–61–
2
PURY-(P)200·250YMF-C
1)
Starting of defrost operations
• After integrated 43 minutes of compressor operations, defrosting operations start when –8˚C : P-YMF-C, –6˚C :
YMF-C or less of piping temperature (TH7) is detected for 3 consecutive minutes.
• Forcible defrosting operations start by turning on forcible defrost switch (SW2-7) if 3 minutes have already elapsed
after compressor start or completion of defrosting operations.
2)
Completion of defrosting operations
Defrosting operations stop when 10 minutes have passed since start of defrosting operation, or piping temperature
(TH5) reaches 8˚C or more.
(Defrosting operations do not stop for 4 minutes after starting, except when piping temperature exceeds (TH5 and
TH7) 20˚C and Pd >10kg/cm
2
G (0.98MPa).)
3)
Defrosting prohibition
Defrosting operations do not start during oil recovery, and for 10 minutes after starting compressor.
4)
Trouble during defrosting operations
When trouble is detected during defrosting operations, the defrosting operations stop, and defrosting prohibition
time decided by integrated operation time of compressor is set to be 20 minutes.
5)
Change in number of operating indoor units during defrosting operations
• In case number of operating indoor units changes during defrosting operations, the defrosting operations continue,
and control of unit number change is performed after the defrosting operations are finished.
• Even in case all indoor units stop or thermostat is turned off during defrosting operations, the defrosting operations
do not stop until expected defrosting activities are completed.
(8)
Control of liquid level detecting heater
Detect refrigerant liquid level in accumulator, and heat refrigerant with liquid level heater for judging refrigerant
amount. 6 steps of duty control is applied to liquid level heater depending on frequency and outdoor air temperature,
1minute after starting compressor.
(9)
Judgement of refrigerant amount
LD2 OFF
LD1 ON
LD1 OFF
LD : Liquid level Detected Switch
AL=1
AL=0
LD2 ON
–
AL=2
Inlet
AL=2
AL=0
AL=1
LD2
Float
LD1
Outlet
Oil return
Содержание PUHY-200YMF-C
Страница 16: ... 15 FANCON board CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 G A board CNE CNDC1 ...
Страница 17: ... 16 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 ...
Страница 18: ... 17 RELAY 10 board RELAY 4 board ...
Страница 104: ... 103 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...