–138–
Checking
code
6607
(continued)
Meaning, detecting method
System
compo-
sition
Generating
unit address
Display of
trouble
Detecting
method
Cause
Checking method & countermeasure
No ACK error
When no ACK signal is detected in 6 continuous times with 30 second
interval by transmission side controller, the transmission side detects error.
Note:
The address/attribute shown on remote controller indicates the
controller not providing the answer (ACK).
(3) Connecting system with system controller (MELANS)
1
Outdoor
unit (OC)
2
BC
controller
(BC)
3
Indoor
unit (IC)
4
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
No reply
(ACK) at
BC
transmis-
sion to OC
No reply
(ACK) at
RC
transmis-
sion to IC
No reply
(ACK) at
transmis-
sion
of SC to IC
No reply
(ACK) at
transmission
of IC to RC
No reply
(ACK) at
transmis-
sion of
MELANS to
RC
As same that for single refrigerant system.
Same cause of that for grouping from plural re-
frigerants.
Trouble of partial IC units:
1) Same cause as that for single refrigerant
system.
Trouble of all IC in one refrigerant system:
1) Cause of total capacity error.
(7100)
2) Cause of capacity code setting error. (7101)
3) Cause of connecting number error. (7102)
4) Cause of address setting error.
(7105)
5) Slipping off or short circuit of transmission line
of OC unit terminal block for central control
(TB7).
6) Power source shut down of OC unit.
7) Trouble of OC unit electrical system.
Trouble of all IC:
1) As same that for single refrigerant system.
2) Insertion of power supply connector (CN40)
into OC unit transmission line for centralized
control.
3) Slipping off or power source shut down of
power supply unit for transmission line.
4) Faulty system controller (MELANS).
Same cause as that for plural refrigerant system.
Trouble of partial IC units:
1) Same cause of that for single refrigerant sys-
tem.
Trouble of all IC in one refrigerant system:
1) Error detected by OC unit.
Total capacity error.
(7100)
Capacity code setting error. (7101)
Connecting number error.
(7102)
Address setting error.
(7105)
2) Slipping off or short circuit of transmission line
of OC unit terminal block for central control
(TB7).
3) Power source shut down of OC unit.
4) Trouble of OC unit electrical system.
Trouble of all IC:
1) As same that for single refrigerant system.
2) Insertion of power supply connector (CN40)
into OC unit transmission line for central-ized
control.
3) Slipping off or power shutdown of power sup-
ply unit for transmission line.
4) Faulty MELANS.
Same countermeasure as that for single
refrigerant system.
Same countermeasure as that for IC unit
error in plural refrigerant system.
→
Same countermeasure as that for
single refrigerant system.
Confirm OC trouble diagnosis LED.
→
At trouble generation, check for the
content according to check code.
Check the content of 5)~7) shown left.
Confirm voltage of transmission line for
centralized control.
• More than 20V
→
Confirm 1) 2) left.
• Less than 20V
→
Confirm 3) left.
Same countermeasure as that for plur-
al refrigerant system.
→
Same countermeasure as that for
single refrigerant system.
Confirm OC trouble diagnosis LED.
→
At trouble generation, check for the
content according to check code.
Check the content of 2)~4) shown left.
Check the causes of 1) ~ 4) left.
Содержание PUHY-200YMF-C
Страница 16: ... 15 FANCON board CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 G A board CNE CNDC1 ...
Страница 17: ... 16 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 ...
Страница 18: ... 17 RELAY 10 board RELAY 4 board ...
Страница 104: ... 103 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...