5. Dip switch setting
5.2. Outdoor unit setting
Set Dip SW 1-6 to set the outdoor unit type.
Dip SW 1-6
Setting
Note
OFF
Split type
Necessary to connect TH2
ON
Packaged type
Not necessary to connect TH2
Pressure sensor (option) is necessary for SUZ-SWM outdoor unit.
Dip SW 4-1
Setting
OFF
WITHOUT Pressure sensor
ON
WITH Pressure sensor
Flow sensor (option) is necessary for PUZ-(H)WM outdoor unit.
Dip SW 4-2
Setting
OFF
WITHOUT Flow sensor
ON
WITH Flow sensor
Dip SW 1-3 (DHW tank)
Dip SW 1-4 (Immersion heater)
Dip SW 1-5 (BH function)
System diagram
OFF
(WITH DHW tank)
OFF
(WITHOUT immersion heater)
OFF
(For heating and DHW)
Booster heater
Heat emitter
DHW tank
THW5
THW1
THW2
3-way valve
OFF
(WITH DHW tank)
ON
(WITH immersion heater)
OFF
(For heating and DHW)
Booster heater
Heat emitter
DHW tank
THW5
THW1
THW2
Immersion heater
3-way valve
OFF
(WITH DHW tank)
OFF
(WITHOUT immersion heater)
ON
(For heating only)
Booster heater
Heat emitter
DHW tank
THW5
THW1
THW2
3-way valve
OFF
(WITH DHW tank)
ON
(WITH immersion heater)
ON
(For heating only)
Booster heater
Heat emitter
DHW tank
THW5
THW1
THW2
Immersion heater
3-way valve
ON
(WITHOUT DHW tank)
—
—
Booster heater
Heat emitter
THW1
THW2
<Summary of Function setting>
5.3. Functions setting
Set Dip SW 1-3 to set whether the system has a DHW tank.
Dip SW 1-3
Setting
Note
OFF
WITH DHW tank
Necessary to connect THW5
ON
WITHOUT DHW tank
Not necessary to connect THW5
When Dip SW 1-3 is ON, DHW and legionella prevention mode is not available.
Set Dip SW 1-4 to set whether the system has an immersion heater.
Dip SW 1-4
Setting
OFF
WITHOUT immersion heater
ON
WITH immersion heater
Set Dip SW 1-5 to set the booster heater function.
Dip SW 1-5
Setting
OFF
For heating and DHW
ON
For heating only or WITHOUT booster heater