background image

En-3

*2

1-5. INSTALLATION DIAGRAM

Units should be installed by licensed contractor according to local code requirements.

After the leak test, apply insulat-

ing material tightly so that there 

is no gap.

ACCESSORIES (MXZ-6D122VA only)

Check the following parts before installation.

(1) Drain socket

1

(2) Drain cap

5

PARTS TO BE PROVIDED AT YOUR SITE

(A) Power supply cord*1

1

(B) Indoor/outdoor unit connecting wire*1

1

(C) Extension pipe

1

(D) Wall hole cover

1

(E) Piping tape

1

(F)

Extension drain hose 

(or soft PVC hose, 15 mm inner 

diameter or hard PVC pipe VP16)

1

(G) Refrigeration oil

Little 

amount

(H) Putty

1

(I) Pipe fixing band

2 to 7

(J) Fixing screw for (I)

2 to 7

(K) Wall hole sleeve

1

(L)

Soft PVC hose, 15 mm inner diam-

eter or hard PVC pipe VP16 for drain 

socket (1)

1

Note:

*1  Place indoor/outdoor unit connecting wire (B) and 

power supply cord (A) at least 1 m away from the 

TV antenna wire.

The “Q’ty” for (B) to (K) in the above table is quantity 

to be used per indoor unit.

More than 

100 mm

Open as a rule

More than 500 mm 

if the front and both 

sides are open

More than 100 mm 

More than 200 mm if there are 

obstacles to both sides

Open as a rule

More than 500 mm if the back, 

both sides and top are open

More than 350 mm

Outdoor unit installation

Air inlet

Air outlet

Air inlet

950 mm
600 mm

175 

mm

2-U-shape notched holes

(Base bolt M10)

330

 mm

2 - 12 mm × 36 mm  

oval holes (Base bolt M10)

370

 mm

417

 mm

When the piping is to be attached to 

a wall containing metals (tin plated) 

or metal netting, use a chemically 

treated  wooden  piece  20  mm  or 

thicker between the wall and the 

piping or wrap 7 to 8 turns of insula-

tion vinyl tape around the piping.

To use existing piping, perform 

COOL  operation  for  30  minutes 

and pump down before removing 

the old air conditioner. Remake flare 

according to the dimension for new 

refrigerant.

1-6. DRAIN PIPING FOR OUTDOOR UNIT (MXZ-6D122VA only)

(1) Drain socket

(L) Soft PVC hose

(2) Drain cap

1)  Perform the drain piping work only when draining from one place.

2)  Provide drain piping before indoor and outdoor piping connection. 

3)  Attach the drain socket to one of the several drain holes.

  Fix the drain socket into the drain hole of the base using the catches to secure 

it in place.

4)  Connect the soft PVC hose I.D.15 mm as shown in the illustration.

5)  Make sure to provide drain piping with a downhill grade for easy drain flow.

6)  Glue  the  drain  caps  to  close  all  the  other  unnecessary  holes  with  the  glue 

(Prepare in the field).

Note:

Apply the glue securely, as the glue (Prepare in the field) will work as seal to 

prevent water from leaking.

Use the adhesive for the rubber and metal.

Attention

The outdoor unit is provided with several holes for drainage at the bottom to make 

drainage easier. 

The drain socket is used to close the unnecessary holes and centralize the drain-

age when using the drain tube at the installation place.

Do not to use the drain socket in cold region. The drain tube can be frozen.

*2  The manufacturing year and month is indicated on the spec name plate.

BH79A198H01_en.indd   3

6/2/2015   5:48:27 PM

Содержание MXZ-4E83VAHZ

Страница 1: ...nuale di instal lazione Εγχειρίδιο εγκατάστασης Για τον ΤΕΧΝΙΚΟ Στο παρόν εγχειρίδιο περιγράφεται μόνο η εγκατάσταση της μονάδας εξωτερικού χώρου Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidad...

Страница 2: ...ng sections so the stress of the wires is not applied to the sections Do not extend the wires or use intermediate connection Incomplete connecting and securing could cause fire n Do not install the unit in a place where inflammable gas may leak If gas leaks and accumulates in the area around the unit it could cause an explosion n Do not use intermediate connection of the power cord or the extensio...

Страница 3: ...ind it is recommended to install a baffle board on the air outlet side of the outdoor unit Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring sewage waste water Where there is high frequency or wireless equipme...

Страница 4: ...iping is to be attached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insula tion vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for new refri...

Страница 5: ...ot to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 ...

Страница 6: ...ith Fig 6 If flare is noted to be defective cut off the flared section and do flaring work again WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side of the outdoor ...

Страница 7: ...o lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please note that the cooling and heating capacity may lower if this function is activated Changing the setti...

Страница 8: ...tronic control P C board damage make sure to perform static elimination before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED1 Red LED2 Yellow LED3 Green Lighted Lighted Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lighted Not lighted Lighted Completed Problem correct...

Страница 9: ... plaque du produit Opmerking het serienummer staat op het naamplaatje van het product Nota El número de serie se encuentra en la placa que contiene el nombre del producto Nota il numero di serie si trova sulla targhetta del prodotto Σημείωση Ο σειριακός του αριθμός βρίσκεται στην πινακίδα ονόματος του προϊόντος Nota o número de série encontra se na placa que contém o nome do produto Bemærk Serienu...

Отзывы: