EN-17
Dip switch
Function
OFF
ON
Default
setting
SW1
SW1-1
System setting
SW1-1 SW1-2
ON/OFF input
Change mode input Change temp. input
OFF
OFF
Remote controller
Remote controller
Remote controller
ON
OFF
External input
Remote controller
OFF
ON
Analog input
(4-20mA/1-5V)
External input
Analog input
(4-20mA/1-5V)
ON
ON
External input
Analog input
(0-10V)
OFF
SW1-2
OFF
SW1-3
DHW tank
WITH DHW tank
WITHOUT DHW tank
OFF
SW1-4
Immersion heater
WITHOUT Immersion heater
WITH Immersion heater
OFF
SW1-5
Booster heater function
For Heating and DHW
For Heating only or WITHOUT Booster heater OFF
SW1-6
Outdoor unit type
Split type
Packaged type
OFF
SW1-7
Cooling mode function
Inactive
Active
OFF
SW1-8
Automatic change over mode function
(Heating mode ↔ DHW mode)
Active
Inactive
OFF
SW1-9
Automatic change over mode function
(Cooling mode ↔ DHW mode)
Active
Inactive
OFF
SW1-10
Heat pump maximum outlet water temp.
55°C
60°C
ON*1
SW2
SW2-1
DHW temparature drop
10deg
20deg
OFF
SW2-2
Operation in DHW mode
Eco
Nomal
OFF
SW2-3
Economy setting for water circulation pump
Inactive
Active
OFF
SW2-4
Legionella prevention mode setting
SW2-4
SW2-5
Operation
OFF
OFF
Activate every "1 times" DHW operations.
ON
OFF
Activate every "15 times" DHW operations.
OFF
ON
Activate every "150 times" DHW operations.
ON
ON
Activate by IN2.
ON
SW2-5
OFF
SW2-6
Legionella prevention hot water temp.
60°C
65°C
OFF
SW2-7
Immersion heater usage in DHW mode
Used
Not used
OFF
SW2-8
Booster heater usage in Heating mode
Used
Not used
OFF
SW2-9
Booster heater usage in DHW mode
Used
Not used
OFF
SW2-10
Heater delay timer in DHW mode
15min
30min
OFF
SW3
SW3-1
3-way valve control during defrost in Heating mode OFF (Heating circuit)
ON (DHW circuit)
OFF
SW3-2
Water circulation pump manual operation
OFF
ON
OFF
SW3-3
3-way valve manual operation
OFF
ON
OFF
SW3-4
Room thermostat input (Ana,IN1) logic change
Operation stop at thermostat short
Operation stop at thermostat open
OFF
SW3-5
Comp. OFF for mode change (DHW ↔ Heating)
Inactive
Active
OFF
SW3-6
Flow switch input (IN3) logic change
Failure detection at fl ow switch short
Failure detection at fl ow switch open
OFF
SW3-7
Emergency mode
(Heater only operation)
Normal
Emergency mode (Heater only operation)
(To be activated only when powered ON)
OFF*2
SW3-8
Freeze protection function
Active
Inactive
OFF
SW3-9
Thermo differential during comp. cycling (ON/OFF)
prevention operation
Target temp. ±3deg
Target temp. ±5deg
OFF
SW3-10
—
—
—
OFF
SW4
SW4-1
Pressure sensor
WITHOUT Pressure sensor
WITH Pressure sensor
OFF
SW4-2
Flow sensor
WITHOUT Flow sensor
WITH Flow sensor
OFF
SW4-3
—
—
—
OFF
SW4-4
—
—
—
OFF
SW4-5
—
—
—
OFF
SW6
SW6-1
Analog input setting
SW6-1
SW6-2
Operation
OFF
OFF
0-10V or Not used
ON
OFF
—
OFF
ON
1-5V
ON
ON
4-20mA
OFF
SW6-2
OFF
5.1. Dip switch functions
Located on the FTC2BR printed circuit board are 5 sets of small white switches
known as Dip switches. The Dip switch number is printed on the circuit board next
to the relevant switches. The word ON is printed on the circuit board and on the Dip
switch block itself. To move the switch you will need to use a pin or the corner of a
thin metal ruler or similar.
Dip switch settings are listed below.
Make sure to turn off both indoor unit and outdoor unit power supplies before
changing the switch settings.
Note: 1. When the FTC2BR is connected with a
outdoor unit of which maximum outlet water temperature is 55ºC, Dip SW1-10 must be changed to OFF.
2. If emergency mode is no longer required, return the switch to OFF position.
5. Dip switch setting
SW6
SW1,SW2,
SW3,SW4
en