Control every minute so that superheat amount detected by bypass inlet and oulet
temperatures (TH12, TH15) stay in the specified range.
Control every minute so that detected differential pressure (PS1, PS3) stay in the
specified range.
60 or more pulses are sometimes detected because of rise in liquid side pressure (PS1).
• Liquid level
control *3
• Differential
pressure control
*2
60
Differential
Pressure control
*2
[2] Control of BC Controller
(1)
Control of SVA, SVB and SVC
SVA, SVB and SVC are turned on and off depending on connection mode.
Cooling
Heating
Stop
Defrost
SVA
ON
OFF
OFF
OFF
SVB
OFF
ON
OFF
OFF
SVC
ON
OFF
OFF
OFF
(2)
Control of SVM
SVM is turned on and off corresponding to operation mode.
Operation mode
Cooling-only
Cooling-main
Heating-only
Heating-main
Stop
SVM
ON
OFF
OFF
OFF
OFF
(3)
Control of LEV
LEV opening (sj) is controlled corresponding to operation mode as follows:
(Number of pulse)
Operation mode
Cooling-only
Heating-only
Cooling-main
Heating-main
Stop
*
SVM is not built in depending on models.
* Please confirm that the above parts of BC controllers are being color-corded and shown with the name plate inside
the BC controller unit.
Содержание PUHY-200YMF-C
Страница 16: ... 15 FANCON board CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 G A board CNE CNDC1 ...
Страница 17: ... 16 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 ...
Страница 18: ... 17 RELAY 10 board RELAY 4 board ...
Страница 104: ... 103 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...