VIII
Control ]
- 87 -
HWE10190
GB
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) When set to the capacity priority mode and if the following conditions are met, the Low-noise mode will terminate, and the unit
will go back into the normal operation mode.
Cooling: Outside temperature is high or high pressure is high.
Heating: Outside temperature is low or low pressure is low.(page 22)
4) The table below summarizes the factory settings for dipswitches SW5-1 through SW5-4, and SW5-7. The factory setting for
all other dipswitches is OFF.
(2) INV board
Functions are switched with the following connector.
CN6 short-circuit connector is mated with the mating connector.
Leave the short-circuit connector on the mating connector during normal operation to enable error detection and protect the
equipment from damage.
Switch
Function
Function according to switch setting
Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF
ON
OFF
ON
OC
OS
SW5
1
Model selection
See the table below (Note 4)
Before being energized
C
C
2
3
4
5
Low-noise mode
selection
Capacity priority
mode (Note 3)
Low-noise mode
Before being energized
A
-
6
-
-
-
-
-
-
7
Model selection
See the table below (Note 4)
Before being energized
B
B
8
-
-
-
-
-
-
9
-
-
-
-
-
-
10
-
-
-
-
-
-
SW 5
Model
1
2
3
4
7
ON
ON
OFF
OFF
ON
P250 model
OFF
ON
ON
OFF
ON
P350 model
ON
ON
ON
OFF
ON
P400 model
Connector
Function
Function according to connec-
tor
Setting timing
Enabled
Disabled
Enabled
Disabled
CN6 short-
circuit con-
nector
Enabling/disabling the following error
detection functions;
ACCT sensor failure
(5301 Detail No. 115)
ACCT sensor circuit failure
(5301 Detail No.117)
IPM open/ACCT erroneous wiring
(5301 Detail No. 119)
Detection of ACCT erroneous wiring
(5301 Detail No.120)
Error detec-
tion enabled
Error detec-
tion disable
(No load op-
eration is pos-
sible.)
Anytime after power on
0000002115.book 87 ページ 2011年6月4日 土曜日 午前10時48分
Содержание PUHY-P250YJM-A
Страница 1: ......
Страница 11: ... 2 HWE10190 GB ...
Страница 25: ... 16 HWE10190 GB ...
Страница 45: ... II Restrictions 36 HWE10190 GB ...
Страница 47: ... 38 HWE10190 GB ...
Страница 57: ... 48 HWE10190 GB ...
Страница 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Страница 71: ... 62 HWE10190 GB ...
Страница 73: ... V Remote Controller 64 HWE10190 GB ...
Страница 75: ... 66 HWE10190 GB ...
Страница 82: ... 73 HWE10190 GB VII Refrigerant Circuit 1 Refrigerant Circuit Diagram 75 2 Principal Parts and Functions 78 ...
Страница 83: ... 74 HWE10190 GB ...
Страница 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Страница 93: ... 84 HWE10190 GB ...
Страница 115: ... VIII Control 106 HWE10190 GB ...
Страница 117: ... 108 HWE10190 GB ...
Страница 137: ... 128 HWE10190 GB ...
Страница 225: ... X Troubleshooting 216 HWE10190 GB ...
Страница 226: ... 217 HWE10190 GB XI LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 219 ...
Страница 227: ... 218 HWE10190 GB ...
Страница 272: ......