
Страница 226: ... 217 HWE10190 GB XI LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 219 ...
Страница 227: ... 218 HWE10190 GB ...
Страница 272: ......