–106–
2) Temperature Sensor
Thermistor troubleshooting flow
Start
Disconnect applicable thermistor
connector from the board.
Measure temperature of applicable
thermistor (actual measured value).
Check thermistor resistance value.
Compare temperature for thermistor
resistance value with actual mea-
sured valued.
No
difference?
Insert applicable thermistor connector
into board, and check sensor input
temperature on LED monitor for differ-
ence.
No
difference?
No abnormality.
Change thermistor.
Check for connection
problem.
Change the controller
board.
Note 5
Yes
No
No
Yes
Note 4
Note 2
Note 1
Note 3
Содержание PUHY-200YMF-C
Страница 16: ... 15 FANCON board CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 G A board CNE CNDC1 ...
Страница 17: ... 16 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 ...
Страница 18: ... 17 RELAY 10 board RELAY 4 board ...
Страница 104: ... 103 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...