–93–
(2)
Trouble and remedy of remote controller
Symptom
Cause
Checking method & countermeasure
1
2
Despite pressing of
remote controller
switch, operation
does not start with
no electronic sound.
(No powering signal
appears.)
At about 10 seconds
after turning remote
controller operation
switch ON, the
display distinguishes
and the operation
stops.
1) M-NET transmission power source is not supplied
from outdoor unit.
1
Main power source of outdoor unit is not
connected.
2
Slipping off of connector on outdoor unit circuit
board.
Main board
: CNS1, CNVCC3
INV board
: CNAC2, CNVCC1, CNL2
3
Faulty power source circuit of outdoor unit.
• Faulty INV board,
• Blown fuse (F1 on INV board)
• Broken diode stack
• Broken resistor (R1) for rush current protection
2) Short circuit of transmission line.
3) Erroneous wiring of M-NET transmission line at outdoor unit.
1
Transmission line disconnection or slipping off from terminal
block.
2
Erroneous connection of indoor/outdoor transmission line to
TB7.
4) Slipping off of transmission wiring at remote controller.
5) Faulty remote controller.
The cause of 2) and 3) is
displayed with self-diagnosis
LED for 7102 error.
1) Power source is not fed to indoor unit from transformer.
1
Main power source of indoor unit is not turned on.
2
Slipping off of connector (CND, CNT, CN3T) on indoor controller board.
3
Blown fuse on indoor controller board.
4
Faulty or disconnected transformer of indoor unit.
5
Faulty indoor controller board.
2) Faulty outdoor control circuit board or being out of control.
As normal transmission is failed between indoor and outdoor units, outdoor unit model can not be
recognized.
Checking method & countermeasure
a) Check transmission terminal block of
remote controller for voltage.
i) In case of 17 ~ 30V
→
Faulty network remote controller
ii) In case of less than 17V
→
See “Transmission Power Circuit
(30V) Check Procedure”.
Check indoor LED3
Lighting?
Check for the change of LED
display by operating dip switch
SW1 for self-diagnosis.
Extinguishing or
unable to confirm
Check indoor unit
power source terminal
block voltage
AC 220~240V?
Check fuse on circuit
board
Blown?
Check connector slipping
off (CND, CNT, CN3T)
Slipped off?
Check transformer
resistance value
Within rated?
Check self-diagnosis
function of outdoor unit
Changed?
Faulty indoor
controller board
Check main power source
of power source wiring.
Apply power
source again.
Check 220V~240V
circuit for short circuit
and ground fault.
Improper connector
connection
Check cause of trans-
former disconnection.
•Ground fault on circuit
board
•Ground fault on
sensor, LEV
Check self-diagnosis function af-
ter powering outdoor unit again.
Changed?
Casual
trouble
Faulty outdoor unit
control circuit board
Repair
faulty point.
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
Lighting
*1 Check the transformer in accordance with the “TROUBLE SHOOTING” in the indoor unit’s service handbook.
NO
*1
Содержание PUHY-200YMF-C
Страница 16: ... 15 FANCON board CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 G A board CNE CNDC1 ...
Страница 17: ... 16 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 ...
Страница 18: ... 17 RELAY 10 board RELAY 4 board ...
Страница 104: ... 103 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...